8
Instructions RI8JN253 © Danfoss 05/2005
EKC 414A1
Operation of the controller can take place via data communication
or from a separate display.
Operation
Menu survey
English
SW = 1.0x
Examples put in another way:
Set the temperature
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
Set a menu
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push both buttons simultaneously until the parameter value is
shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting
The buttons (EKA 162 only)
When you want to change a setting, the two buttons will give you
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the
menu. You obtain this by pushing the upper button for a couple of
seconds - you will then enter the column with parameter codes. Find
the parameter code you want to change and push the two buttons
simultaneously. When you have changed the value, save the new
value by once more pushing the two buttons simultaneously.
Or briefly:
Gives access to the menu (or cutout an alarm)
Gives access to changes
Saves a change
Temperature setting
When it is the temperature setting you wish to change, do not enter
the menu. Push both buttons simultaneously and you will be al-
lowed to change the temperature reference when the display an-
swers back by flashing.
Forced control
In addition to the normal way of operating the controller you are
now able to perform a number of forced control functions which
you start, as follows:
- Cut out alarm relay / check alarm code
• Push the upper button
- Read the defrost stop temperature
• Push the lower button
- Manual start or stop of defrost
• Push the lower button for four seconds
Function
Para
meter
Min.
Max.
Factory
settings
Normal display
Shows the temperature at the selected sensor
Define view in O17
-
°C
If you wish to see selected defrost stop
temperature, give the lower button a brief
push (1 sec.)
no= stop on temperature not selected
-
°C
Thermostat
Differential
r01
0.1 K
10.0 K
2.0
Max. limitation of thermostat’s setting tem-
perature
r02
-49°C
50°C
50.0
Min. limitation of thermostat’s setting tem-
perature
r03
-50°C
49°C
-50.0
Temperature unit (°C/°F)
r05
°C
°F
0/°C
Correction of signal from S4 (S
out
)
r09
-10.0 K 10.0 K
0.0
Correction of signal from S3 (S
in
)
r10
-10.0 K 10.0 K
0.0
Start/Stop of refrigeration
r12
OFF
ON
OFF
Reference displacement during night opera-
tion
r13
-20.0 K 20.0 K
0.0
Define thermostat function
1=ON/OFF, 2=Modulating
r14
1
2
1
Definition and weighting, if applicable, of
thermostat sensors
100%=S4 (S
out
), 0%=S3 (S
in
).
The thermostat temperature can be seen in
U17
r15
0%
100%
100
Time between melt periods
r16
0 h
10 h
1
Duration of melt periods
r17
0 min
10 min. 5
Alarm
Alarm time delay
A03
0 min. 120 min 30
Door alarm time delay
A04
0 min. 90 min. 60
Time delay during cooling
A12
0 min. 240 min 120
High alarm limit
A13
-50°C
50°C
5.0
Low alarm limit
A14
-50°C
50°C
-30.0
Setting of the weighting between S3/S4 to
be used by the alarm function. The alarm
temperature can be seen in u57
A36
0%
100%
100
Compressor
Min. ON-time
c01
0 min
50 min 0
Min. OFF-time
c02
0 min
50 min 0
Defrost
Defrost stop temperature
d02
0
25°C
6.0
Interval between defrost starts
d03
OFF
48 h
8
Max. defrost duration
d04
0
180 min 45
Time displacement of defrost cut-ins during
start-up
d05
0
240 min 0
Drip-off time
d06
0
60 min 0
Fan start delay after defrost
d07
0
60 min 0
Fan start temperature
d08
-15
0°C
-5.0
Fan cut-in during defrost (yes/no)
d09
no
yes
no
Defrost sensor
0=S4 (S
out
) , 1=S5 (S
def
), 2=non. Stop on time
d10
0
2
2
Defrost at power up
d13
no
yes
no
RTC module (if installed)
see RTC instructions
t01 to
t16
Injection control function
Max. value of superheat reference
n09
3.0 K
15.0 K
12.0
Min. value of superheat reference
n10
3.0 K
10.0 K
3.0
MOP temperature
n11
-50.0°C 15°C/off 15°C
AKV valve’s time period
Should only be changed to OFF by trained
staff
n13
3 sec.
6 sec.
6
Adaptive control
Should only be changed to OFF by trained
staff
n14
OFF
ON
on