background image

© Danfoss | 2019.02 | 15

VI.D3.C2.02 

CCR2+ Controller

78

Slave Unit Comm. 
Status

Shows Slave Unit communication status between CCR2+ Controller

0% – 

no communication

100% – 

communication OK

Possible (readable values): 0 – 100%

Save Settings

Click »Save Settings« to confirm changes

Note: 

In case of changing IP address in CCR+ Controller, changes should also be applied in PC local network settings.

FIRMWARE MENU:

Name

Description

Upgrade of firmware

To update CCR2+ with new firmware first download firmware file from Danfoss website. 
Then follow procedure: Browse file -> Start upgrade! 

Reset settings to default

To return all setting to default (except Network settings) click on “Return Defaults” 

Reset to defaults passwords To reset all passwords to defaults (admin1234) click on “Reset Passwords«.
Reset network settings

Reset all network settings to defaults

NOTE:

 When uploading firmware, do not interrupt the web browser by closing the window, clicking a link, or loading a new page. No 

not power-off CCR2+. It could corrupt the firmware.

When the upload is complete, CCR+ restarts. The upgrade process typically takes several minutes.

LOGIN MENU – push user to change password

Name

Description

Login

Access with login password enable changes in all setting

Skip login

Access without password allows only data readings. Changes of settings values can not be done.

11. Service/trouble shooting

Reset Wi-Fi password

Available via long press on reset button (located on LAN port) for at least 5 seconds.
Wi-Fi password is reset to “admin00x” where x is the number of BT (blue) LED blinks.

Reset the setting only

Go to firmware menu and click on “Return Defaults”

Reset password only 
(but not change other 
parameters)

Go to firmware menu and click on “Reset passwords”

Recovery (device can be 
recover back to factory 
firmware)

Via long press on reset button, power down and with access code “

369

” (code for recovery to 

default firmware). To perform a recovery, you need to make these steps:

1.  turn off power supply
2.  press hardware button
3.  turn on power supply, power led will be ON 
4.  hold button for more than 5 sec until ALL 3 leds turned ON
5.  when all 3 leds is turned immediately release the button

From this moment you need to enter 3 digits code
In this mode there are two hardware button function: 

- short press increase code number,
- long press switch to next code digit

Currently code number is signalled by lighting of led diode: blue led = 1 digit, white led = 2 digit, 
orange led = 3 digit

Example to enter code 123:

- first led diode (blue) is turned ON, then make a short button press 1 time, blue led should 

blink once

- make a long press until white led is turned on
- using short button press 2 times, white led should blinks 2 times
- make a long press until orange led is turned on
- using short button press 3 times, orange led should blinks 3 times
- if code is entered properly than recovery has started. 

DO NOT TURN OFF POWER SUPPLY!

10.  CCR2+ DASHBOARD 
(Web App Screen) 

(continuous)

Summary of Contents for CCR2+

Page 1: ... Danfoss 2019 02 VI D3 C2 02 1 ENGLISH CCR2 Disinfection Process Control Temperature Registration www danfoss com CCR2 Controller Operating Guide Master Controller Slave Unit ...

Page 2: ... S2 S7 S8 S9 S S19 S20 MTCV MTCV MTCV MTCV MTCV MTCV MTCV MTCV V1 TWA V2 TWA V7 TWA V8 TWA V9 TWA V TWA V19 TWA V20 TWA TVM TVM TVM 1 2 7 8 9 19 20 5 4 3 H C MIX 5 4 3 H C MIX 5 4 3 H C MIX TVM TVM TVM 5 4 3 H C MIX 5 4 3 H C MIX 5 4 3 H C MIX TVM TVM TVM 5 4 3 H C MIX 5 4 3 H C MIX 5 4 3 H C MIX TVM TVM TVM 5 4 3 H C MIX 5 4 3 H C MIX 5 4 3 H C MIX TVM TVM TVM 5 4 3 H C MIX 5 4 3 H C MIX 5 4 3 H ...

Page 3: ...dbus RS 485 B port B Modbus RS 485 A port A Modbus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Heat Force O2 output Start next CCR Slave Unit O3 output Disinfection finished O4 output Alarm C V1 4 C common port dedicated to actuators V1 4 V1 V4 outputs to actuators C V5 8 C common port dedicated to actuators V5 8 V5 V8 outputs to actuators C V9 12 C common port dedicated to a...

Page 4: ...ty Socket Place G S0 B3 B2 B1 S4 S3 S1 S8 S7 S5 S12 S11 S9 S16 S15 S13 S20 S19 S17 G G G G G S2 S6 S10 S14 S18 Actuators of risers valves V1 V20 Open collector outputs connect to 0V V1 0V 24VDC V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16 V17 V18 V19 V20 TCP IP LAN BMS CCR SLAVE WEB SERVER BMS TCP IP ETHERNET INTERNET KO1 KO2 KO3 KO4 Heat force Start next CCR Disinfection finished Alarm Ris...

