Danfoss EKD 316 Manual Download Page 5

©Danfoss A/S (AC-MCI / sw), 2014-03 

DKRCC.PS.RP0.A1.02/520H7142 

 9

DKRCC.PS.RP0.A1.02/520H7142 

©Danfoss A/S (AC-MCI / sw), 2014-03

Manual                      Superheat controller type EKD 316

Manual                      Superheat controller type EKD 316 

Installation

The EKD 316 is normally mounted on a DIN rail, and the necessary 

connections are shown in the diagram. If the sensor S4 is not 

used to measure air temperature in connection with thermostat 

function or as part of the controlling loop, then it is not necessary 

to connect the S4 sensor. The 18-24 V battery input at terminals 15 

and 16 is not required if battery back-up is not needed.

Power supply considerations

The terminals 1 and 2 for the voltage supply are not isolated 

from the rest of the controller terminals. This means care should 

be taken when connecting two or more controllers to the same 

voltage supply. In the example below, the two controllers are 

connected to the same voltage supply and on the input side, 

terminals 21 (Analogue Input) are connected to each controller 

and similarly terminals 22 (GND). 

This way of connecting the controllers can cause damage and 

should be avoided.

 Note:

The same applies to other signal inputs e.g. terminals 2 and 4.

See warning page 5.

Stepper motor output

After installation the following checks can be made to the 

connection between the EKD 316 controller and the stepper 

motor of the ETS 6/ETS valve.

With the power off, check that resistance between terminals 5 and 

6 and terminals 7 and 8 is approximately 53 Ohms. Make slight 

allowances for cable resistance.

If resistance values differ from above, ensure that the cable is 

properly connected to the actuator of the ETS 6/ETS valve.

With the power on and parameter o18 set to 1, measure the phase 

current from terminal 5 (or 6) and terminal 7 (or 8 ) with a true RMS 

multimeter when the valve is operating. The valve can be driven 

from 0% to 100% and vice versa by changing the valve opening 

percentage in parameter o45. The phase current should be 70 mA 

rms when operating.

If this not the case and the cable connections are correct, then the 

stepper motor driver in the EKD 316 might be damaged.

Remember to set o18 back to 0 after checks.

If checks 1) and 2) are not correct, ensure that motor cable 

corrections are correct and the cable length is less than 30 meters.

Output relay contact

The contact of the alarm relay will be made when there is an alarm.

Battery back-up

A battery back-up can be connected to terminals 3 (+) and 4 (-).  

The voltage should be at least 18 V and this can be achieved by 

using two 9 V 100 mAh batteries in series. 

The back-up voltage can also come from UPS giving 24 V.

If the controllers are operated by a common analogue signal as 

above, the voltage supply should be separate as shown below.

Choice of S2 sensor type 

Surface sensor S2 * 

Suction pipe of copper or on thin (≤ 3mm) steel pipe.  

Remember to put on heat conducting paste and insulate the 

sensor.

Pocket sensor S2 **

Suction pipe of steel ≥ 3mm   

*)  Pt1000 Ω    Type AKS21 or AKS10

**) Pt1000 Ω   Type AKS21W 

Installation sensors

S2 sensor positioning in the suction line

The position of the S2 sensor is crucial for an optimal control of the 

liquid injection.

The main purpose is to measure temperature of the superheated 

gas leaving the evaporator. In addition to this, the S2 sensor plays 

an important role detecting fast changes of superheat. Suction 

pressure is on the whole stable whereas the leaving gas condition 

is dependent on the temporary mixture of gas, liquid refrigerant 

and oil.   

The sensor is also there to react quickly on liquid passing the 

evaporator, to avoid damage to the compressor.   

An S2 sensor placed two-thirds of the way up a riser after an oil 

trap is where conditions are at their optimum, i.e. good mixture of 

gas, oil and liquid droplets, provided this is not more than 0.5 m 

from the evaporator.

If a horizontal pipe is the only option, the S2 sensor must be 

placed at least half a meter away from the evaporator. 

S1 (Po pressure) is less critical but must be close to the actual 

suction pressure right after the evaporator.

If the measured value is 1-2 K lower than the actual value of Po 

right after the evaporator, it may cause the evaporator to flood. 

This is the case when the pressure transmitter is located in the 

machine room away from the evaporator. If the measured value 

is higher than the actual value of Po, the evaporator might be 

starved of liquid.

AKS 21W

Heat compound

S2 sensor fixing on the suction pipe:

When the S2 sensor is fixed to the surface of the suction pipe, the 

angle of the sensor position will depend on the diameter of the 

pipe, as given in the following diagram:

Summary of Contents for EKD 316

Page 1: ...hus a high suction pressure EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigerati...

Page 2: ...e sensor AKS 21A and pressure transmitter AKS 32R have been shown as an example Function overview Minimum Stable Superheat MSS The controller will search for the minimum stable superheat between an up...

Page 3: ...y are 18 24 V d c See also page 12 Max distance between controller and valve 30 m Accessories Pressure transducer Temperature sensor External display Programming key AKS 32R NSK AKS 21 AKS 11 EKA 164A...

Page 4: ...ible to connect the EKA 164A universal display in this configuration Configuration Valve driver Via Analog Signal This is where the controller receives signals from another controller after which it c...

Page 5: ...that motor cable corrections are correct and the cable length is less than 30 meters Output relay contact The contact of the alarm relay will be made when there is an alarm Battery back up A battery...

Page 6: ...EKD 316 Valve definition Valve type Display EKA 164A Valve type Display EKA 164A n03 0 ETS 12 5 ETS 25 KVS 15 1 ETS 50 CCM 10 CCM 20 CCM 30 2 ETS 100 CCM 40 3 ETS 250 KVS 42 4 ETS 400 25 50 100 250 40...

Page 7: ...implicity and being easier to tune In water chillers where the S4 sensor is located at the leaving water outlet the double loop gives some advantage in terms of being less susceptible to compressor or...

Page 8: ...ing of the valve The force opening of valve function has been implemented in the EKD 316 controller After startup this function will provide a constant set minimum opening degree during a set time per...

Page 9: ...p 990 9990 stp 262 Number of steps per second n38 5 stp s 300 stp s 300 Start backlash extra closing steps at 0 opening in of n37 n39 0 100 10 Integration time for inner loop TnT0 n44 10 s 120 s 30 Co...

Page 10: ...Kp but only just around the reference value A setting of 0 5 will reduce the KP value by half The value should only be changed by specially trained staff n19 Kp Min Amplification factor for the superh...

Page 11: ...logue input Read status of input DI start stop input u10 DI Read the temperature at the S2 sensor u20 S2 temp Read superheat u21 SH Read the control s actual superheat reference u22 SH ref Read the va...

Page 12: ...scaling 10 means that the read value is 10 times larger than the actual value Parameter PNU R W Config lock Min Max Default Actual value Scale Injection control 1 n04 Kp factor 3003 R W 0 5 20 0 2 0...

Reviews: