Parameter
PNU
Default Description
R012
Main switch
3001
0
0 = regulation Off | 1 = regulation On
R102
Operation mode
3002
0
0 = Superheat control | 1 = Valve driver
I033
Driver reference
configuration
3131
-
0 = Voltage to OD | 1 = Current to OD | 2 = Modbus to OD |
3 = Modbus to steps
I034
Ext ref. voltage low
3130
0
Range 0 – 10 V. To be used with
I033
I035
Ext ref. voltage high
3129
10
Range 0 – 10 V. To be used with
I033
I067
Valve configuration
3132
0
0
= no valve,
1
= UserDef
2
= ETS 12C,
3
= ETS 24C,
4
= ETS 25C,
5
= ETS 50C,
6
= ETC 100C
7
= ETS 6,
8
=
ETS 12.5
,
9
= ETS 25
,
10
= ETS 50
,
11
= ETS 100,
12
= ETS 250
,
13
= ETS 400
14
= KVS 2C,
15
= KVS 3C,
16
= KVS 5C
17
= KVS 15,
18
= KVS 42
19
= CCMT 0,
20
= CCMT 1
21
= CCMT 2,
22
= CCMT 4,
23
= CCMT 8,
24
= CCMT 16,
25
= CCMT 24,
26
= CCMT 30,
27
= CCMT 42
28
= CCM 10,
29
= CCM 20,
30
= CCM 30,
31
= CCM 40
32
= CTR 20
O030
Refrigerant
3017
0
0 = Undef
9 = R500
18 = R402A 27 = R600a
36 = XP10
1 = R12
10 = R503
19 = R404A 28 = R744
37 = R407F
2 = R22
11 = R114
20 = R407C
29 = R1270
38 = R1234ze
3 = R134A 12 = R142b
21 = R407A 30 = R417A
39 = R1234yf
4 = R502
13 = R User
22=R407B
31 = R422A
40 = 448A
5 = R717
14 = R32
23 = R410A 32 = R413A
41 = 449A
6 = R13
15 = R227
24 = R170
33 = R422D
42 = 452A
7 = R13b1 16 = R401
25 = R290
34 = 427A
8 = R23
17 = R507
26 = R600
35 = R438A
I081
S2 sensor configuration
3266
0
0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |
4 = 112CP | 5 = Bus Shared
I083
S3 sensor configuration
3106
0
0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |
4 = 112CP | 5 = Bus Shared
I084
S4 sensor configuration
3262
0
0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K |
4 = 112CP | 5 = Bus Shared
I085
Pe transmitter configuration
3270
0
0 = Not defined | 1 = AKS 32R | 2 = ACCPBP Ratio | 3 = 112CP | 4 = OEM Ratio|
5 = NSK | 6 = AKS 32 1-5V | 7 = OEM Voltage | 8 = Bus shared
O020
Pe transmitter min. (in bar g)
3115
-1
Define pressure range in bar gauge
O021
Pe transmitter max. (in bar g)
3116
12
Define pressure range in bar gauge
N021
SH reference mode
3027
2
0 = Fixed SH | 1 = Loadap | 2 = MSS | 3 = Delta temp
N107
SH fixed setpoint ( K)
3028
7
Range 2 – 40 K
N009
SH max. ( K)
3029
9
Range 4 – 40 K
N010
SH min. ( K)
3030
4
Range 2 – 9 K
N116
SH ref. delta temp. factor ( %)
3035
65
Range 20 – 100
EKE 1B – Commonly used parameter identification
PNU
- equivalent to the Modbus register no. (Modbus a1).
Actual value are read/written as 16-bit integer values without decimals. This is the default value as read via Modbus.
For a detailed parameter list and explanation, please check the EKE data sheet.