Installation guide

Stepper Valve Driver

 

Type EKF 1A, EKF 2A 

080

R0

43

5

© Danfoss | Climate Solutions | 2021.07

AN375548103097en-000202 | 1

Імпор

тер:Т

ОВ з іі "Д

анфос

с Т

ОВ" 04080, Київ 80, п/с 168, У

країна

Inf

o f

or UK cust

omers only

: Danf

oss L

td

., 22 

W

yc

ombe End

, HP9 1NB

, GB

080

R0

43

5

Introduction

Stepper Valve Driver EKF series is for use where stepper motor valves must be accurately controlled, 

typically in commercial air conditioning, heat pumps, commercial refrigeration and food retailing 

applications. 

Supply voltage

EKF 1A: 24 V AC / DC  50 / 60 Hz
EKF 2A: 24 V AC / DC, 50 / 60 Hz

Power consumption

Idle operating:                            < 1 W (without valve)
Power consumption for using 1 valve. 
CCMT 16 – CCMT 42:                25 VA / 15 W
ETS 5M, ETS 6:                            20 VA / 10 W
ETS 12C – ETS 100C, KVS C:    30 VA /15 W
ETS 12.5 – 400:                           10 VA / 5 W
ETS 500P, 800P:                          28 VA / 20 W
CCMT 2- CCMT 8:                       10 VA / 5 W
CTR 20:                                          14 VA / 10 W
CCMT L:                                         20 VA / 10 W
When using two valves sum the power consumption of each valve.

 

Analog inputs

EKF 1A: 1 input AI1

0-5 V, 0-10 V, 4-20 mA, 0-20 mA

EKF 2A: 2 inputs AI1 and AI2

0-5 V, 0-10 V, 4-20 mA, 0-20 mA

Max. 15 V Analog input voltage. Do not connect voltage sources to unpowered units 
without limiting the current to analog inputs (overall 40 mA per input). 
Input Impedance: >50 kΩ  (Voltage Input) 120 Ω ± 2% (Current Input)

 

Digital outputs

1 output for EKF1A / EKF 2A: D01 (open collector), sink current max 10 mA

Valve support

EKF 1A: 1 stepper motor valve output, EKF 2A: 2 stepper motor valve output

STEPPER 1: A1, A2, B1, B2

STEPPER 2: A1, A2, B1, B2

Bipolar and unipolar stepper motor output:

- Danfoss ETS / KVS / ETS C / KVS C / CCMT 2 – CCMT 42 / CTR / CCMT L    Valves 

- ETS 6 / ETS 5M Valves 
Open circuit HW diagnostics is present.

Battery backup

1 input for EKF 1A / EKF2A: Vbat

BAT, GND: Nominal 18 – 24 V DC, Min 16 V DC - Max 28 V DC (EKE 2U 

recommended)

Max. battery current: 2 A at 18 V (valve depended)

Battery alarm/warning will be activated below 16 V DC. 

Enviroment

Storage

-30 – 80 °C / -22 – 176 °F

Operating

-20 – 60 °C / -4 – 140 °F

Humidity

< 90% RH, non-condensing

DIN Mounting

4 DIN

Technical Specificatons

Summary of Contents for EKF Series

Page 1: ...nalog inputs EKF 1A 1 input AI1 0 5 V 0 10 V 4 20 mA 0 20 mA EKF 2A 2 inputs AI1 and AI2 0 5 V 0 10 V 4 20 mA 0 20 mA Max 15 V Analog input voltage Do not connect voltage sources to unpowered units wi...

Page 2: ...tery backup is galvanic isolated and the polarity of power supply is maintained correct The same should be observed while sharing power supply with EKF and master controller AI signal Connect PE eithe...

Page 3: ...EKF to power and the device is ready to use LED indication Valve Two status LED per valve output Each stepper drive has a set of Red and Green LED as shown in image The change in LED light with the L...

Page 4: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 0 1 1 1 1 1 0 1 Alarm 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0s 1sec 2sec...

Page 5: ...be selected to ETS 250 ETS 400 Dip switch of driver 2 should be selected to Manifold Valves ETS 500P ad ETS 800P Valve DIP Switch 1 2 3 4 5 6 7 8 A No Valve Default B ETS 12C ETS 24C ETS 25C ETS 50C...

Page 6: ...onnection cable or JST XHP 5 connector The default valve setting in EKF 1A 2A is No Valve The correct valve must be defined as per section DIP Switch Valve Stepper driver 2 DIP Switch 1 2 3 4 5 6 7 8...

Page 7: ...ecommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device from the main power supply Before...