background image

M2M

The M2M Bridge establishes a connection that transmits CAN messages between CS10 devices using an
existing WiFi-connection between them. The two devices can be connected peer to peer where one
device is configured as an Access point, and the other one is configured to station mode (DHCP must be
disabled). Alternatively, both can be configured to station mode to connect to a router, in this case DHCP
needs to be enabled.

For a successful M2M configuration one device needs to be configured as a master, the other one as a
slave using the field Role.

For the slave only the Local Password must be applied which needs to match the Remote Password of
the master device. Due to its multipurpose meaning the local password can be found on the Overview
page.

For the master device the following settings must be applied. The operation mode can be set in the field

Remote EID mode. In auto-mode a connection to the first accessible Interlink-device to be found is
established while in manual mode a connection to the device with the Interlink EID to be set in the field

Remote EID is established. To connect to a device the remote password must be applied in the field

Remote Password where it must match the local password of the slave device. If the option Autoenable
is set, the M2M unit is automatically enabled when the device is powered. The set of messages to be
transferred to and from the connected device is defined in the sections Remote/Local filter

configuration . In the dropdown list above there are three options available where “Pass all messages”
let’s all messages pass through while “Block all messages” let’s no message pass through. The option
“Define messages” offers the opportunity to explicitly select up to 10 messages to be transmitted. If the
set of Filter/Mask is set to 0 for both all messages will pass the bridge. If the set of Filter/Mask is set to
0x80000000 for both the message is blocked. In the Output filter configuration section all outgoing
messages are defined, while in the Input filter configuration section all incoming messages are defined.
All these settings get applied to the device when pressing the button Save.

Technical Information

PLUS+1® CS10 Wireless Gateway

Configuration

 

14 | 

©

 Danfoss | November 2020

BC356772124151en-000102

Summary of Contents for CS10

Page 1: ...Technical Information PLUS 1 CS10 Wireless Gateway www danfoss com...

Page 2: ...ory Table of revisions Date Changed Rev November 2020 Removed some redundancy 0102 October 2020 First edition 0101 Technical Information PLUS 1 CS10 Wireless Gateway 2 Danfoss November 2020 BC35677212...

Page 3: ...0 7 Overview 7 Station mode 8 Access point 11 CAN 13 M2M 14 LEDs 15 Programming Nonfunctional specifications 16 PLUS 1 compliance development 16 Product ratings Environmental testing criteria 17 Power...

Page 4: ...pecifications contain detailed information about the module BIOS PLUS 1 BIOS functionality is pin dependent Pins are defined in module data sheets as C connector number p pin number API specifications...

Page 5: ...ponsibility for Danfoss products being incorrectly applied or the system being programmed in a manner that jeopardizes safety All safety critical systems shall include an emergency stop to switch off...

Page 6: ...Fi works by default as an access point with the SSID being DanfossCS10_MAC address and the password being the device s seriel number Specification WiFi The WiFi functionality offers the possibility to...

Page 7: ...elect Replace Missing ECU and former address will be replaced by the current address of the device While in an M2M bridge making an Interlink connection will break the M2M bridge functionality Overvie...

Page 8: ...ce the device is powered it will automatically try to connect to the configured network 5 Select the appropriate Country code 6 If DHCP mode is set to DHCP diabled adjust the following settings IP add...

Page 9: ...established Link quality shows the quality of the connection when it s established Connection IPv4 address shows the assigned network address The section AP list shows the networks available Using th...

Page 10: ...Technical Information PLUS 1 CS10 Wireless Gateway Configuration 10 Danfoss November 2020 BC356772124151en 000102...

Page 11: ...and Netmask 6 If DHCP enable is set all clients that connect as DHCP client automatically retrieve an address from the range defined in the fields IPv4 start address and IPv4 end address for the time...

Page 12: ...A list of the devices connected to the access point is provided in the section Connected clients The number of clients is shown in the field Amount In the field Index the device at this index in the...

Page 13: ...xt ID and Mask must be applied The option Protect leaves the latest received message at the output of the corresponding CAN receiver Pressing the Save button sends the applied configuration to the dev...

Page 14: ...erlink EID to be set in the field Remote EID is established To connect to a device the remote password must be applied in the field Remote Password where it must match the local password of the slave...

Page 15: ...r Status Using the Reset button applies a set of default parameters LEDs There are four LEDs on every CS10 module one blue one white one green and one red These are under application software control...

Page 16: ...pany software development standards must be adhered to At time of initial development Danfoss Power Solutions SW PDP v5 00 70036901v5 00 is the adopted standard Technical Information PLUS 1 CS10 Wirel...

Page 17: ...le standard Comment Chemical resistance ISO 16750 5 Mechanical environment Description Applicable standard Comment Vibration IEC 60068 2 64 test Fh Bump IEC 60068 2 29 test Eb Shock IEC 60068 2 27 Ea...

Page 18: ...supply pins must be connected to the vehicle power supply to support advertised module maximum output current capacity DO NOT use module power supply pins to supply power to other modules on a machine...

Page 19: ...in Function Pin Function 1 GND 4 CAN Low 2 Power 5 Key Switch 3 CAN High 6 CAN Shield Pairing Hot plugging Machine power should be off when connecting CS10 modules to mating connectors Mounting Care m...

Page 20: ...isplays microcontrollers and expansion modules be connected to a common ground A dedicated ground wire of appropriate size connected to the machine battery is recommended Technical Information PLUS 1...

Page 21: ...effects of EMI RFI radiation Do not run wires near sharp metal corners consider running wires through a grommet when rounding a corner Do not run wires near hot machine members Provide strain relief f...

Page 22: ...foss Power Solutions US Company 2800 East 13th Street Ames IA 50010 USA Phone 1 515 239 6000 Danfoss Power Solutions Trading Shanghai Co Ltd Building 22 No 1000 Jin Hai Rd Jin Qiao Pudong New District...

Reviews: