Danfoss EKC 414A1 Instructions For Use Manual Download Page 9

 EKC 414A1 

Instructions  RI8JN253  ©  Danfoss  05/2005 

9

Average opening degree.
Should only be changed by trained staff

n16

10%

75%

30.0

Start-up time for signal reliability
Should only be changed by trained staff.

n17

5%

70%

30.0

Stability factor for superheat control.
Changes should only be made by trained staff

n18

0

10

4

Forced closing. AKV valve shut in pos. ON

n36

OFF

ON

OFF

Fan

Fan stop on compressor cut out

F01

no

yes

no

Delayed fan stop when compressor is cut out F02

0 min

30 min 0

Safety function. The fan stops if the S5 tem-
perature reaches this value

F04

-50.0

50.0/
off

50.0

Miscellaneous

Delay of output signal after start-up

o01

0 sec.

600 sec 5

Define digital input signal (DI:
OFF=not used, 1=Door alarm, 2=defrost start, 
3=Night operation, 4=External start/stop, 5 = 
Coordinated defrost with cable connections, 
6 = door function

o02

OFF

6

0

Network address (range = 0-60)

o03

0

990

0

ON/OFF switch (service-pin message)

o04

OFF

ON

OFF

Access code

o05

OFF

100

OFF

Used sensor type for S3, S4 and S5  (Pt / PTC)

o06

Pt

Ptc

0/Pt

Set supply voltage frequency

o12

50 Hz

60 Hz

50

Define digitalt output signal (DO:
0=not used 
Coordinated defrost with cable connections: 
1=Master, 2= Slave

o13

0

2

0

Max. standby time after coordinated defrost

o16

1 min

30 min 20

Display S4 % (S

out

)

0%=S3 (S

in

)

100%=S4 (S

out

)

The display temperature can be seen in u56

o17

0%

100%

100

Manual control of outputs:
OFF=No override
1: Compressor reay is ON (railheat relay = ON)
2: Defrost relay is ON
3: Fan relay is ON
4: Alarm relay is OFF  (Railheat relay = on)
5: DO output is ON
6: AKV output is ON
7: Light relay is ON (Railheat relay = on)
When manual control is terminated, the set-
ting must be changed to OFF

o18

OFF

7

OFF

Pressure transmitter working range – min. 
value

020

-1 bar 5 bar

-1

Pressure transmitter working range – max. 
value

021

6 bar

36 bar 12

Inject-ON definition
When the ON input is cut out refrigeration is 
stopped.
Here you define how the fan relay and the 
alarm function are to act:
1 = Fan relay = ON, alarm monitoring active
2 = Fan relay = OFF, alarm monitoring active
3 = Fan relay = OFF, no alarm monitoring
4 = Fan relay = ON, no alarm monitoring
5 to 8= as 1 to 4, but without connection to 
terminal 40-41.

o29

1

8

5

Refrigerant setting
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  
6=R13.  7=R13b1.  8=R23.  9=R500.  
10=R503.  11=R114.  12=R142b. 13=User 
defined. 14=R32. 15=R227.  16=R401A.  
17=R507. 18=R402A.  19=R404A. 20=R407C.  
21=R407A.  22=R407B.  23=R410A.  24=R170.  
25=R290.  26=R600.  27=R600a.  28=R744.  
29=R1270.  30=R417A

o30

0

30

0

Rail heat during day operation.
Setting of ON period in percentage of the 
time in ”o43”

o41

0%

100%

100

Rail heat during night operation.
Setting of ON period in percentage of the 
time in ”o43”

o42

0%

100%

100

Rail heat
Time period for the aggregate ON/OFF time

o43

6 min

60 min 10

Rail heat definition
0 = no rail heat relay
1 = alarm relay changed into rail heat relay
2 = compressor relay changed into rail heat 
relay
3 = no function
4 = no function
5 = light relay changed into rail heat relay

o68

0

5

0

Service

The following readouts can be performed via the belonging parameter
Defrost sensor S5 S

def

u09

°C

Status on DI-input

u10

Defrost time

u11

min.

Air temperature S3 (S

in

)

u12

°C

Status on night operation (on or off)

u13

Status on ON-input

u14

Status on DO-output

u15

Air temperature S4 (S

out

)

u16

°C

Thermostat temperature

u17

°C

Thermostat cut-in time

u18

min.

Temperature at S2

u20

°C

Superheat

u21

K

Superheat reference

u22

K

AKV valve’s actual opening degree

u23

%

Evaporating pressure

u25

bar

Evaporating temperature

u26

°C

Weighted S3/S4 temperature shown in the 
display

u56

°C

Weighted S3/S4 temperature used by the 
alarm function

u57

°C

Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage

Summary of Contents for EKC 414A1

Page 1: ...mun remise en rout apr s d givrage Identi kation Identi cation Identi caci n Application eksempel Application example Anwendungsbeispiel Application exemple Aplicaci n ejemplo P AKS 32R S2 Pt 1000 ohm...

Page 2: ...t kantvarmerel kan enten alarmrel et kompressorrel et eller lysrel et ndres tiil denne anvendelse ndringen skal ske vi en indstilling i o68 Necessary connections 11 12 Pt 1000 ohm sensor Refrigeration...

Page 3: ...zu werden Die Umkon gurierung kann entweder am Alarmrelais Verdich terrelais oder Lichtrelais erfolgen Raccordements n cessaires Bornes 11 12 Sonde Pt 1000 ohm Sortie de r frig rant S2 13 14 Sonde de...

Page 4: ...n termi nal 4 si hay desescarche coordinado con conexiones en cable D1 Posibilidad de conectar una pantalla externa tipo EKA 161 D2 Posibilidad de conectar una pantalla externa con botones de operaci...

Page 5: ...skal du trykke kortvarigt 1s p den nederste knap no der er ikke valgt stop p temperatur C Termostat Di erens r01 0 1 K 10 0 K 2 0 Max begr nsning af termostatens indstilling stemperatur r02 49 C 50 C...

Page 6: ...er ON Kantvarmerel ON N r den manuelle stryring er afsluttet skal indstillingen ndres til OFF o18 OFF 7 OFF Tryktransmitterens arbejdsomr de min v rdi 020 1 bar 5 bar 1 Tryktransmitterens arbejdsomr...

Page 7: ...ng afsluttes S2 Venter p at kompressor On tid afsluttes S3 Venter p at kompressor O tid afsluttes S4 Afrimningssekvens Fordamperen drypper af og afventer at tiden udl ber S10 K lingen er stoppet med d...

Page 8: ...the selected sensor De ne view in O17 C If you wish to see selected defrost stop temperature give the lower button a brief push 1 sec no stop on temperature not selected C Thermostat Di erential r01 0...

Page 9: ...nject ON de nition When the ON input is cut out refrigeration is stopped Here you de ne how the fan relay and the alarm function are to act 1 Fan relay ON alarm monitoring active 2 Fan relay OFF alarm...

Page 10: ...the coordinated defrost S2 Waiting for end of compressor ON time S3 Waiting for end of compressor OFF time S4 Defrost sequence Evaporator drips o and waits for the time to expire S10 Refrigeration st...

Page 11: ...s Men bersicht SW 1 0x Funktion Para meter Min Max Werks einstel lung Normal displayanzeige Anzeige der Temperatur am gew hlten F hler Die Anzeige wird in o17 de niert C Zur Anzeige der Temperatur am...

Page 12: ...ahmenheizung ON Wenn die Manuelle steuerung abgeschlossen ist muss die Einstellung auf OFF eingstellt werden o18 OFF 7 OFF Arbeitsbereich des Druckmessumformers min Wert 020 1 bar 5 bar 1 Arbeitsberei...

Page 13: ...btauung S2 Abwarten dass Verdichter on zeit abgeschlos sen wird S3 Abwarten dass Verdicher o zeit abgeschlossen wird S4 Abtaufrekvens Der Verdampfer tropft af ung abwartet das die Zeit ablauft S10 Die...

Page 14: ...ri vement 1 s sur le bouton inf rieur no arr t sur temp rature pas choisi C Thermostat Di rential r01 0 1 K 10 0 K 2 0 Limite maximum de la temp rature de consigne du thermostat r02 49 C 50 C 50 0 Lim...

Page 15: ...ent est arr t D nition de la fonction du relais du ventilateur et de l alarme 1 relais ventilateur ON surveillance d alarme active 2 relais ventilateur OFF surveillance d alarme active 3 Relais ventil...

Page 16: ...n S2 Attend le compresseur Fin de la p riode ON S3 Attend le compresseur Fin de la p riode OFF S4 S quence de d givrage L vaporateur s goutte et attend la n de la temporisation S10 Le refroidissement...

Page 17: ...lsar el bot n inferior 1 s no parada por temperatura no seleccionado C Termostato Diferencial r01 0 1 K 10 0 K 2 0 L mite m x de corte de temperatura en el termostato r02 49 C 50 C 50 0 L mite m n de...

Page 18: ...l esta terminado el ajuste se debe cambiar a OFF o18 OFF 7 OFF Rango de trabajo del transd de presi n valor min 020 1 bar 5 bar 1 Rango de trabajo del transd de presi n valor m x 021 6 bar 36 bar 12 D...

Page 19: ...el desescarche coor dinado S2 Esperando para nalizar tiempo ON de compre sor S3 Esperando para nalizar tiempo OFF de compre sor S4 Secuencia de desescarche Goteo de evaporador y esperando para que el...

Page 20: ...20 Instructions RI8JN253 Danfoss 05 2005 EKC 414A1...

Reviews: