Basic principles

Control of district heating circuits with or 

without heat exchanger and for boiler-based 

heating circuits 

Typically, the flow temperature is adjusted 

according to the desired flow temperature.

•   Adjustment of flow temperature
  The desired flow temperature is calculated 

in the ECL Comfort controller, based on the 

outdoor temperature. The lower the outdoor 

temperature, the higher the desired flow 

temperature. 

The motorized control valve is opened 

gradually when the flow temperature is lower 

than the desired flow temperature and vice 

versa.

•   Return temperature limitation
  The return temperature to the district heating 

supply should not be too high. If so, the 

desired flow temperature can be adjusted 

(typically to a lower value) thus resulting in a 

gradual closing of the motorized control valve. 

In boiler-based heating supply the return 

temperature should not be too low (same 

adjustment procedure as above).

•  Room temperature limitation
  If the measured room temperature does not 

equal the desired room temperature, the 

desired flow temperature can be adjusted.

•   Circulation pump control
  The circulation pump is ON when the desired 

flow temperature is higher than a user-defined 

value (factory setting: 20 °C ) or the outdoor 

temperature is lower than a user-defined 

value (factory setting: 2 °C).

Summary of Contents for ECL Comfort 110

Page 1: ...controller for weather compensated flow temperature control heating constant temperature control domestic hot water e g and prepared for new applications by means of chip card and communication interf...

Page 2: ...anger Basic principles Constant DHW temperature control with heat exchanger or storage tank Typically the flow temperature is adjusted according to the desired flow temperature Adjustment of DHW tempe...

Page 3: ...Auto tuning A function for automatically setting the proportional band Xp and integration time constant Tn Safety functions Frost protection The controller automatically switches the circulation pump...

Page 4: ...desired flow temperature and vice versa Return temperature limitation The return temperature to the district heating supply should not be too high If so the desired flow temperature can be adjusted ty...

Page 5: ...ity 61000 6 1 Emission 61000 6 3 LVD Directive 2006 95 EC Wiring 230 V a c Connections for safety thermostat Supply voltage 230 V a c 50 Hz Voltage range 207 to 244 V a c IEC 60038 Power consumption 3...

Page 6: ...foss 09 2008 6 Operation Adjust temperatures and values Switch between menu lines Select return 2 sec Return to daily user menu Menu navigation 5FNQ A8FFLEBZ MPX UFNQ 3FUVSO 5 MJNJU 3PPN 5 MJNJU 0QUJN...

Page 7: ...Data sheet DH SMT DK VD KT C3 02 Danfoss 09 2008 7 ECL Comfort 110 Dimensions Cut out for mounting Mounting in a panel panel mounting kit code no 087B1249 The panel thickness must not exceed 5 mm...

Page 8: ...8 ECL Comfort 110 Data sheet VD KT C3 02 Produced by Danfoss A S 09 2008 Additional documentation for ECL Comfort 110 is available on http heating danfoss com...

Reviews: