Installation
Leak detection
Leak detection must be carried out using a
mixture of nitrogen and refrigerant or nitrogen
and helium, as indicated in the table below.
Never use other gasses such as oxygen, dry air
or acetylene as these may form an inflammable
mixture. Pressurize the system on HP side first
then LP side.
Leak detection with refrigerant
Leak detection with a mass spectrometer
Nitrogen and R410A
Nitrogen and Helium
Note 1: Leak detection with refrigerant may be forbidden in some countries. Check local regulations.
Note 2: The use of leak detecting additives is not recommended as they may affect the lubricant properties.
Moisture obstructs the proper functioning of
the compressor and the refrigeration system. Air
and moisture reduce service life and increase
condensing pressure, and cause excessively high
discharge temperatures, which can destroy the
lubricating properties of the oil. Air and moisture
also increase the risk of acid formation, giving
rise to copper platting. All these phenomena
can cause mechanical and electrical compressor
failure.
For these reasons it’s important to perform a
vacuum dehydration on the system to remove
all residual moisture from the pipe-work after
assembly; CH compressors are delivered with <
100 ppm moisture level. The required moisture
level in the circuit after vacuum dehydration
must be < 100 ppm for systems with a CH.
• Never use the compressor to evacuate the
system.
• Connect a vacuum pump to both the LP & HP
sides.
• Evacuate the system to a pressure of 500 μm Hg
(0.67 mbar) absolute.
Do not use a megohm meter nor apply power to
the compressor while it’s under vacuum as this
may cause internal damage.
Vacuum evacuation and
moisture removal
Filter driers
A properly sized & type of drier is required.
Important selection criteria include the driers
water content capacity, the system refrigeration
capacity and the system refrigerant charge.
The drier must be able to reach and maintain
a moisture level of 50 ppm end point dryness
(EPD).
For new installations with CH compressors with
polyolester oil, Danfoss recommends using the
Danfoss DML (100% molecular sieve) solid core
filter drier. Molecular sieve filter driers with loose
beads from third party suppliers shall be avoided.
For servicing of existing installations where acid
formation is present the Danfoss DCL (solid core)
filter driers containing activated alumina are
recommended.
The drier is to be oversized rather than under
sized. When selecting a drier, always take into
account its capacity (water content capacity),
the system refrigeration capacity and the system
refrigerant charge.
After burn out, remove & replace the liquid line
filter drier and install a Danfoss type DAS burnout
drier of the appropriate capacity. Refer to the DAS
drier instructions and technical information for
correct use of the burnout drier on the liquid line.
For the initial charge the compressor must not
run and eventual service valves must be closed.
Charge refrigerant as close as possible to the
nominal system charge before starting the
compressor. This initial charging operation must
be done in liquid phase. The best location is on
the liquid line between the condenser outlet
and the filter drier. Then during commissioning,
when needed, a complement of charge can be
done in liquid phase: slowly throttling liquid in
on the low pressure side as far away as possible
from the compressor suction connection while
compressor is running. The refrigerant charge
quantity must be suitable for both summer and
winter operations. Vacuum or charge from one
side can seal the scrolls and result in a non-
starting compressor. When servicing, always
ensure that LP/ HP pressures are balanced before
starting the compressor.
Be sure to follow all government regulations
regarding refrigerant reclamation and storage.
For more detailed information see
“Recommended refrigerant system charging
practice” news bulletin FRCC.EN.050.
Refrigerant charging
37
FRCC.PC.026.A4.02
Application Guidelines