Performance data
R410A 50-60 Hz, Single compressor
Table 8: 50-60 Hz Performance data
Model
Nominal tons
60 Hz
Nominal cooling capacity
Power input
COP
E.E.R.
TR
W
Btu/h
kW
W/W
Btu/h/W
50Hz
DSH090
7.5
20048
68402
6.57
3.05
10.40
DSH105
9.0
23578
80449
7.69
3.07
10.47
DSH120
10.0
26787
91396
8.65
3.10
10.57
DSH140
12.0
30370
103621
9.74
3.12
10.64
DSH161
13.0
34894
119059
11.09
3.15
10.74
DSH184
15.0
39036
133191
12.42
3.14
10.72
DSH240
20.0
52730
179920
17.04
3.09
10.56
DSH295
25.0
64520
220149
20.35
3.17
10.82
DSH381
30.0
80707
275379
25.83
3.12
10.66
DSH485
40.0
104687
357202
32.39
3.23
11.03
DSH600
50.0
128864
439698
40.60
3.17
10.83
60Hz
DSH090
7.5
27471
93730
8.60
3.19
10.90
DSH105
9.0
32279
110136
10.06
3.21
10.94
DSH120
10.0
36629
124977
11.31
3.24
11.05
DSH140
12.0
41510
141631
12.81
3.24
11.06
DSH161
13.0
47222
161122
14.77
3.20
10.91
DSH184
15.0
53157
181371
16.44
3.23
11.03
DSH240
20.0
71760
244852
22.46
3.20
10.90
DSH295
25.0
87610
298934
26.96
3.25
11.09
DSH381
30.0
110116
375726
34.41
3.20
10.92
DSH485
40.0
143956
491192
43.03
3.35
11.42
DSH600
50.0
175344
598291
53.80
3.26
11.12
NOTE:
TR
: Ton of Refrigeration,
COP
: Coefficient Of Performance
EER
: Energy Efficiency Ratio
Standard rating conditions For 50 Hz: Evaporating temperature: 5°C (41°F), Condensing temperature: 50°C (122°F),
Superheat: 10K (18°F), Subcooling: 0K (0°F)
For 60 Hz: Evaporating temperature: 7.2°C (45°F), Condensing temperature: 54.4°C (130°F), Superheat: 11.1K (20°F),
Subcooling: 8.3K (15°F)
Subject to modification without prior notification.
Data given for motor code 4 compressor with above conditions
For regular updates and detailed capacities, please refer to
© Danfoss | Climate Solutions | 2022.10
AB288965961751en-001402 | 13