© Danfoss | DCS (ADAP-KOOL®) | 2018.12

RI8SP202 | 5

Menu Survey

Function

Min

Max

Factory

Unit

AKM name

Gas level

Sensor 1 Actual gas level in % of range

0.0

100.0

-

%

Gas level %

Sensor 1 Actual gas level in ppm

0

FS

2

 

-

ppm

Gas level ppm

Sensor 2 Actual gas level in % of range

0.0

100.0

-

%

2: Gas level %

Sensor 2 Actual gas level in ppm

0

FS

2

 

-

ppm

2: Gas level ppm

Alarms

Alarm settings

Indication of critical alarm (critical alarm of Gas1 or Gas2 active)
0:  No active alarm(s)
1: Alarm(s) active

0

1

0

-

GD alarm

Common indication of both critical and warning alarm as well as 
internal and maintenance alarms 
0:  No active alarm(s), warning(s) or errors
1: Alarm(s) or warning(s)) active

0

1

0

-

Common errors

Gas 1 Alarm limit in %. 
Alarm limit in % (0-100),  not lower  1: Warn Limit allowed 

0.0

100.0

HFC: 25 
CO2: 25 
R290: 16

%

Crit. limit %

Gas 1 Alarm limit in ppm
Alarm limit in ppm; 0: Warning Signal deactivated  

0

FS

2

 

HFC: 500 
CO2: 5000 
R290: 800

ppm

Crit. limit ppm

Gas 1. Warning limit in % (0-100) 

0

100.0

HFC: 25 
CO2: 25 
R290: 16

%

Warn. limit %

Gas 1 
Warning limit ppm 0: Warning Signal deactivated

0.0

FS

2

HFC: 500 
CO2: 5000 
R290: 800

ppm

Warn. limit ppm

High (critical and warning) alarm delay in seconds, if set to 0: no delay 0

600 

0

sec

Alarm delay s

When set to 1, the audible sounder are reset (and the relays if 
defined: Relay rest enable) to no alarm indication. When the alarm is 
reset or the time out duration is exceeded, the value is reset to 0.
Note: The alarm condition is not reset only the output indication is 
reset. 
0: Alarm outputs not reset 
1: Alarm outputs reset –buzzer muted and relays reset if configured

0

1

0

-

Reset alarm

Duration of alarm reset before automatic re-enable of alarm outputs. 
A setting of 0 disables the ability to reset alarm.

0

9999

300

sec

Reset alarm time 

1

Relay reset enable:
Relay reset with alarm acknowledge function
1= (default) Relays wil be reset if the alarm acknowledge function is 
activated 
0: Relays remains active until the alarm condition clears

0

1

1

-

Relay rst enable 

1

Gas 2 Alarm limit in %. 
Alarm limit in % (0-100),  not lower  1: Warn Limit allowed 

0.0

100.0

CO2: 25 

%

2:Crit. limit %

Gas 2 Alarm limit in ppm
Alarm limit in ppm; 0: Warning Signal deactivated  

0

FS

2

 

CO2: 5000  ppm

2:Crit. limit ppm

Gas 2. Warning limit in % (0-100) 

0

100.0

CO2: 25 

%

2:Warn. limit %

Gas 2. Warning limit ppm 0: Warning Signal deactivated

0.0

FS

2

CO2: 5000  ppm

2:Warn. limit ppm

High (critical and warning) alarm delay in seconds, if set to 0: no delay 0

600 

0

sec

2:Alarm delay s

Service

Status of the sensors warm up period
0:Ready
1: Warming Up 1 or more sensors

0

1

0

-

DGS Warm-up

SW 1.1x

Summary of Contents for DGS

Page 1: ...as a safety device securing a reaction to a detected high gas concentration If a leakage occurs the DGS will provide alarm functions but it will not solve or take care of the leakage root cause itself Regular Test To maintain product performance and comply with the local requirements the DGS must be tested regularly DGS s are provided with a test button that may be activated to validate the alarm ...

Page 2: ...y to the Ackn Test button DC supply for external Strobe Horn Whether the DGS is powered by 24Vdc or 24Vac a 24Vdc power supply max 50mA is available between terminals 1 and 5 on connector x1 Jumpers JP4 open 19200 Baud JP4 closed 38400 Baud default JP5 open AO 0 20 mA JP5 closed AO 0 10 Volt default Note the DGS must be power cycled before any change to JP4 take effect Cable Gland opening Danfoss ...

Page 3: ...r general BMS system set the Modbus address using the DGS Service Tool using password 1234 when prompted See the DGS User Guide for details on operating the DGS Service Tool The Baud Rate is adjusted by jumper JP4 As default the setting is 38 4kBaud For integration with AK SM 720 350 change the setting to 19 2kBaud For more information about data communication see document RC8AC Sensor replacement...

Page 4: ... bottle with pressure regulator and a calibration adapter In doing so the set alarm thresholds are exceeded and all output functions are activated It is necessary to check if the connected output functions are working correctly e g the horn sounds the fan switches on devices shut down By pressing the push button on the horn the horn acknowledgment must be checked After removal of the reference gas...

Page 5: ...y 0 600 0 sec Alarm delay s When set to 1 the audible sounder are reset and the relays if defined Relay rest enable to no alarm indication When the alarm is reset or the time out duration is exceeded the value is reset to 0 Note The alarm condition is not reset only the output indication is reset 0 Alarm outputs not reset 1 Alarm outputs reset buzzer muted and relays reset if configured 0 1 0 Rese...

Page 6: ...on 0 32000 HFC 365 CO2 1825 R290 182 days 2 Days til calib Gas 2 Shows how many of Sensitivity remaining Note Value only updated after calibration 0 100 100 2 Rem sensivity Activates a mode which simulates an alarm Buzzer LED and relays all activate 1 Test function no alarm generation possible now Automatically falls back to Off after 15 min 0 back to Normal mode 0 1 0 Test Mode Analog Output Selc...

Page 7: ...l operation i e alarms are created and cleared 1 Alarms inhibited i e alarm status is not updated e g due to DGS in test mode 0 1 0 Alarm inhibited Critical Limit alarm 0 Alarm not active 1 Alarm gas limit exceeded and delay expired 0 1 0 2 Criti limit 0 OK 1 Fault Out of range under test Overrange or Underrange 0 1 0 2 Out of range 0 OK sensor no errors 1 Fault Sensor and Head failures 0 1 0 2 Wr...

Page 8: ... reached the end of life Carry out calibration routine or replace with a new factory calibrated sensor Yellow AO configured but not connected only 0 20 mA output Check wiring Sensor type does not match DGS specification Check gas type and measuring range Sensor may be disconnected from printed circuit board Check to see sensor is properly connected The sensor has been damaged and needs to be excha...

Reviews: