N
Be sure to install both an earth leakage detector and circuit breaker
with specified capacity in accordance with relevant local and national
regulations. -If it is not installed properly, it may cause electric shocks
and fire.
6.1
Fuse table
Outdoor Unit Mains
Supply
Fuse size
5kW
9kW
16kW
230V 1-N, 50Hz
16 A
16 A
25 A
400V 3-N, 50Hz
-
10 A
16 A
Tab. 3: Fuse table
Indoor Unit
Mains Supply
DHP-
iQ
Mini
Fuse
size
DHP-iQ Maxi (including immersion heat-
er) Fuse size
3kW
6kW
9kW
12kW 15kW
230V 1-N,
50Hz
10 A
16 A
32 A
50 A
-
-
400V 3-N,
50Hz
-
10 A
16 A
16 A
20 A
25 A