4
TPOne-S
OK
Mounting
Thermostat positioning:
30
cm
MIN
30m MAX
Please note: This product should only be installed by
a qualified electrician or competent heating installer
and should be in accordance with the local wiring
regulations.
Note: These products use RF (Radio Frequency) technology to
communicate with each other and it is important that care is taken
during installation to ensure good wireless connection. Building
structure and materials may influence performance and large metal
objects such as boiler cases, appliances or mirrors in line of sight
between the thermostat and the receiver will prevent communication.
The receiver should be mounted near to the heat source leaving
a minimum distance of 30cm away from any metal enclosures or
appliance and positioned so that no large metal obstruction is between
the receiver and thermostat. The thermostat can be mounted remotely
up to 30m from the receiver while considering signal strength will
be reduce as it passes through walls and ceilings. Walls and ceilings
containing steel reinforcement or with metal foil lined insulation will
also have a significant effect on communication distance and may
block signal completely.
It is recommended that the RF connection should be checked
before permanently mounting the thermostat and where necessary
the location of the thermostat must be moved to ensure reliable
communication. The thermostat should be mounted at a height of
approximately 1.5m from the floor and away from draughts or heat
sources such as radiators, open fires or direct sunlight.