Figure 37: For DSH120, DSH161 or DSH184
1
2
CC-000032
Figure 38: DSH240, DSH295 or DSH381
3
CC-000033
3
CC-000033
3
Tightening torque 145Nm
Supplied with the compressor
Included in tandem kit
1
2
3
To connect the equalization line on rotolock connections, the organ pipe, adaptor sleeves, Teflon gaskets included
in the tandem accessory kit must be used.
Organ pipe
Tightening torque 100Nm
Tightening torque 145Nm
Supplied with the compressor
Included in tandem kit
Oil equalization design DSH482-535, DSH590 to DSH1800
The oil level is balanced by a pipe of 1"3/8 or 1"5/8. To connect the equalization line on rotolock connections, the
adaptor sleeves included in the tandem or trio accessory kit must be used.
Figure 39: DSH482-535, DSH590 to DSH1800
Scroll compressors, DSH090 to DSH600 | Mechanical connections
© Danfoss | Climate Solutions | 2022.10
AB288965961751en-001402 | 36