 EKC 302A, B 

Instructions  RI8PK153  ©  Danfoss  08/2011 

5

Start-up:

Regulation starts when the voltage is on.

1 Go through the survey of factory settings. Make any necessary changes in the respective parameters.
2 For network. Set the address in o03 and then transmit it to the gateway/system unit with setting o04.

English

The buttons

Set menu

1. Push the upper button until a parameter 

is shown

2. Push the upper or the lower button and 

find that parameter you want to change

3. Push the middle button until the 

parameter value is shown

4. Push the upper or the lower button and 

select the new value

5. Push the middle button again to enter 

the value.

Set temperature

1. Push the middle button until the 

temperature value is shown

2. Push the upper or the lower button and 

select the new value

3. Push the middle button to select the 

setting.

Reading the temperature at sensor S5

• Push briefly the lower button

Manuel start or stop of a defrost

• Push the lower button for four 
seconds.

 

Light emitting diode

 = refrigeration

 = defrost
 = fan running

Flashes fast at alarm

Cutout alarm relay / see alarm code 

• Push briefly the upper button

SW = 1.0x

Parameters

Controller

Min.-

value

Max.-
value

Factory 

setting

Actual 

setting

Function

 Codes

EKC 

302A

EKC 

302B

Normal operation

Temperature (set point)

---

-50°C

50°C

2°C

Thermostat

Differential

r01

0,1 K

20 K

2 K

Max. limitation of set point setting

r02

-49°C

50°C

50°C

Min. limitation of set point setting

r03

-50°C

49°C

-50°C

Adjustment of temperature indication

r04

-20 K

20 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from Sair

r09

-10 K

10 K

0 K

Manual service(-1), stop regulation(0), start regulation (1)

r12

-1

1

1

Displacement of reference during night operation

r13

-10 K

10 K

0 K

Activation of reference displacement r40

r39

OFF

on

OFF

Value of reference displacement (activation by r39 or DI)

r40

-50 K

50 K

0 K

Alarm

Delay for temperature alarm

A03

0 min

240 min

30 min

Delay for door alarm

A04

0 min

240 min

60 min

Delay for temperature alarm after defrost

A12

0 min

240 min

90 min

High alarm limit

A13

-50°C

50°C

8°C

Low alarm limit

A14

-50°C

50°C

-30°C

Alarm delay DI1

A27

0 min

240 min

30 min

High alarm limit for condenser temperature (o70)

A37

0°C

99°C

50°C

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Compressor relay must cutin and out inversely (NC-function)

c30

0 / OFF

1 / on

0 / OFF

External relays (Zero crossing control – only EKC 302)
Must be 'ON' when connecting to external relays

c70

OFF

On

On

Defrost

Defrost method (none/EL/gas)

d01

no

gas

EL

Defrost stop temperature

d02

0°C

25°C

6°C

Interval between defrost starts

d03

0 hours

48 hours

8 hours

Max. defrost duration

d04

0 min

180 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-15°C

0°C

-5°C

Fan cutin during defrost

0: Stopped
1: Running
2: Running during  pump down and defrost

d09

0

2

1

Defrost sensor (0=time, 1=S5, 2=Sair)

d10

0

2

0

Max. aggregate refrigeration time between two defrosts

d18

0 hours

48 hours

0 hours

Defrost on demand - S5 temperature’s permitted variation during frost build-up. On 
central plant choose 20 K (=off)

d19

0 K

20 K

20 K

Fans

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50°C

50°C

50°C

Real time clock

Six start times for defrost. 
Setting of hours. 
0=OFF

t01-t06

0 hours

23 hours

0 hours

Summary of Contents for EKC 302A

Page 1: ...DO3 6 3 A 3 FLA 18 LRA 1 10 6 A 5 FLA 30 LRA 2 DO4 4 1 A Min 100 mA EKC 302 DO1 are 20 A relays DO2 and DO3 are 16 A relays DO4 are 10 A relays The max load listed above must be observed when connecti...

Page 2: ...2 Instructions RI8PK153 Danfoss 08 2011 EKC 302A B EKC 302A EKC 302B AU Guld Gold or Oro l max 15 m AU Guld Gold or Oro l max 15 m...

Page 3: ...af referenceforskydningen r40 r39 OFF on OFF V rdi for referenceforskydning kan aktiveres af r39 eller DI r40 50 K 50 K 0 K Alarm Forsinkelse p temperaturalarm A03 0 min 240 min 30 min Forsinkelse p d...

Page 4: ...m ved ben 3 d ralarm ved ben 4 afrimningsstart pulstryk 5 ekstern hovedafbryder 6 natdrift 7 skift reference r40 aktiveres 8 alarmfunktion ved sluttet 9 alarmfunktion ved ben 10 m belreng ring pulstry...

Page 5: ...r12 1 1 1 Displacement of reference during night operation r13 10 K 10 K 0 K Activation of reference displacement r40 r39 OFF on OFF Value of reference displacement activation by r39 or DI r40 50 K 5...

Page 6: ...on DI1 2 door function with alarm when open 3 door alarm when open 4 defrost start pulse pressure 5 ext main switch 6 night operation 7 change reference r40 will be activated 8 alarm function when cl...

Page 7: ...s Signals vom Sair r09 10 K 10 K 0 K Manuell 1 Regelung stoppen 0 Regelung starten 1 r12 1 1 1 Sollwertverschiebung w hrend Nachtbetrieb r13 10 K 10 K 0 K Aktivierung der Sollwertverschiebung r40 r39...

Page 8: ...am DI1 Funktion 0 wird nicht verwendet 1 Status am DI1 2 T rfunktion mit Alarm bei offen 3 T ralarm bei offen 4 Abtaustart Puls Signal 5 Ext Hauptschalter 6 Nachtbetrieb 7 Sollwert ndern r40 wird akti...

Page 9: ...me de nuit r13 10 K 10 K 0 K Actionnement d une d viation de r f rence r40 r39 OFF on OFF Valeur de la d viation de r f rence activation par r39 ou DI r40 50 K 50 K 0 K Alarme Temporisation de l alarm...

Page 10: ...0 non utilis e 1 tat de DI1 2 fonction porte avec alarme d ouverture 3 alarme porte ouverte 4 d but de d givrage poussoir 5 interrupteur principal externe 6 r gime de nuit 7 changer de r f rence acti...

Page 11: ...ivaci n por r39 o DI r40 50 K 50 K 0 K Alarma Retardo de alarma de temperatura est ndar A03 0 min 240 min 30 min Retardo de alarma de puerta A04 0 min 240 min 60 min Retardo de alarma de temperatura d...

Page 12: ...n al equipo o01 0 s 600 s 5 s Funci n de la entrada digital DI1 0 no utilizada 1 comunica el estado de DI1 2 puerta abierta y alarma 3 s lo la alar ma de puerta 4 pulso para iniciar un desescarche 5 i...

Reviews: