Analog input selection

Configure Analog signal type by selecting DIP switch as shown in below table (green denotes ON).

Analog Input

DIP Switch

1

2

3

4

5

6

7

8

0 - 10 V (Default)
0 - 5 V
4 - 20 mA
0 - 20 mA

Stepper driver 1 

DIP Switch

1

2

3

4

5

6

7

8

Analog Input AI1
Analog input AI2

Analog input sharing

Configure analog input to be shared if needed as below (green denotes ON).

Digital output signal

One digital output is present in EKF and only alarm activates the output. 

Output type

Similar to NPN, open collector

Load type

Resistive only

Maximum allowed current

10 mA

Maximum Voltage

28 V  (allow 24 V DC + 15%)

Stepper Motor Output

•   The stepper motor is connected to the “Stepper Valve” terminals (see connection overview) with a standard M12 
   connection cable or JST XHP-5 connector.
•   The default valve setting in EKF 1A/2A is: No Valve.
•   The correct valve must be defined as per section DIP Switch – Valve

Stepper driver 2

DIP Switch

1

2

3

4

5

6

7

8

Analog Input AI1
Analog input AI2

Valve Cable Connection 

Danfoss recommends to use ETS 5M and ETS 6 valves to be connected to JST XHP-5 pin connectors instead of 4 pole terminal 
block, but it is possible to connect to terminal block, follow color codes of wires of coil as shown in table below.

Stepper valve

ETS/KVS/CCM/ CCMT/CTR/ CCMT L

ETS 5M

ETS 6

A1

White

Brown

Orange

A2

Black

Black

Yellow

B1

Red

Orange

Red

B2

Green

Yellow

Black

While using JST 5pin, its plug and play for ETS 6 and ETS 5M valves. 

Guideline for long M12 cables for Danfoss stepper motor valves

•    Long cables will lead to degradation of performance. 
•    Cable length for stepper motor connection must be less than 30 m. 
•    Danfoss recommends to use 4-20 mA signal for long distances and use shorter cable between driver and valve. 

Summary of Contents for EKF Series

Page 1: ...nalog inputs EKF 1A 1 input AI1 0 5 V 0 10 V 4 20 mA 0 20 mA EKF 2A 2 inputs AI1 and AI2 0 5 V 0 10 V 4 20 mA 0 20 mA Max 15 V Analog input voltage Do not connect voltage sources to unpowered units wi...

Page 2: ...tery backup is galvanic isolated and the polarity of power supply is maintained correct The same should be observed while sharing power supply with EKF and master controller AI signal Connect PE eithe...

Page 3: ...EKF to power and the device is ready to use LED indication Valve Two status LED per valve output Each stepper drive has a set of Red and Green LED as shown in image The change in LED light with the L...

Page 4: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 0 1 Alarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0s 1sec 2sec...

Page 5: ...be selected to ETS 250 ETS 400 Dip switch of driver 2 should be selected to Manifold Valves ETS 500P ad ETS 800P Valve DIP Switch 1 2 3 4 5 6 7 8 A No Valve Default B ETS 12C ETS 24C ETS 25C ETS 50C...

Page 6: ...onnection cable or JST XHP 5 connector The default valve setting in EKF 1A 2A is No Valve The correct valve must be defined as per section DIP Switch Valve Stepper driver 2 DIP Switch 1 2 3 4 5 6 7 8...

Page 7: ...ecommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device from the main power supply Before...

Reviews: