Danfoss EKD 316 Manual Download Page 7

©Danfoss A/S (AC-MCI / sw), 2014-03 

DKRCC.PS.RP0.A1.02/520H7142 

 13

12 

DKRCC.PS.RP0.A1.02/520H7142 

©Danfoss A/S (AC-MCI / sw), 2014-03

Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

Types of regulation

As a general rule, do not use mode 2 (Load define application) 

if the effect is not evaluated by e.g. an OEM chiller 

manufacturer in a laboratory. 

An incorrect setting will only make regulation poorer than the 

factory setting of mode 1.

Single Loop (address o56 Reg.type = 1)

The EKD 316 has the traditional PI controlling function with the Kp 

factor for Proportional Gain and Tn for Integration Time in seconds. 

This is also known as the Single loop control with only one PI 

block, as shown in the diagram below. 

Instability caused by too much Proportional Gain can be corrected 

by reducing to the value of the Kp factor. 

This should be done by gradually reducing and observing the 

results before making further reductions.

If the superheat response is slow to change, it can be increased by 

reducing the value of the Integration Time Tn.

When tuning the superheat stability, it is good practice to have a 

fixed superheat reference by making 

SH max the same as SH min.

Double Loop (address o56 Reg.type = 2)

The controller can regulate the superheat using a double loop 

system. The so-called outer loop is really the same as in the single 

loop system except that the output of PI block is the reference for 

the inner loop. 

The inner loop also has a PI block where the Proportional Gain 

factor is KpT0 and the Integration Time is TnT0.

The feedback of the inner loop is the temperature difference 

between media temperature S4 and S1. This value represents the 

load on the evaporator and large values will tend to increase the 

opening degree OD% of the valve.

The tuning of the double loop is more complicated than the single 

loop and it is advisable not to change too many parameters at 

the same time. The starting point should be to use the following 

settings.

Function

Parameter

Value

Kp factor

n04

0.7

Tn sec

n05

120

KpT0

n20

3

TnT0 sec

n44

30

If the superheat is unstable, the KpT0 parameter should be slightly 

reduced. The value parameter Kp factor is not large so little is 

gained by reducing this parameter.

For details refer to the "Finding the optimum setting” section.

When to use Single or Double Loop

In most applications and especially air coolers, the single loop is 

the best option due to its simplicity and being easier to tune.

In water chillers where the S4 sensor is located at the leaving water 

outlet, the double loop gives some advantage in terms of being 

less susceptible to compressor or fan step changes. In addition, it 

opens the valve quicker during startup. However, the double loop 

is less advantageous on air coolers because of the slower response 

to the media temperature changes.

Recommended control loop type and settings for some 

applicatiions

From the experience of using single loop and double regulation, 

the following recommendations are given. These are only 

recommendations and the final choice is made by the end user.

Application

Reg. type

Kp 

factor

Tn sec

KpT0

TnT0 sec

address 

n56

address 

n04

address 

n05

address 

n20

address 

n44

Air cooler

1

(Single loop)

3.0

120

0.4

-

Water chiller

2

(Double 

loop)

0.7

120

2.0

30

 Note:

The S4 sensor has to be connected when Reg. type = 2, otherwise 

an alarm sounds.

 Note:

After o56 is changed, the controller must be switched off and 

powered up again.

There are two modes for operating the valve manually, and these 

are described in the following sections.

Operating the valve manually from the external display (or via 

MODBUS)

The opening degree of the ETS can be operated manually by 

setting parameter o18 to 1 and then setting parameter o45 to the 

required opening degree between 0% and 100%. Relay outputs 

can also be checked using parameter o18.

Operating the valve manually using an external analogue 

signal

The opening degree of the ETS 6/ETS valve can be operated 

manually with 0 to 20 mA or 4 to 20 mA or 0 to 10 V or 1 to 5 V 

external analogue signal connected to terminals 21 (-) and 22 (+) 

of the controller.

Manual control of outputs

For service purposes the ETS 6/ETS output and alarm relay outputs can be forced, but 

only when regulation has been stopped.

OFF:  No override

1: Manual control via o45 is enabled

2: The alarm relay releases so that there is a connection between 24 and 25 (= alarm)

3: The alarm relay picks up so that there is a connection between 25 and 26 (= no alarm)

018

Manual ctrl

Manual control of the valve’s opening degree

045

0-100% valve OD

Controlling a valve with an analogue signal

061

Application mode 061=1

Input signal for external control of the valve's opening degree

Only used if o61 is set to 1.

Definition of the signal's range:

0: No signal

1: 0-20 mA

2: 4-20 mA

3: 0-10 V

4: 1-5 V

(At the lower value the valve will be closed. At the upper value the value will be fully 

open. There is a linear relationship between the signal and the opening degree. The 

height of the valve is not taken into account.)

o10

AI type

Manually operating the valve

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: