Application

Valve Driver

EKF 1A

EKF 2A

ETS Colibri

Analog signal AI1

Digital out

Digital out

AI 1
AI 2

ETS Colibri

ETS Colibri

•    Supports both Bipolar and Unipolar motor.
•    Only one connection can be used, either 4 pole terminal block or JST XHP-5 pin connector. 
•   It is possible to share power supply with 2 EKF and battery backup if battery backup is galvanic isolated and the polarity of power  
    supply is maintained correct. The same should be observed while sharing power supply with EKF and master controller (AI signal)• 
•  Connect PE either to the       or      of power connector. If grounding is done in the transformer do not use EKF grounding connector.

Connection overview

EKF 1A

AI1

Analog input 1

COM

Common

AI2

Analog input 2 for EKF2A only

COM

Common

DO1

Digital output 1

Wire Color scheme 

1Green
2 Red
3 Black
4 White

EKF 2A

1 2  3 4

1 2  3 4

1 2  3 4

Koolkey

Koolkey

Kooprog pc tool

Kooprog pc tool

Dip S

wit

ch2

Dip S

wit

ch1

Dip S

wit

ch

Summary of Contents for EKF Series

Page 1: ...nalog inputs EKF 1A 1 input AI1 0 5 V 0 10 V 4 20 mA 0 20 mA EKF 2A 2 inputs AI1 and AI2 0 5 V 0 10 V 4 20 mA 0 20 mA Max 15 V Analog input voltage Do not connect voltage sources to unpowered units wi...

Page 2: ...tery backup is galvanic isolated and the polarity of power supply is maintained correct The same should be observed while sharing power supply with EKF and master controller AI signal Connect PE eithe...

Page 3: ...EKF to power and the device is ready to use LED indication Valve Two status LED per valve output Each stepper drive has a set of Red and Green LED as shown in image The change in LED light with the L...

Page 4: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 0 1 Alarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0s 1sec 2sec...

Page 5: ...be selected to ETS 250 ETS 400 Dip switch of driver 2 should be selected to Manifold Valves ETS 500P ad ETS 800P Valve DIP Switch 1 2 3 4 5 6 7 8 A No Valve Default B ETS 12C ETS 24C ETS 25C ETS 50C...

Page 6: ...onnection cable or JST XHP 5 connector The default valve setting in EKF 1A 2A is No Valve The correct valve must be defined as per section DIP Switch Valve Stepper driver 2 DIP Switch 1 2 3 4 5 6 7 8...

Page 7: ...ecommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device from the main power supply Before...

Reviews: