DKRCI.PI.RP0.C1.02 / 520H8794 

© Danfoss A/S (RC-MDP/MWA), 2014-08

Setup & service menu 

(Requires Log-In. Password to be assigned in Commisioning menu)

Parameter

Options

User level - access

Default 

values

Daily

Service

Commissioning

Reference

Main switch

On, Off

RW

RW

RW

Off

Liquid level setpoint

0 - 100%

RW

RW

RW

50.0%

Operation mode

Master, IO, Slave

R

R

RW (L)

Master

Alarm setup

Lower level limit

0 - 100%

RW

RW

RW

15%

Upper level limit

0 - 100%

RW

RW

RW

85%

Level alarm mode

Time, Hysteresis

R

R

RW

Time

Lower delay

0 - 999 sec

R

RW

RW (D)

10 sec

Upper delay

0 - 999 sec

R

RW

RW (D)

50 sec

Lower level hysteresis

0-20 %

R

RW

RW (D)

3%

Upper level hysteresis

0-20 %

R

RW

RW (D)

5%

Function common alarm

Not follow; Follow up; Follow low; Follow all

R

R

RW

Not follow

Oscillation detect band

0 - 100%

R

RW

RW (D)

100%

Oscillation detect timeout

2 - 30 min

R

RW

RW (D)

20 min

IO Lower level limit

0 - 100%

RW

RW

RW (D)

5%

IO Upper level limit

0 - 100%

RW

RW

RW (D)

95%

IO Lower level hysteresis

0-20 %

R

RW

RW (D)

3%

IO Upper level hysteresis

0-20 %

R

RW

RW (D)

3%

IO Lower delay

0 - 999 sec

R

RW

RW (D)

10 sec

IO Upper delay

0 - 999 sec

R

RW

RW (D)

50 sec

IO Level limit

0 - 100%

R

RW

RW (D)

50%

IO Level delay

0 - 999 sec

R

RW

RW (D)

10 sec

IO Level hysteresis

0-20 %

R

RW

RW (D)

3%

IO Level action

Falling,Rising

R

RW

RW (D)

Falling

Control

Control Method

On/Off ,P, PI

R

RW

RW

PI

Regulating principle

Low, High

R

RW

RW

Low

P-band

5 - 200%

R

RW

RW (D)

30.0%

Integration time Tn

60 - 600 sec

R

RW

RW (D)

400 sec

Neutral zone

0 - 25%

R

RW

RW (D)

2.0%

Difference

0,5-25%

R

RW

RW (D)

2%

Period time for AKV/AKVA

3-15 sec

R

RW

RW (D)

6 sec

Minimum OD

0 - 99%

R

RW

RW (D)

0%

Maximum OD

1 - 100%

R

RW

RW (D)

100%

Display

Language

EN,CN,PT,RU,SP,FR,IT, GER, ARAB

R

RW (L)

RW (L) (D)

EN

Output indication

level, OD

R

RW

RW (D)

Level

Login timeout

0 - 120 min

R

RW

RW

10 min

Backlight timeout

0 - 120 min

RW

RW

RW

2 min

Password daily

3 -digit, 0 - 999

N/A

N/A

RW

100

Password service

3 -digit, 0 - 999

N/A

N/A

RW

200

Password commission

3 -digit, 0 - 999

N/A

N/A

RW

300

IO config

System configuration

ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only

R

R

RW (L)

ICAD + NC

Level signal setup

AKS 4100, AKS 41, Current, Voltage

R

R

RW (L)

AKS4100

Voltage at low liquid level

0-10V

R

RW

RW (D)

0 V

Voltage at high liquid level

0-10V

R

RW

RW (D)

10 V

Current at low liquid level

0-20 mA

R

RW

RW (D)

4 mA

Current at high liquid level

0-20 mA

R

RW

RW (D)

20 mA

Valve position setup

Not used, Current, Voltage

R

R

RW (L)

Not used

Voltage at closed valve 

position

0-10V

R

RW

RW (D)

0 V

Voltage at open valve 

position

0-10V

R

RW

RW (D)

10 V

Current at closed valve 

position

0-20 mA

R

RW

RW (D)

4 mA

Current at open valve 

position

0-20 mA

R

RW

RW (D)

20 mA

Common alarm setup

D04, High alarm, D03, Disp only

R

R

RW (L)

