Data sheet
DH-SMT/DK
VD.KT.C3.02
© Danfoss 09/2008
5
ECL Comfort 110
General data
Ambient temperature
0 - 55 °C
Storage temperature
-40 - + 70 °C
Enclosure
DIN rail, wall or panel
Sensor type
Pt 1000 (1000 Ω @ 0 °C)
Grade of enclosure
IP 41 DIN 40050
- marking
in accordance with the standards
EMC-Directive: 2004/108/EC
Immunity: 61000-6-1
Emission: 61000-6-3
LVD-Directive: 2006/95/EC
Wiring - 230 V a.c.
* Connections for safety thermostat
Supply voltage
230 V a.c. - 50 Hz
Voltage range
207 to 244 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 1 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 230 V a.c.
Wiring - 24 V a.c.
* Connections for safety thermostat
Supply voltage
24 V a.c. - 50 Hz
Voltage range
21.6 to 26.4 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 2 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 24 V a.c.