Danfoss EKD 316 Manual Download Page 12

List of literature

www.danfoss.com
Click: "Technical literature" in the left bar
Click: Refrigeration and Air Conditioning  " > Technical literature"
Paste or write the no. in the box " Literature No."

 

ƒ

Catalogue 

RK0YG

 

ƒ

ETS valves, technical brochure 

DKRCC.PD.VD

 

ƒ

Installation guide for data communication 

RC8AC

Installation considerations

Accidental damage, poor installation, or site conditions can give 

rise to malfunctions of the control system, and ultimately lead to a 

plant breakdown.

Every possible safeguard is incorporated into our products to 

prevent this. However, an incorrect installation, for example, could 

still present problems. Electronic controls are no substitute for 

normal, good engineering practice.

Danfoss will not be responsible for any goods, or plant 

components, damaged as a result of the above defects. It is the 

installer‘s responsibility to check the installation thoroughly, and 

to fit the necessary safety devices.

Particular attention is drawn to the need for a "force closing" signal 

to controllers in the event of compressor stoppage, and to the 

requirement for suction line accumulators.

Your local Danfoss agent will be pleased to assist with further 

advice, etc.

Your local Danfoss agent will be pleased to assist with further 

advice, etc.

©Danfoss A/S (AC-MCI / sw), 2014-03 

DKRCC.PS.RP0.A1.02/520H7142 

 23

22 

DKRCC.PS.RP0.A1.02/520H7142 

©Danfoss A/S (AC-MCI / sw), 2014-03

Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

EKD 316 – Parameter  identification (modbus)

Explanations: 

Parameter

  –  The parameter name and abbreviation

PNU

 

–  The Parameter Number. 

 Note:

 

This is equivalent to the modbus register number (modbus a 1)

R/W

 

–  R means read only, RW means it can be changed

Config lock

 

  If the parameter is config locked it means that the value can only be changed when the main switch is off

Min

 

–  The minimum value of the parameter

Max

 

–  The maximum value of the parameter

Default

 

–  The default value of the parameter (factory setting)

Actual value

 –  Values are read/written as 16 bit integer values without decimals. This is the default value as read via modbus

Scale

 

–  This shows the scaling factor of the value. *1 means that there is no scaling. *10 means that the read value is 10 times larger than  

 

  the actual value.

Parameter

PNU

R/W

Config lock

Min

Max

Default

Actual value

Scale

Injection control (1)

n04 Kp factor

3003

R/W

0.5

20.0

2.0

20

*10

n05 Tn seconds

3004

R/W

30

600

120

120

*1

n06 Td seconds

3005

R/W

0

90

0

0

*1

n09 Max SH

3015

R/W

2.0

15.0

10.0

100

*10

n10 Min SH

3021

R/W

1.0

12.0

6.0

60

*10

n11 MOP

3013

R/W

0.0

200.0

20.0

200

*10

n15 Start time

3017

R/W

1

90

0

0

*1

n17 MinOdAtStart

3012

R/W

0

100

0

0

*1

n18 Stability

3014

R/W

0

10

5

5

*1

n19 Kp min.

3024

R/W

0.0

1.0

0.3

3

*10

n20 Kp T0

3025

R/W

0.0

10.0

0.4

4

*10

n21 SH mode

3026

R/W

1

2

1

1

*1

n22 SH close

3027

R/W

1.0

15.0

4.0

40

*10

n32 ETS OD% Max

3023

R/W

0

100

100

100

*1

n44 TnT0 sec.

3039

R/W

10

120

30

30

*1

o56 Reg. type

2076

R/W

x

1

2

1

1

*1

Motor(2)

n37 Max steps

3032

R/W

x

10

999

262

262

*1

n38 Max StepsSec

3033

R/W

x

5

300

300

300

*1

n39 Start backlash

3034

R/W

x

0

100

10

10

*1

n40 Backlash

3035

R/W

x

0

100

23

23

*1

n03 Valve type

3002

R/W

x

0

8

1

1

*1

Alarm settings (3)

A34 Battery low

10035

R/W

0

1

0

0

*1

Miscellaneous (11)

r05 Temp.unit

105

R/W

0

1

0

0

*1

r09 Adjust S2

113

R/W

-10.0

10.0

0.0

0

x10

r10 Adjust S3

114

R/W

-10.0

10.0

0.0

0

x10

o20 MinTransPres

2034

R/W

-1.0

0.0

0.0

0

*10

o21 MaxTransPres

2033

R/W

1.0

200.0

12.0

120

*10

o30 Refrigerant

2551

R/W

x

0

37

0

0

*1

o18 Manual ctrl.

2075

R/W

0

3

0

0

*1

o45 Manual OD%

2064

R/W

0

100

0

0

*1

Service (12)

o61 Appl.mode

2077

R/W

x

1

2

2

2

*1

u10 DI1 status

2002

R

0

1

0

0

*1

u06 Analog input

2504

R

0.0

30.0

0.0

0.0

*10

--- AL/Light rel

2509

R

0

1

0

0

*1

--- Reset alarm

2046

R/W

0

1

0

0

*1

--- Rfg.Fac.A1

2548

R/W

8000

12000

10428

10428

*1

--- Rfg.Fac.A2

2549

R/W

-4000

-1000

-2255

-2255

*1

--- Rfg.Fac.A3

2550

R/W

1000

3000

2557

2557

*1

Alarms (13)

--- Standby

20000

R

0

1

0

0

*1

--- EKC Error

20001

R

0

1

0

0

*1

--- S2 Error

20002

R

0

1

0

0

*1

--- S3 Error

20003

R

0

1

0

0

*1

--- P

e

 inp.error

20004

R

0

1

0

0

*1

--- AI inp.error

20005

R

0

1

0

0

*1

--- No Rfg. Sel.

20006

R

0

1

0

0

*1

--- Battery low

20008

R

0

1

0

0

*1

Danfoss only (14)

o03 Unit addr.

2008

R/W

x

1

240

240

240

*1

No text (15)

r12 Main switch

117

R/W

0

1

0

0

*1

u20 S2 temp.

2537

R

-200.0

200.0

0.0

0.0

*10

u21 Superheat

2536

R

0.0

100.0

0.0

0.0

*10

u22 SuperheatRef

2535

R

0.0

100.0

0.0

0.0

*10

u24 Opening %

2542

R

0

100

0

0

*1

u25 EvapPress P

e

2543

R

-200.0

200.0

0.0

0.0

*10

u26 EvapTemp T

e

2544

R

-200.0

200.0

0.0

0.0

*10

u27 Temp. S3

2545

R

-200.0

200.0

0.0

0.0

*10

--- EKC State

2007

R

0

100

0

0

*1

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: