5.5
Test the auxiliary heater
1. Start the circulation pump by setting the value CIRC.PUMP to: 1 (OPTIMUM not selected), 30-100% (OPTIMUM selected) .
2. Start the auxiliary heater by setting the value of present EXT. AUX. HEAT to 1.
3. Check that the auxiliary heater works by exiting the MANUAL TEST menu and
enter the INFORMATION -> OP. DATA menu and check that the temperature of SUPPLY LINE rises.
4. Return to the menu MANUAL TEST and stop the auxiliary heater by setting EXT. AUX. HEATER value to 0.
5. Stop the circulation pump by setting the SYSTEM CIRC. PUMP value to 0.
5.6
Test the fan
1. Start the fan by setting the value FAN to between 3 - 10V (30 - 100%). Check that the fan is running.
2. Stop the fan by setting the FAN value to 0.
5.7
Checking the four way valve
1. Start the circulation pump by setting the value CIRC.PUMP to: 1 (OPTIMUM not selected), 30-100% (OPTIMUM selected) .
2. Start the compressor by setting the value COMPRESSOR to 1.
3. Start the fan by setting the value FAN to between 3 - 10V (30 - 100%).
4. Check the temperature on the supply line (INFORMATION -> OP. DATA) after a few minutes.
5. Switch the four way valve (FOUR-WAY VALVE = 1).
6. Check that the temperature of the supply line drops.
7. Reset the four-way valve and stop the fan, compressor and circulation pump
5.8
Checking sensors
Check the defrost sensor temperature so that it corresponds to the actual outdoor temperature. Checked in the INFORMATION -> OP.
DATA menu, DEFR SENSOR
Check applicable sensors described in the table below.
Parameter
Meaning
OUTD
Shows the temperature on the outdoor sensor.
ROOM
Shows the temperature on the room sensor.
SUPPLY LINE
Shows the temperature on the supply line sensor.
The calculated supply temperature to the heating system group is within brackets.
RETURN LINE
Shows the temperature on the return line sensor.
The stop temperature, MAX RETURN is within brackets.
SYSTEM SUPPLY
Displays the temperature of the system supply line sensor at the buffer tank system or if the external auxiliary
heater is activated.
DISTRIBUTION
CIRCUIT 1
Shows the temperature on the distr. cir. 1 sensor.
The calculated supply temperature for the shunt group is within brackets.
DISTRIBUTION
CIRCUIT 2
Shows the temperature on the distr. cir. 2 sensor.
The calculated supply temperature for the shunt group is within brackets.
BUFFER TANK
Shows the temperature on the sensor for the buffer tank.
HOT WATER
Displays the temperature on the hot water sensor on the condition that hot water production is permitted.
INTEGRAL
Shows the actual calculated value for the integral.
REFR 1
Shows the temperature at refrigerant sensor 1.
REFR 2
Shows the temperature at refrigerant sensor 2.
POOL
Displays the temperature on the pool sensor on the condition that pool operation is permitted.
Commissioning
VIGFH102
Danfoss Heating Solutions
18