8
DKRCI.PI.RP0.C1.02 / 520H8794
© Danfoss A/S (RC-MDP/MWA), 2014-08
Setup & service menu
(Requires Log-In. Password to be assigned in Commisioning menu)
Parameter
Options
User level - access
Default
values
Daily
Service
Commissioning
Reference
Main switch
On, Off
RW
RW
RW
Off
Liquid level setpoint
0 - 100%
RW
RW
RW
50.0%
Operation mode
Master, IO, Slave
R
R
RW (L)
Master
Alarm setup
Lower level limit
0 - 100%
RW
RW
RW
15%
Upper level limit
0 - 100%
RW
RW
RW
85%
Level alarm mode
Time, Hysteresis
R
R
RW
Time
Lower delay
0 - 999 sec
R
RW
RW (D)
10 sec
Upper delay
0 - 999 sec
R
RW
RW (D)
50 sec
Lower level hysteresis
0-20 %
R
RW
RW (D)
3%
Upper level hysteresis
0-20 %
R
RW
RW (D)
5%
Function common alarm
Not follow; Follow up; Follow low; Follow all
R
R
RW
Not follow
Oscillation detect band
0 - 100%
R
RW
RW (D)
100%
Oscillation detect timeout
2 - 30 min
R
RW
RW (D)
20 min
IO Lower level limit
0 - 100%
RW
RW
RW (D)
5%
IO Upper level limit
0 - 100%
RW
RW
RW (D)
95%
IO Lower level hysteresis
0-20 %
R
RW
RW (D)
3%
IO Upper level hysteresis
0-20 %
R
RW
RW (D)
3%
IO Lower delay
0 - 999 sec
R
RW
RW (D)
10 sec
IO Upper delay
0 - 999 sec
R
RW
RW (D)
50 sec
IO Level limit
0 - 100%
R
RW
RW (D)
50%
IO Level delay
0 - 999 sec
R
RW
RW (D)
10 sec
IO Level hysteresis
0-20 %
R
RW
RW (D)
3%
IO Level action
Falling,Rising
R
RW
RW (D)
Falling
Control
Control Method
On/Off ,P, PI
R
RW
RW
PI
Regulating principle
Low, High
R
RW
RW
Low
P-band
5 - 200%
R
RW
RW (D)
30.0%
Integration time Tn
60 - 600 sec
R
RW
RW (D)
400 sec
Neutral zone
0 - 25%
R
RW
RW (D)
2.0%
Difference
0,5-25%
R
RW
RW (D)
2%
Period time for AKV/AKVA
3-15 sec
R
RW
RW (D)
6 sec
Minimum OD
0 - 99%
R
RW
RW (D)
0%
Maximum OD
1 - 100%
R
RW
RW (D)
100%
Display
Language
EN,CN,PT,RU,SP,FR,IT, GER, ARAB
R
RW (L)
RW (L) (D)
EN
Output indication
level, OD
R
RW
RW (D)
Level
Login timeout
0 - 120 min
R
RW
RW
10 min
Backlight timeout
0 - 120 min
RW
RW
RW
2 min
Password daily
3 -digit, 0 - 999
N/A
N/A
RW
100
Password service
3 -digit, 0 - 999
N/A
N/A
RW
200
Password commission
3 -digit, 0 - 999
N/A
N/A
RW
300
IO config
System configuration
ICAD+NC, ICAD, AKV/A+NC, AKV/A, NC only
R
R
RW (L)
ICAD + NC
Level signal setup
AKS 4100, AKS 41, Current, Voltage
R
R
RW (L)
AKS4100
Voltage at low liquid level
0-10V
R
RW
RW (D)
0 V
Voltage at high liquid level
0-10V
R
RW
RW (D)
10 V
Current at low liquid level
0-20 mA
R
RW
RW (D)
4 mA
Current at high liquid level
0-20 mA
R
RW
RW (D)
20 mA
Valve position setup
Not used, Current, Voltage
R
R
RW (L)
Not used
Voltage at closed valve
position
0-10V
R
RW
RW (D)
0 V
Voltage at open valve
position
0-10V
R
RW
RW (D)
10 V
Current at closed valve
position
0-20 mA
R
RW
RW (D)
4 mA
Current at open valve
position
0-20 mA
R
RW
RW (D)
20 mA
Common alarm setup
D04, High alarm, D03, Disp only
R
R
RW (L)
High alarm
Multiple valve setup
Not used, 2 same cap, 2 dif cap, 3 same cap, 3 dif cap
R
R
RW (L)
Not used
Multiple valve pattern
Parallel,Sequence
R
R
RW (D)
Parallel
Valve A capacity
0-100 %
R
R
RW (L) (D)
50%
Valve B capacity
0-100 %
R
R
RW (L) (D)
50%
Valve C capacity
0-100 %
R
R
RW (L) (D)
30%
ICAD takeover OD
0-100%
R
RW
RW (D)
80%
IO module setup
Used, Not used
R
R
RW (L) (D)
Not used
Communication
CAN ID
1 - 127
R
R
RW
1
CAN baudrate
20k, 50k, 125k, 250k, 500k, 1M
R
R
RW
500k
Modbus ID
0 - 120
R
R
RW
1
Modbus baudrate
0, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400
R
R
RW
19200
Modbus mode
8N1, 8E1, 8N2
R
R
RW
8N1
Modbus mapping
Operation, Setup
R
R
RW
Operation
Valve B CAN ID
1 - 127
R
R
RW (D)
2
Valve C CAN ID
1 - 127
R
R
RW (D)
3
IO Mod. CAN ID
1 - 127
R
R
RW (D)
4
RW = Read & Write R = Read only N/A = Not shown (L) = Locked by Mainswitch ( Switch OFF Mainswitch for change of setting)
(D) = Parameter is hidden if not active in the selected application