diC
"
Default non
DI Config
This is the digital input used for a digital sensor or bus communications.
"
non
": not used.
"
doC
": door contact, contact closed when door closed.
"
doo
": door contact, contact open when door closed.
"
ECo
": external input to control ECO mode.
"
Pir
": motion sensor. Passive infrared.
"
o1C
"
Default CoP
D01 Config
"
CoP
": direct compressor control.
"
PiC
": pilot Relay (no zero cross) – if using pilot relay to control a
compressor, this option must be used instead of "
CoP
".
"
HEt
": heating application, inverse output.
"PiH": pilot heat relay (no zero cross).
"
o2C
"
Default dEF
D02 Config/o2C
D03 Config/o3C
D04 Config/o4C
"no": not used.
"dEF": electric defrost heater/valve for hot gas.
"ALA": alamr output.
"FAn": fan control.
"Lig": light control.
"
o3C
"
Default FAn
"
o4C
"
Default Lig
"
b1C
"
Default noP
Lower left button:
Button 1 Config (short press)/b1C
Button 1 Config (long press)/b1L
Upper left button:
Button 2 Config (short press)/b2C
Button 2 Config (long press)/b2L
Upper right button:
Button 3 Config (short press)/b3C
Button 3 config (long press)/b3L
Lower right button:
Button 4 Config (short press)/b4C
Button 4 Config (long press)/b4L
"
b1L
"
Default PoF
"
b2C
"
Default dEF
"
b2L
"
Default inF
"
b3C
"
Default tP
"
b3L
"
Default ECo
"
b4C
"
Default tn
"
b4L
"
Default Lig
"
b5C
"
Default noP
Button 5 Config (short press) / b5C
Button 5 Config (long press) / b5L
(Button 5 is an external button option which can be
connected and configured through S4 sensor.)
"
b5L
"
Default noP
Short press function
Long Press function (3 s.)
"
noP
": not operating
"
ECo
": toggle ECO mode
"
SuP
": toggle super-cool/pull down
"
Lig
": toggle light
"
dEF
": toggle defrost
"
noP
": Not operating
"
ECo
": Toggle Eco mode
"
SuP
": Toggle Super-Cool /Pull-down
"
Lig
": Toggle light
"
dEF
": Toggle defrost
"
PoF
": ERC power ON/OFF
"
HoL
": enter holiday mode
1
2
3
4
The buttons can be programmed as follows:
Short press function
Long press function (3 s.)
"
noP
": not operating
"
tP
": increase set point
"tn": decrease set point
"
ECo
": toggle Eco mode
"
Lig
": toggle light
"
dEF
": toggle defrost
"
SuP
": toggle super-cool/pull down
"
diP
" : increase display intensity
"
din
" : decrease display intensity
"
CFA
": toggle °C and °F
"
noP
": not operating
"
tP
": increase set point
"
tn
": decrease set point
"
ECo
": toggle Eco mode
"
Lig
": toggle light
"
dEF
": toggle defrost
"
SuP
": toggle super-cool/pull down
"
diP
": increase display intensity
"
din
": decrease display intensity
"
CFA
": toggle °C and °F
"
PoF
": ERC power ON/OFF
"
HoL
": enter holiday mode
"
inF
": enter info menu
"
tEc
": Toggle Winter & Summer Eco mode
NOTE: Your assignments may not be shown on the printed buttons. We advice to
use this functionality together with the fully integrated mounting model only.
User Guide | ERC 112 Refrigeration Controller
22 | BC200686422115en-000802