Connecting Modbus

 

 

•  For the MODbus cable, it is best to use  24 AWG shielded twisted-pair cable with a shunt capacitance 

 

    of 16 pF/ft and 100Ω impedance. 

 

•  The controller provides an insulated RS485 communication interface which is connected to the  

 

    RS485 terminals (see connection overview). 

 

•  The max. permissible number of devices simultaneously connected to RS485 cable output is 32.  

 

   The RS485 cable is of impedance 120 Ω with maximum length of 1000 m. 

 

•  Terminal resistors 120 Ω for terminal devices are recommended at both ends. 

 

•  The EKE communication frequency (baud rate) can be one of the following: 9600, 19200 or  

 

    38400 baud, default 19200 8 E 1. 

 

•  The default unit address is 1, which can be changed using  parameter “G001 Controller adr.”.

For a detailed explanation of Modbus installation and setting software parameters, see:
Data sheet for “EKE Superheat controller” and “EKD EIM Data Communication Modbus RS485 RTU”.

Modbus
D+
D-
Not in use
Gnd

Cable length

EKE controller supports the following max. cable length.

Cable length

Wire size min. / max.

[m]

[m

2

]

Analog inputs (Current/Voltage)

max. 10

0.14 / 1.5

Temperature sensor

max. 10 *)

Stepper valve connection

max. 30

0.14 / 1.5

Power supply

max. 5

0.2 / 2.5

Digital input

max. 10

0.14 / 1.5

Digital output

0.2 / 2.5

Digital MMI

max. 3  over CAN RJ

Communication bus

max. 1000

0.14 / 1.5

Relay Outputs

EKE 1B has 1 relay output:

•  Type SPDT relay. Digital Output can be used to connect either a solenoid valve or an alarm.
•  The relays cannot be used for the direct connection of capacitive loads such as LEDs and ON/OFF control of  

  EC motors. All loads with a switch-mode power supply must be connected with a suitable contactor or similar.

Warning

Separate the sensor and digital input cables as much as possible (at least 10 cm) from the power cables to  the 

loads to avoid possible electromagnetic disturbance. Never lay power cables and probe cables in the same 

conduits (including those in the electrical panels).

Cable and wiring *)

 

 

•  

The max. cable distance between the controller and the valve depends on many factors like shielded/ 

 

    unshielded cable, the wire size used in the cable, the output power for the controller and EMC.  

 

•  

Keep controller and sensor wiring well separated from mains wiring. 

 

•  

Connecting sensors by wires more than the specified length may decrease the accuracy of measured values.

Summary of Contents for EKE 1B

Page 1: ...eat must be accurately controlled typically in commercial air conditioning heat pumps commercial refrigeration food retailing and industrial applications Compatible valves Danfoss ETS 6 ETS ETS Colibr...

Page 2: ...cle Normally Open 3 A Inductive AC 15 250 V AC 100 k cycle Normally Closed 2 A General purpose 250 V AC 100 k cycle Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 A3 A4 Bipolar and unipolar ste...

Page 3: ...e user INSTALLATION WARNINGS Recommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device fro...

Page 4: ...C1 NC1 PWR 24V Vbat STEPPER VALVE DIGITAL OUTPUT Superheat controller EKE 1B 080G5350 DKRCC PI RS0 C6 02 4 DIN rail mounting demounting The unit can be mounted onto a 35 mm DIN rail simply by snapping...

Page 5: ...troller EKE 1B 080G5350 DKRCC PI RS0 C6 02 5 Connection overview EKE 1B Master controller Pressure transmitter e g AKS 32R Power supply 24 V AC 20 24 V DC 20 2 5 A T fuse optional Batt backup optional...

Page 6: ...tant Note Mount the sensor on a clean paint free surface Remember to use heat conducting paste and insulate the sensor For precise measurements mount the sensor max 5 cm from the outlet of the evapora...

Page 7: ...min max m m2 Analog inputs Current Voltage max 10 0 14 1 5 Temperature sensor max 10 Stepper valve connection max 30 0 14 1 5 Power supply max 5 0 2 2 5 Digital input max 10 0 14 1 5 Digital output 0...

Page 8: ...er motor valves Long cables will lead to degradation of performance You can overcome this degradation by changing the settings for the valve driver This guideline is based on the cable type being the...

Page 9: ...PC you must Connect terminals R and H on MMIMYK CAN port using a termination wire Place cable holder close to MMIMYK to keep USB connector firmly in place Keep USB cable length 1 m Place MMIMYK and ro...

Page 10: ...n controller and display is 3 m over CAN RJ CANbus requires termination in both ends of the cable by a 120 Ohm resistor to ensure reliable communication Connecting external MMIGRS2 display MMIGRS2 dis...

Page 11: ...ation and d Output configuration When using the Setup Wizard repeat the following sequence for all parameter settings a From Setup wizard select relevant parameters b Press ENTER to highlight 1st opti...

Page 12: ...ressure Select Superheat Control Set Min Max Ref value Select Other features Finish main switch ON Select the predefined refrigerant Parameter O030 Refrigerant Select Pressure transmitter type AKS 32R...

Page 13: ...2 R413A 41 449A 6 R13 15 R227 24 R170 33 R422D 42 452A 7 R13b1 16 R401 25 R290 34 427A 8 R23 17 R507 26 R600 35 R438A I081 S2 sensor configuration 3266 0 0 Not defined 1 EKS 221 2 ACCPBT NTC10K 3 MBT...

Page 14: ...Danfoss DCS az 2018 06 DKRCC PI RS0 C6 02 14 For your own notes...

Page 15: ...logging Pressure Transducer Temperature Sensor AKS Pressure Tranducer Available with ratiometric and 4 20 mA NSK Ratiometric pressure probe XSK Pressure probe 4 20 mA PT 1000 AKS is a High precision...

Reviews: