Alarm delay 

(short alarm delay)

If one of the two limit values is exceeded, a timer function will commence. The alarm will not 
become active until the set time delay has been passed. The time delay is set in minutes.

A03

Alarm delay

Time delay for door alarm

The time delay is set in minutes.
The function is defined in o02.

A04

DoorOpen del

Time delay for cooling 

(long alarm delay)

This time delay is used during start-up, during defrost, immediately after a defrost.
There will be change-over to the normal time delay (A03) when the temperature has dropped 
below the set upper alarm limit.
The time delay is set in minutes.

A12

Pulldown del

Upper alarm limit

Here you set when the alarm for high temperature is to start. The limit value is set in °C (absolute 
value). The limit value will be raised during night operation. The value is the same as the one set 
for night setback, but will only be raised if the value is positive.
The limit value will also be raised in connection with reference displacement r39.

A13

HighLim Air

Lower alarm limit

Here you set when the alarm for low temperature is to start. The limit value is set in °C (absolute 
value).
The limit value will also be raised in connection with reference displacement r39.

A14

LowLim Air

Delay of a DI alarm

A cut-out/cut-in input will result in alarm when the time delay is passed. The function is defined 
in o02.

A27

AI.Delay DI

High alarm limit for condenser temperature

If the S5 sensor is used for monitoring the condenser’s temperature you must set the value at 
which the alarm is to become activated. The value is set in °C.
The definition of S5 as condenser sensor is accomplished in o70. The alarm is zeroset again 10 K 
below the set temperature.

A37

Condtemp Al.

Reset alarm

Compressor

Compressor control

The compressor relay works in conjunction with the thermostat. When the thermostat calls for 
refrigeration will the compressor relay be operated.

Running times

To prevent irregular operation, values can be set for the time the compressor is to run once it has 
been started. And for how long it at least has to be stopped.
The running times are not observed when defrosts start.

Min. ON-time (in minutes)

c01

Min. On time

Min. OFF-time (in minutes)

c02

Min. Off time

Reversed relay function for compressor relay

0: Normal function where the relay cuts in when refrigeration is demanded
1: Reversed function where the relay cuts out when refrigeration is demanded (this wiring pro

-

duces the result that there will be refrigeration if the supply voltage to the controller fails). 

c30

Cmp relay NC

Defrost

Defrost control

The controller contains a timer function that is zeroset after each defrost start.
The timer function will start a defrost if/when the interval time is passed.
The timer function starts when voltage is connected to the controller, but it is displaced the first 
time by the setting in d05.
If there is power failure the timer value will be saved and continue from here when the power 
returns.
This timer function can be used as a simple way of starting defrosts, but it will always act as 
safety defrost if one of the subsequent defrost starts is not received.
The controller also contains a real-time clock. By means of settings of this clock and times for the 
required defrost times, defrost can be started at fixed times of the day. If there is a risk of power 
failure for periods longer than four hours, a battery module should be mounted in the controller.
Defrost start can also be accomplished via data communication, via contact signals or manual 
start-up.
All starting methods will function in the controller. The different functions have to be set, so that 
defrosts do not ”come tumbling” one after the other.
Defrost can be accomplished with electricity, hotgas or brine.
The actual defrost will be stopped based on time or temperature with a signal from a tempera

-

ture sensor.

Defrost method

Here you set whether defrost is to be accomplished with electricity or "non". 
During defrost the defrost relay will be cut in.
When gas defrosting the compressor relay will be cut in during defrost.

d01

Def. method

Defrost stop temperature

The defrost is stopped at a given temperature which is measured with a sensor (the sensor is 
defined in d10).
The temperature value is set.

d02

Def. Stop Temp

Summary of Contents for EKC 202

Page 1: ...Controller for temperature control EKC 202 Manual...

Page 2: ...geration technical functions Defrost on demand in 1 1 systems Buttons and seal imbedded in the front IP65 density from the front panel Digital input for either Door contact function with alarm Defrost...

Page 3: ...sor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital input Tempera...

Page 4: ...regulation Change over to night operation Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance t...

Page 5: ...e new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operatio...

Page 6: ...g during pump down and defrost d09 0 2 1 Defrost sensor 0 time 1 S5 2 Sair d10 0 2 0 Max aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hours Defrost on demand S5 temperature...

Page 7: ...nually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on relay 4 alarm defrost light Can be controlled manually but only when r12 1 u71 Fault code display Alarm code display...

Page 8: ...ure can be carried out r04 Disp Adj K Temperature unit Set here if the controller is to show temperature values in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the setting Correction of sign...

Page 9: ...un once it has been started And for how long it at least has to be stopped The running times are not observed when defrosts start Min ON time in minutes c01 Min On time Min OFF time in minutes c02 Min...

Page 10: ...e from a defrost and until the compressor is to start again The time when water drips off the evaporator d06 DripOff time Delay of fan start after defrost Here you set the time that is to elapse from...

Page 11: ...t is open it signals that the door is open The refrigeration and the fans are stopped When the time setting in A04 is passed an alarm will be given and refrigeration will be resumed 3 Door alarm When...

Page 12: ...There is access to adjustments of values but not to configuration settings If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100 If...

Page 13: ...alarm A2 Low temperature alarm Low t alarm A4 Door alarm Door Alarm A5 Information Parameter o16 is expired Max Hold Time A15 Alarm Signal from DI input DI1 alarm A45 Standby position stopped refriger...

Page 14: ...emands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and when the controller is dead de energised Light The contact will cut in when the...

Page 15: ...rrent terminals are with plugs Relays CE 250 V a c UL 240 V a c DO1 Refrigeration 10 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 10 6 A 10 A Resistive 5FLA 30LRA DO3 Fan 6 3 A 6 A Resistive 3FLA 18LRA 1...

Page 16: ...anfoss and Danfoss logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no EKC 202A Refrigeration controller 084B8521 EKC 202B Refrigeration controller with fan funct...

Reviews: