background image

Instructions

8510294P01C - AN323020831102en-000101 | 3

© Danfoss | DCS (CC) | 2020.07

on LP side exceed the pressure on HP side 
with more than 5 bar. Such pressure difference 
could cause internal compressor damage.

 •  Keep the refrigerant charge below the indi-

cated charge limits if possible. Above this limit; 
protect the compressor against liquid flood-
back with a pump-down cycle or suction line 
accumulator.

 •  Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant charge 

limit (kg)

DSF 115-130-155-175-200

10

DSF 090-100

8

12 – Verification before commissioning

 Use safety devices such as safety pressure swit-

ch and mechanical relief valve in compliance with 
both generally and locally applicable regulations 
and safety standards. Ensure that they are opera-
tional and properly set. 

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 
service pressure of any system component.

 •  

A low-pressure switch is recommended to 
avoid vacuum operation. Minimum setting for 
DSF: 1.5 bar g.

  •   Verify that all electrical connections are proper-

ly fastened and in compliance with local regu-
lations.

  •   When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-
up and start-up after prolonged shutdown for 
belt type crankcase heaters (6 hours for surface 
sump heaters).

13 – Start-up

 Never operate the compressor without the 

electrical box cover fitted.
 •  Never start the compressor when no refrige-

rant is charged.

  •   All service valves must be in the open position.
  •   Balance the HP/LP pressure.
 •   Energize the compressor. It must start promp-

tly. If the compressor does not start, check wi-
ring conformity and voltage on terminals.

 •  Eventual reverse rotation can be detected by 

following phenomena; the compressor doesn’t 

build up pressure, it has abnormally high sound 
level and abnormally low power consumption. 
In such case, shut down the compressor imme-
diately and connect the phases to their proper 
terminals. Danfoss DSF scroll compressors are 
protected against reverse rotation either by an 
internal reverse rotation protection. They will 
shut off automatically. 

 •  If the internal overload protector trips out, it 

must cool down to 60°C to reset. Depending 
on ambient temperature, this may take up to 
several hours.

14 – Check with running compressor

  •   Check current draw and voltage.
  •   Check suction superheat to reduce risk of slug-

ging.

  •   Observe the oil level in the sight glass for about 

60 minutes to ensure proper oil return to the 
compressor.

  •   Respect the operating limits.
 •    Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 
as far as possible from the compressor. The 
compressor must be operating during this pro-
cess.

  •   Do not overcharge the system.
  •   Never release refrigerant to atmosphere.
 •  For reversible systems, ensure that the 4-way 

valve does not reverse when the compressor 
is stopped due to heating or cooling demand 
(stop on thermostat)

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

 •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

15 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent inju-
ry.Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.

To prevent system related compressor problems, 
following periodic maintenance is recommended:
 •   Verify that safety devices are operational and 

properly set.

  •    Ensure that the system is leak tight.
  •    Check the compressor current draw.
 •    Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •   Check that all electrical connections are still 

adequately fastened.

 •    Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compressor 
shell, tubes and electrical connections.

16 - Warranty

Always transmit the model number and serial nu-
mber with any claim filed regarding this product.
The product warranty may be void in following 
cases:
  •    Absence  of  nameplate.
 •   External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •    Compressor opened or returned unsealed.
 •   Rust, water or leak detection dye inside the 

compressor.

 •    Use of a refrigerant or lubricant not approved 

by Danfoss.

  •    Any deviation from recommended instructions 

pertaining to installation, application or main-
tenance.

  •    Use in mobile applications.
  •    Use in explosive atmospheric environment.
 •   No model number or serial number trans-

mitted with the warranty claim.

The compressor is not designed to withstand 
natural disasters such as earthquakes, cyclones, 
floods…. or extreme events such as fires, terrorist 
attacks, military bombardments, or explosions of 
any kind.
Danfoss Commercial Compressor is not liable 
for any malfunction of its product resulting from 
such events

17 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products 

already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Òu*=Í4P01C Ó

Reviews: