Anti-condensation heater connector
1
Anti-condensation heater connector (inside the connection box)
2
Inlet and cable gland for the anti-condensation heater cable
After the installation of the electric machine, and any time when needed, the resistance of the warming
element can be measured. Connect the measurement device between the heater terminals. The
resistance should be around 1 kΩ. Measuring no value, or zero value, indicates a possible failure in the
heater element.
If the electric machine has an anti-condensation heater and failure is suspected, contact Danfoss
representative.