Page 5: ...nit Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuators V24 V28 outputs to actuators C V29 32 C common port dedicated to actuators V29 V32 outputs to actuators C V30 36 C common port dedicated to actuators V33 V36 outputs to actuators Connector port De...

Page 6: ...ower Supply Board 24VDC 0VDC Lbus G S0 20180904 Connection of two CCR2 with individual S0 sensor in sequence mode Slave Controller and Power Supply Board 24VDC 0VDC Lbus G V24 V23 V21 V28 V27 V25 V32 V31 V29 V36 V35 V33 C C C C V22 V26 V30 V34 Module 1 Input Output Board Module 2 Input Output Board Module 3 Input Output Board Module 4 Input Output Board S24 S23 S21 S28 S27 S25 S32 S31 S29 S36 S35 ...

Page 7: ...VDC Lbus G S0 TEMP S 0 KO1 FORCE HEATING SOURCE 20180904 Connection of two CCR2 with individual S0 sensor in sequence mode Slave Controller and Power Supply Board 24VDC 0VDC Lbus G V24 V23 V21 V28 V27 V25 V32 V31 V29 V36 V35 V33 C C C C V22 V26 V30 V34 Module 1 Input Output Board Module 2 Input Output Board Module 3 Input Output Board Module 4 Input Output Board S24 S23 S21 S28 S27 S25 S32 S31 S29...

Page 8: ...n 20 C 120 C Measuring accuracy 0 1 K Inputs B1 B2 and B3 Free contact 5 V 1 mA Number of control valves risers 20 additional 16 with system extension via CCR Slave Unit Output signal to actuators 24 VDC max 1 A Alarm signal output 24 VDC max 1 A Relay output 0 24 DC max 1 A Type of memory Build In Capacity of memory 8 GB Timer Real time clock Built in battery service life 10 years Communication i...

Page 9: ...an for Wireless Network Connection 4 Select CCRplus 5 Enter password default is admin1234 4 Switching the control on Before switching the control on for the first time disconnect all cables and connect a 24 VDC source to the disconnected power plug Use a voltmeter to measure the voltage on the power cable plug before it is connected to the control If the voltage is correct 1 Read the instructions ...

Page 10: ...ramme not active 2 S0 main temp S0 value of C supply temperature The same readings apply to sensors S1 S20 Open no sensor or break sensor circuit Closed shortcut to ground in sensor circuit If the S0 is disinfection source statutes are shown in color Grey S0 is start disinfection source Red S0 temp is OK greater than disinfection temp Blue S0 temp is too low during disinfection process lower than ...

Page 11: ...finish Close when disinfection is finished in sequence mode 17 Disinfection Disinfection process is enabled or disabled can be changed in User menu Disinfection 18 Total Dis Adv Advance of Disinfection progress calculated from all active and non active risers 19 Dis timeout Time to finish 20 Divide adv Advance of Disinfection progress calculated from active risers After divide time period Divide a...

Page 12: ... divide adv Dividing risers into groups If dividing is Enable system is counting progress of disinfection of active risers between divide time period If in divide time period progress of disinfection is less than Min divide adv Active risers will be automatical divided to half New active group will continue with most promising hottest risers 40 Risers number Number of risers connected to the CCR2 ...

Page 13: ...d to G and sensor S0 reports a temperature higher than the disinfection temperature in the scheduled time period Factory setting S0 51 DisSources type Relevant for input StillOn Disinfection is started when input contact is shorted to M Pulse Disinfection is started by short pulse of input contact to M Factory setting Pulse 52 Date format Form of date display YY MM DD year month day YY DD MM year ...

Page 14: ...Enable Modbus is switch on Disable Modbus is switched off 65 Modbus baudrate Type of date transmission ModBus 96 9 600 Mod Bus 19 19 000 ModBus 38 38 400 FBus Factory setting ModBus 96 66 Modbus parity None transmition parity disabled Even Even type of transmition parity enabled Odd Odd type of transmition parity enabled Factory setting Odd 67 Modbus address Unit Address for Mobus RTU RS485 Factor...

Page 15: ...Reset Wi Fi password Available via long press on reset button located on LAN port for at least 5 seconds Wi Fi password is reset to admin00x where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmware menu and click on Reset passwords Recovery device can be recover back to fac...

Page 16: ...our Tuesday Start minute Tuesday Stop hour Tuesday Stop minute Tuesday Active Tuesday Start hour Wednesday Start minute Wednesday Stop hour Wednesday Stop minute Wednesday Active Wednesday Start hour Thursday Start minute Thursday Stop hour Thursday Stop minute Thursday Active Thursday Start hour Friday Start minute Friday Stop hour Friday Stop minute Friday Active Friday Start hour Saturday Start...

Reviews: