Blueglobe cable gland tightening torques (continued)
Metric thread
Nominal torque
M63x1,5
35,0 Nm
M75x1,5
80,0 Nm
M85x2,0
100,0 Nm
1. Remove the small hexagonal piece from the BlueGlobe-sealing insert as shown in Figure below.
BlueGlobe-sealing
2. Cut the cable sheath at the distance A from the end of the cable, see Figure below. Pull the cut part of
the sheath partly (length B is from 10 to 15 mm) off the cable as shown in the Figure. The distance A
depends of the length of the cable lug used. Measure with the cable lug that is used and cut to
suitable length.
Install two layers of copper tape on the cable so that the distance B is covered. Use 3M
™
Copper Foil Tape 1181 or similar.
The maximum distance between the copper tape or the shield (braid) of the cable and the
cable lug or the conductor (which ever is closer), is 10 mm.
Do not remove the cable sheath completely at this point and do not cut the braid screen of
the cable!
Cut length of the cable sheath