These Danfoss scroll compressors are protected against overheating and 
overloading by an internal safety motor protector. However, an external 
manual reset overload protector is recommended for protecting the circuit 
against over-current. 

4 - Electrical connections details

Legend:

Fuses ........................................................................................... F1
Compressor contactor ......................................................... KM
High pressure safety switch .................................................HP

Safety pressure switch .........................................................LPS 
Discharge gas temperature protection ......................... DGT
Compressor motor ...................................................................M

Surface sump heater ........................................................... SSH
Thermal magnetic motor circuit breaker   ...................... CB
Phase sequence relay .............................................................Ph

5 – Handling and storage

 •  Handle the compressor with care. Use the 

dedicated handles in the packaging. Use the 
compressor lifting lug and use appropriate 
and safe lifting equipment.

 •  Store and transport the compressor in an 

upright position.

 •   Store the compressor between Ts min and Ts 

max values for LP side indicated on compres-
sor nameplate. 

 •   Don’t expose the compressor and the packa-

ging to rain or corrosive atmosphere.

6 – Safety measures before assembly

 Never use the compressor in a flammable at-

mosphere.
 •  Check before assembly that the compressor 

does not show any obvious signs of deteriora-
tion that could have occurred during inappro-
priate transportation, handling or storage.

 •  The compressor ambient temperature may 

not exceed Ts max value for LP side indicated 
on compressor nameplate during off-cycle.

 •  Mount the compressor on a horizontal flat 

surface with less than 3° slope.

 •   Verify that the power supply corresponds to 

the compressor motor characteristics (see 

 

nameplate).

 •  When installing DSF, use equipment specifi-

cally reserved for HFC refrigerants which was 
never used for CFC or HCFC refrigerants.

 •   Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •   Use clean and dehydrated system components.
  •   The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

7 – Assembly

 •   The compressor must be mounted on rails or 

chassis according to Danfoss recommenda-

tions described in related product guidelines 
(type of spacer, tightening torques).

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Remove the gaskets when brazing rotolock 

connectors.

  •   Always use new gaskets for assembly.
 •  Connect the compressor to the system as 

soon as possible to avoid oil contamination 
from ambient moisture.

  •   Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas 
flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 
remove the internal valve.

 •  

Do not exceed the maximum tightening 
torque for rotolock connections: 

Rotolock connections Tightening torque

1” rotolock

80 Nm

1 1/4 “ rotolock

90 Nm

1 3/4” rotolock

110 Nm

2 1/4” rotolock

130 Nm.

8 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.
 •  DSF090 to 200: Pressurize the system on HP 

side first and then on LP side. Never let the 
pressure on LP side exceed the pressure on 
HP side with more than 5 bar. Such pressure 
difference could cause internal compressor 
damage.

  •   Do not use dye for leak detection.
  •   Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed 1.1 x PS 

value for LP side and PS value for HP side indi-
cated on compressor nameplate.

  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

9 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

 •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

10 – Electrical connections

  •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

  •   All electrical components must be selected as 

per local standards and compressor require-
ments.

 •  Refer to section 4 for electrical connections 

details.

 •  The Danfoss scroll compressors only works 

correctly in one rotation direction. Line 
phases L1, L2, L3 must absolutely be connec-
ted to compressor terminals T1, T2, T3 to 
avoid reverse rotation.

 •   Use ø 4.8 mm (3/16”) screws and ¼” ring ter-

minals for the power connection. Fasten with 
3 Nm torque.

 •   The compressor must be connected to earth 

with the 5 mm earth terminal screw.

11 – Filling the system

  •   Keep the compressor switched off.
 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. The charge must 
be as close as possible to the nominal system 
charge to avoid low pressure operation and 
excessive superheat. Never let the pressure 