© Danfoss | DCS (az) | 2018.06
Danfoss
80G294.20
1
2
3
5
4
DKRCC.PI.RS0.C6.02 | 11
Danfoss
80G294.20
1
2
3
5
4
Power on
Login
PW:
Commissioning 300
Service 200
Daily 100
Reference
Control
QR code
Defrost
Controller info
Alarm configuration
Detailed status
IO config
SH trend 25 min
Display
Display
Communication
Service
Setup wizard
Controller name
Home menu
Setup and service
Status menu
Esc
Press and
hold enter
Setup wizard via MMIGRS2 display
When all connections to the controller have been made, after the power is switched on, the Danfoss logo will appear
for 5 seconds, then the Home screen will be displayed.
To access the Wizard: press and hold enter to access the Login screen, the commissioning password is 300, scroll down
the Setup and service menu and select “Setup wizard”.
The Wizard workflow is: a. Language selection; b. Application selection; c. Input configuration; and d.
Output configuration.
When using the Setup Wizard, repeat the following sequence for all parameter settings:
a. From
Setup wizard,
select relevant parameters.
b. Press ENTER to highlight 1st option
c. Scroll with UP / DOWN to your desired option
d. If the selected default value is acceptable, press DOWN to get to the next settings. Otherwise,
press ENTER to set your choice
e. Scroll with DOWN to the next parameter (repeat sequence a. to e.)
Note:
• If you do not have sufficient information to complete the Wizard, leave settings on their default values. To generate
the requested info, you can use Danfoss Coolselector2 software to calculate operating conditions and valve OD for the
same operating point.
• Setup Wizard only covers the most important parameters. If other features are to be enabled
(e.g. Alarm settings, MOP/LOP, etc.), they must be configured separately once the Setup Wizard is done.
Setup Wizard is also available in KoolProg PC tool.
The workflow process is the same as that described above for MMIGRS2 display.
For details, please refer to EKE data sheet.