High alarm

Multiple valve setup

Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap

R

R

RW (L)

Not used

Multiple valve pattern

Parallel,Sequence

R

R

RW (D)

Parallel

Valve A capacity

0-100 %

R

R

RW (L) (D)

50%

Valve B capacity

0-100 %

R

R

RW (L) (D)

50%

Valve C capacity

0-100 %

R

R

RW (L) (D)

30%

ICAD takeover OD

0-100%

R

RW

RW (D)

80%

IO module setup

Used, Not used

R

R

RW (L) (D)

Not used

Communication

CAN ID

1 - 127

R

R

RW

1

CAN baudrate

20k, 50k, 125k, 250k, 500k, 1M

R

R

RW

500k

Modbus ID

0 - 120 

R

R

RW

1

Modbus baudrate

0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400 

R

R

RW

19200

Modbus mode

8N1, 8E1, 8N2

R

R

RW

8N1

Modbus mapping

Operation, Setup

R

R

RW

Operation

Valve B CAN ID

1 - 127

R

R

RW (D)

2

Valve C CAN ID

1 - 127

R

R

RW (D)

3

IO Mod. CAN ID

1 - 127

R

R

RW (D)

4

RW = Read & Write                        R = Read only                           N/A = Not shown                             (L) = Locked by Mainswitch ( Switch OFF Mainswitch for change of setting)

(D) = Parameter is hidden if not active in the selected application

Summary of Contents for EKE 347

Page 1: ...0 1 080G5000 2 110 5 70 60 63 Danfoss 80G74_ 01 2014 Liquid Level Regulating principle ICM with ICAD motor EKE 347 Danfoss 80G75_06 2014 AKS 4100 AKS 4100U Danfoss 80G76_06 2014 EKE 347 AKS 4100 AKS 4...

Page 2: ...e display ModBUS 4 20 mA 24 V DC yellow blue orange ICAD 1st gen ICAD ICM feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 yellow gray orange ICAD 1st gen pre 2010 ICAD 2nd gen 2010 yellow green brown bro...

Page 3: ...C 2 NO 2 NO 1 C 1 NC 1 POWER SUPPLY AKV AKVA 24 V AC 20 15 VA 24 V DC 20 10 W Common Normally Open or Normally Closed Low Level Alarm Normally Open or Normally Closed High Level Alarm Normally Open or...

Page 4: ...ication Open Close solenoid valve with coil 24V 230V AKS 4100 AKS 4100U Danfoss M84H0084_1 MASTER I O AKVA ICAD R120 CAN H CAN L GND 15 16 17 18 R120 CAN H CAN L GND 15 16 17 18 Jumper 15 16 Jumper 15...

Page 5: ...mode Lower level alarm off pump on Upper level alarm off Power on 1st time Power on Setup Wizard A guided configuration of EKE 347 Home Image Log in Press and hold Short press on Reference Alarm setup...

Page 6: ...the set value is passed 30 32 Relay for upper level limit Installer can choose between Normally Open 30 31 or Normally Closed 31 32 circuits The relay will switch when the set value is passed 6 10 ICM...

Page 7: ...no alarm is active Level signal out of range hours minutes Standby mode hours minutes Detailed status Controller state Stop Manual Auto Slave IO Actual level 0 0 100 Actual reference 0 0 100 Actual OD...

Page 8: ...ndication level OD R RW RW D Level Login timeout 0 120 min R RW RW 10 min Backlight timeout 0 120 min RW RW RW 2 min Password daily 3 digit 0 999 N A N A RW 100 Password service 3 digit 0 999 N A N A...

Page 9: ...R R D Actual OD C R R R D Manual Mode On Off R RW RW D Off Manual OD 0 100 R RW RW D 50 0 Manual low alarm Off On R RW RW D Off Manual high alarm Off On R RW RW D Off Manual common alarm Off On R RW...

Page 10: ...a to e 1 Language You can select any of these 9 languages English Chinese Portuguese Russian Spanish French Italian German Arabic 2 System configuration Select any of these 5 predefined configura tion...

Page 11: ...Danfoss A S RC MDP MWA 2014 08 DKRCI PI RP0 C1 02 520H8794 11...

Page 12: ...12 DKRCI PI RP0 C1 02 520H8794 Danfoss A S RC MDP MWA 2014 08 www danfoss com ir...

Reviews: