background image

© Danfoss | Climate Solutions | 2022.06

4 | AN14978641682001-000501

ENGLISH

Installation

Refrigerants

Applicable to HCFC, HFC, R717(Ammonia) 

and R744 (CO

2

).

Flammable hydrocarbons are not 

recommended. The valve is only 

recommended for use in closed circuits. For 

further information please contact Danfoss.

Temperature range

DSV: –50/+100°C (–58/+212°F)

Pressure range

DSV: The valves are designed for a max. 

working pressure of 40 bar g (580 psi g).

Installation

Applied in connection with safety valves 

(SFV) installation instruction for safety 

valves must be followed. The DSV and the 

two safety valves (SFV) are to be mounted 

as indicated in fig. 10.

IMPORTANT

:

The inlet/outlet pipe dimensions must not 

be smaller than those of the safety valves.

The valve must be installed with the 

spindle in horizontal position (fig. 1). Valves 

should be opened by hand without the use 

of tools or other devices (fig. 3). The valve 

is designed to withstand a high internal 

pressure. However, the piping system 

should be designed to avoid liquid traps 

and reduce the risk of hydraulic pressure 

caused by thermal expansion. It must be 

ensured that the valve is protected from 

pressure transients like liquid hammer in 

the system.

Recommended flow direction (fig. 2)

To achieve optimum flow conditions, the 

valve should be installed with the flow 

as indicated by the arrow. Flow in the 

opposite direction is also acceptable , but 

slightly reduces the K

v

- / C

v

 value. 

Operating instructions (fig. 2)

When the spindle is turned clockwise the 

inlet socket C is connected to outlet B. 

When the spindle is turned anticlockwise  

the inlet socket C is connected to outlet A.

Welding

If welding fittings are applied, these 

should be dismounted during the welding 

process. Welding directly on the valve 

housing, the bonnet should be removed 

(fig. 4) to prevent damage to the O-rings in 

the packing gland and between the valve 

body and bonnet, as well as the Teflon 

gasket in the valve seat. Only materials and 

welding methods, compatible with the 

valve housing material, must be welded to 

the valve housing. 

The valve should be cleaned internally 

to remove welding debris on completion 

of welding and before the valve is 

reassembled.

Avoid welding debris and dirt in the 

threads of the housing and the bonnet.

Removing the bonnet can be omitted 

provided that:

The temperature in the area between the 

valve body and bonnet during welding 

does not 150°C/+302°F. This 

temperature depends on the welding 

method as well as on any cooling of the 

valve body during the welding itself. 

(Cooling can be ensured by, for example, 

wrapping a wet clothe around the valve 

body.) Make sure that no dirt, welding 

debris etc. gets into the valve during the 

welding procedure.

Be careful not to damage the Teflon cone 

ring.

The valve housing must be free from 

stresses (external loads) after installation.

Double stop valves must not be mounted 

in systems where the outlet side of the 

valve is open to atmosphere. The outlet 

side of the valve must always be connected 

to safety valves, the system or properly 

capped off, for example with a welded-on 

end plate.

Assembly

Remove welding debris and any dirt from 

pipes and valve body before assembly. 

Check that the cone has been fully screwed 

back towards the bonnet before it is 

replaced in the valve body (fig. 5a).

Tightening

Tighten the bonnet with a torque wrench, 

to the values indicated in the table (fig. 5b).

Colours and identification

The DSV valves are painted with a red oxide 

primer in the factory. Precise identification 

of the valve is made via the ID ring at 

the top of the bonnet, as well as by the 

stamping on the valve body. The external 

surface of the valve housing must be 

prevented against corrosion with a suitable 

protective coating after installation and 

assembly.

Protection of the ID ring when repainting 

the valve is recommended.

Maintenance

Packing gland

When performing service and 

maintenance, replace the complete 

packing gland only, which is available as a 

spare part. As a general rule, the packing 

gland must not be removed if there is 

internal pressure in the valve. However, if 

the following precautionary measures are 

taken, the packing gland can be removed 

with the valve still under pressure:

Backseating (fig. 6)

To backseat the valve, turn the spindle 

counter-clockwise until it stops.

Pressure equalization (fig. 7)

In some cases, pressure forms behind the 

packing gland. Hence a hand wheel or 

similar should be fastened on top of the 

spindle while the pressure is equalized. 

The pressure can be equalized by slowly 

screwing out the gland.

Removal of packing gland (fig. 8)

The packing gland can now be removed.

-  Check that the spindle is free of scratches 

and impact marks.

-  If the Teflon cone rings have been 

damaged, the whole cone assembly 

must be replaced.

Assembly

Remove any dirt from the body before the 

valve is assembled. Check that the cone 

has been screwed back towards the bonnet 

before it is replaced in the valve body (fig. 

5a). Also check that the O-rings are free of 

scratches and impact marks.

Tightening

Tighten the bonnet with a torque wrench, 

to the values indicated in the table (fig. 5b). 

Tighten the packing gland with a torque 

wrench, to the values indicated in the table 

(fig. 9).

Use only original Danfoss parts, including 

packing glands, O-rings and gaskets for 

replacement. Materials of new parts are 

certified for the relevant refrigerant. 

In cases of doubt, please contact Danfoss. 

Reviews: