FSt
"
Min. 0 s
Max. 960 s
Default 10 s
Fan Minimum Stop time
Minimum stop time for fan protection.
"
FdC
"
Min. -10.0 K
Max. 10.0 K
Default 0.0 K
Fan
Δ
t cut in
(This parameter is only applicable with Automatic fan control "Aut" mode.)
Delta T for fan to cut in which the temperature offset comparing with
thermostat cut in temperature.
"
Fdt
"
Min. 0 s
Max. 999 s
Default 0 s
Fan stop time on door open
The delay with wich the fan will be stopped after the door has been opened.
"
0
": fan stop immediately when door open.
"
1-998
": delay for fan stop after door open.
"
999
": fan keep running all the time during door open.
"
FLt
"
Min. 0°C
Max. 50°C
Default 50
Fan limit temperature
This function prevents the evaporator fan to operate if the temperature is
above the fan limit temperature.
If the defrost sensor registers a higher temperature than the one set here,
the fan will be stopped to avoid the warm air circulation in the cabinet. This
parameter is active only when evaporator sensor is connected.
"
FdF
"
Min. 1 K
Max. 10 K
Default 2
Fan limit Delta temperature
This is the evaporator delta temperature for the fan to switch ON after it is
switched off due to FLt setting.
Lig
Light settings
"
CLC
"
Min. on
Max. dor
Default on
Cabinet Light Source Control
This parameter can be set to one of these alternatives to control the light
in the cabinet:
"
on
": always ON.
"
oFF
": always OFF.
"
dor
": door sensor only.
"
Lod
"
Min. 0 s
Max. 300 s
Default 0 s
Light OFF delay
Number of seconds the light will stay ON after the door has been closed.
Pud
Pull Down settings
Pull down (sometimes known as Super Cool) is a procedure for improving
cooling performance, accelerating the time used to reach the desired
temperature. Pull down settings overrule all other settings.
"
Pit
"
Min. -40.0°C
Max. 50.0°C
Default 50.0°C
Pull Down Initiate Temperature
This parameter indicates the temperature which causes a pull
down to start. If the temperature measured inside the cabinet
exceeds this value for longer than one hour, then pull down will
start. The compressor will have already cut-in, so the only effect
is to stop defrost cycles until the desired temperature is reached.
The period of one hour is fixed and cannot be altered.
"
PCy
"
Min. 0 min
Max. 360 min
Default 30 min
Pull Down Cycling
This is the duration in minutes of the compressor cycling at the reduced
set point temperature. Once the desired pull down limit temperature
"
PLt
" has been reached during pull down, the compressor will continue to
cycle ON/OFF for the duration of "
PCy
". At the end of the period defined by
"
PCy
", the set point temperature will return to normal and pull down will
cease.