background image

Data sheet

DH-SMT/DK

VD.KT.C3.02  

©  Danfoss 09/2008

5

ECL Comfort 110

General data

Ambient temperature

0 - 55 °C

Storage temperature

-40 - + 70 °C

Enclosure

DIN rail, wall or panel 

Sensor type

Pt 1000 (1000 Ω @ 0 °C)

Grade of enclosure

IP 41 DIN 40050

 - marking

in accordance with the standards

EMC-Directive: 2004/108/EC
Immunity: 61000-6-1 
Emission: 61000-6-3 
LVD-Directive: 2006/95/EC  

Wiring - 230 V a.c.

* Connections for safety thermostat

Supply voltage

230 V a.c. - 50 Hz

Voltage range

207 to 244 V a.c. (IEC 60038)

Power consumption 

3 VA

Load on relay 1 outputs

4 (2) A - 230 V a.c.

Load on triac outputs

15 VA @ 230 V a.c. 

Wiring - 24 V a.c.

* Connections for safety thermostat

Supply voltage

24 V a.c. - 50 Hz

Voltage range

21.6 to 26.4 V a.c. (IEC 60038)

Power consumption 

3 VA

Load on relay 2 outputs

4 (2) A - 230 V a.c.

Load on triac outputs

15 VA @ 24 V a.c. 

Summary of Contents for ECL Comfort 110

Page 1: ...controller for weather compensated flow temperature control heating constant temperature control domestic hot water e g and prepared for new applications by means of chip card and communication interf...

Page 2: ...anger Basic principles Constant DHW temperature control with heat exchanger or storage tank Typically the flow temperature is adjusted according to the desired flow temperature Adjustment of DHW tempe...

Page 3: ...Auto tuning A function for automatically setting the proportional band Xp and integration time constant Tn Safety functions Frost protection The controller automatically switches the circulation pump...

Page 4: ...desired flow temperature and vice versa Return temperature limitation The return temperature to the district heating supply should not be too high If so the desired flow temperature can be adjusted ty...

Page 5: ...ity 61000 6 1 Emission 61000 6 3 LVD Directive 2006 95 EC Wiring 230 V a c Connections for safety thermostat Supply voltage 230 V a c 50 Hz Voltage range 207 to 244 V a c IEC 60038 Power consumption 3...

Page 6: ...foss 09 2008 6 Operation Adjust temperatures and values Switch between menu lines Select return 2 sec Return to daily user menu Menu navigation 5FNQ A8FFLEBZ MPX UFNQ 3FUVSO 5 MJNJU 3PPN 5 MJNJU 0QUJN...

Page 7: ...Data sheet DH SMT DK VD KT C3 02 Danfoss 09 2008 7 ECL Comfort 110 Dimensions Cut out for mounting Mounting in a panel panel mounting kit code no 087B1249 The panel thickness must not exceed 5 mm...

Page 8: ...8 ECL Comfort 110 Data sheet VD KT C3 02 Produced by Danfoss A S 09 2008 Additional documentation for ECL Comfort 110 is available on http heating danfoss com...