4
Configuration of control system
!
To avoid alarms during start-up, the outdoor unit must be powered on.
!
Make the settings in the order they appear in the text that follows
Further information about parameters in the control system are found in the Information Menu and Service Menu chapters in the Tech-
nical Description
4.1
Select display language
The following settings are made in the Information Menu. To enter the Information Menu, press left (<) arrow. Use
+
or
–
to move up and
down in the menu.
Select display language in the INFORMATION menu:
!
INFORMATION
!
Press
–
button several times to get to the LANGUAGE entry
!
Press right arrow button to enter the LANGUAGE menu
!
Use
+
or
–
buttons to navigate to desired language
!
Press right arrow to chose language. An asterisk (*) will appear next to chosen language
!
Press left arrow twice to exit the Information Menu
4.2
Heat pump size settings
The following settings are made in the Service Menu. To enter the Service Menu, press and hold left (<) arrow for at least 5 seconds. Use
+
or
–
to move up and down in the menu.
Set the output size of the heat pump is in the menu:
!
SERVICE
!
INSTALLATION
!
SYSTEM
!
HEAT SOURCE
!
AIR
!
DIRECT EVAP.
!
Press right arrow (
>
) for approximately 20 seconds to enter the Heat Pump size entry.
!
Use
+
or
–
buttons to select Heat Pump size in kW
!
Press right arrow (
>
) to confirm the choice. An asterisk (*) will appear next to the chosen
value
!
Press left arrow (
<
) several times to navigate to the service menu
Commissioning
Danfoss Heating Solutions
VIGFH102
9