EKC 202 

Interval between defrost starts

The function is zeroset and will start the timer function at each defrost start. When the time has 
expired the function will start a defrost.
The function is used as a simple defrost start, or it may be used as a safeguard if the normal 
signal fails to appear.
If master/slave defrost without clock function or without data communication is used, the inter

-

val time will be used as max. time between defrosts.
If a defrost start via data communication does not take place, the interval time will be used as 
max. time between defrosts.
When there is defrost with clock function or data communication, the interval time must be set 
for a somewhat longer period of time than the planned one, as the interval time will otherwise 
start a defrost which a little later will be followed by the planned one.
In connection with power failure the interval time will be maintained, and when the power 
returns the interval time will continue from the maintained value.
The interval time is not active when set to 0.

d03

Def Interval
(0=off)

Max. defrost duration

This setting is a safety time so that the defrost will be stopped if there has not already been a 
stop based on temperature or via coordinated defrost.
(The setting will be the defrost time if d10 is selected to be 0)

d04

Max Def. time

Time staggering for defrost cutins during start-up

The function is only relevant if you have several refrigeration appliances or groups where you 
want the defrost to be staggered in relation to one another. The function is furthermore only 
relevant if you have chosen defrost with interval start (d03).
The function delays the interval time d03 by the set number of minutes, but it only does it once, 
and this at the very first defrost taking place when voltage is connected to the controller.
The function will be active after each and every power failure.

d05

Time Stagg.

Drip-off time

Here you set the time that is to elapse from a defrost and until the compressor is to start again. 
(The time when water drips off the evaporator).

d06

DripOff time

Delay of fan start after defrost

Here you set the time that is to elapse from compressor start after a defrost and until the fan 
may start again. (The time when water is “tied” to the evaporator).

d07

FanStartDel

Fan start temperature

The fan may also be started a little earlier than mentioned under “Delay of fan start after defrost”, 
if the defrost sensor S5 registers another allowable value than the one set here.

d08

FanStartTemp

Fan cut in during defrost

Here you can set whether fan is to operate during defrost.
0: Stopped (Runs during pump down)
1: Running (stopped during  "fan delay")
2: Running during pump down and defrost. After that stopped

d09

FanDuringDef

Defrost sensor 

Here you define the defrost sensor.

0: None, defrost is based on time

1: S5

2: Sair

d10

DefStopSens.

Defrost on demand – aggregate refrigeration time

Set here is the refrigeration time allowed without defrosts. If the time is passed, a defrost will be 

started.

With setting = 0 the function is cut out.

d18

MaxTherRunT

Defrost on demand – S5 temperature

The controller will follow the effectivity of the evaporator, and via internal calculations and 

measurements of the S5 temperature it will be able to start a defrost when the variation of the 

S5 temperature becomes larger than required.

Here you set how large a slide of the S5 temperature can be allowed. When the value is passed, 

a defrost will start.
The function can only be used in 1:1 systems when the evaporating temperature will become 
lower to ensure that the air temperature will be maintained. In central systems the function 
must be cut out.

With setting = 20 the function is cut out

d19

CutoutS5Dif.

If you wish to see the temperature at the S5 sensor, push the controller’s lowermost button.

Defrost temp.

If you wish to start an extra defrost, push the controller’s lowermost button for four seconds.
You can stop an ongoing defrost in the same way

Def Start
Here you can start a manual defrost.

Hold After Def
Shows ON when the controller is
operating with coordinated defrost.
Defrost State
Status on defrost
1= pump down / defrost

Summary of Contents for EKC 202

Page 1: ...Controller for temperature control EKC 202 Manual...

Page 2: ...geration technical functions Defrost on demand in 1 1 systems Buttons and seal imbedded in the front IP65 density from the front panel Digital input for either Door contact function with alarm Defrost...

Page 3: ...sor solenoid valve Defrost sensor Electrical defrost gas defrost Relay output 3 is used for control of fan EKC 202C Controller with four relay outputs two temperature sensors and digital input Tempera...

Page 4: ...regulation Change over to night operation Case cleaning Change to another temperature reference Inject on off Case cleaning function This function makes it easy to steer the refrigeration appliance t...

Page 5: ...e new value by once more pushing the middle button Display The values will be shown with three digits and with a setting you can determine whether the temperature are to be shown in C or in F Operatio...

Page 6: ...g during pump down and defrost d09 0 2 1 Defrost sensor 0 time 1 S5 2 Sair d10 0 2 0 Max aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hours Defrost on demand S5 temperature...

Page 7: ...nually but only when r12 1 u60 Temperature measured with Sair sensor u69 Status on relay 4 alarm defrost light Can be controlled manually but only when r12 1 u71 Fault code display Alarm code display...

Page 8: ...ure can be carried out r04 Disp Adj K Temperature unit Set here if the controller is to show temperature values in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the setting Correction of sign...

Page 9: ...un once it has been started And for how long it at least has to be stopped The running times are not observed when defrosts start Min ON time in minutes c01 Min On time Min OFF time in minutes c02 Min...

Page 10: ...e from a defrost and until the compressor is to start again The time when water drips off the evaporator d06 DripOff time Delay of fan start after defrost Here you set the time that is to elapse from...

Page 11: ...t is open it signals that the door is open The refrigeration and the fans are stopped When the time setting in A04 is passed an alarm will be given and refrigeration will be resumed 3 Door alarm When...

Page 12: ...There is access to adjustments of values but not to configuration settings If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100 If...

Page 13: ...alarm A2 Low temperature alarm Low t alarm A4 Door alarm Door Alarm A5 Information Parameter o16 is expired Max Hold Time A15 Alarm Signal from DI input DI1 alarm A45 Standby position stopped refriger...

Page 14: ...emands refrigeration Defrost Fan Alarm The relay is cut out during normal operation and cuts in in alarm situations and when the controller is dead de energised Light The contact will cut in when the...

Page 15: ...rrent terminals are with plugs Relays CE 250 V a c UL 240 V a c DO1 Refrigeration 10 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 10 6 A 10 A Resistive 5FLA 30LRA DO3 Fan 6 3 A 6 A Resistive 3FLA 18LRA 1...

Page 16: ...anfoss and Danfoss logotype are trademarks of Danfoss A S All rights reserved Ordering Type Function Code no EKC 202A Refrigeration controller 084B8521 EKC 202B Refrigeration controller with fan funct...

Reviews: