![background image](http://html1.mh-extra.com/html/danfoss/dhp-iq/dhp-iq_installation-manual_3575345014.webp)
Item
1phase 5kW
1phase 9kW
3phase 9kW
1phase
16kW
3phase 16kW
Compressor
Type
BLDC Twin Rotary BLDC Twin Rota-
ry
BLDC Twin Ro-
tary
BLDC Twin
Rotary
BLDC Twin
Rotary
Model
UG4TH200FUAE4 UG8TH8265FJW UG8T300FUC-
JU
UG5T450FU
UG5T450FU
Oil
POE
POE
PVE
PVE
PVE
Fan
Air
Flow
Rate
Cool-
ing
CMM 51
66
66
118
118
l/s
850
1100
1100
1967
1967
Number of
Unit
EA
1
1
1
2
2
Base Heater
W
N/A
150
150
150
150
Sound
*4
4A
Sound
Pressure
Level
Heating
dB(A) 45
48
48
52
52
Cooling
dB(A) 45
48
48
54
54
4B
Sound
Power Lev-
el
Heating
dB
61
63
63
66
66
Cooling
dB
62
64
64
69
69
External Di-
mension
Net Weight
kg
59
76.0
76.0
108.0
108.0
Shipping Weight
kg
63
84.0
84.0
118.0
118.0
Net Dimensions (WxHxD)
mm
880 x 798 x 310
940 x 998 x 330
940 x 998 x
330
940 x 998 x
330
940 x 998 x
330
Shipping Dimensions
(WxHxD)
mm
1,023 x 904 x 413 995 x 1,178 x
426
995 x 1,178 x
426
995 x 1,178 x
426
995 x 1,178 x
426
Operating
Temp.
Range
Heating
*5
℃
-25~35
-25~35
-25~35
-25~35
-25~35
Cooling
℃
10~46
10~46
10~46
10~46
10~46
DHW Tank
*6
℃
-25~35
-25~35
-25~35
-25~35
-25~35
*1)
A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C.
*2)
A2W Condition #2 : (Heating) Water In/Out */
35°C, Outdoor Air DB/WB 2°C/1°C
*3)
A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C
*4)
A) Sound Pressure was acquired in an anechoic room. Thus actual noise
level may be different depending on the installation conditions. B) Sound Power Level, Nominal operation.
*5)
At the temperature -25°C ~ -20°C, operation is available but capacity cannot be
guaranteed.
*6)
Heat pump operating range of DHW : -25°C ~ 35°C.
*7)
These products contain R410A which is fluorinated greenhouse gas.
*8)
According to F-gas directive EC 517/2014
※
Heat Exchanger type : Condensor - Fin & Tube (Fin : Al, Tube : Cu), Plate Heat Exchanger(PHE) (STS)
3.1.4
DHP-iQ System solution
Symbol key
The following symbol key applies to all system solutions:
Pos
Description
Pos
Description
5
Heat pump unit
83
Non-return valve
10
Supply line
85
Air bleeding valve
11
Return line
87
Safety valve (9 bar, WW)
12
Cold water
91
Dirt strainer with shut-off valve
13
Hot water
96
Flexible hose
18
Hot water storage tank
100
Security valve (1.5 bar)
21
Volume tank
101
Reversing valve pool