The grey
side of the
ECL Card
Ex
tended ser
vic
e
32l
Service parameter(s) 174-198
196 Service pin - LON
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).
197 LON reset
Circuit
Setting range
Factory setting
I
ON / OFF
ON
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).
198 Daylight saving time changeover
Circuit
Setting range
Factory setting
I
ON / OFF
ON
Choose whether you want the change to summer / winter time to
be automatic or manual.
ON: The controller’s built-in clock automatically
c / - one hour on the standardized
days for daylight saving time changeover for
Central Europe.
OFF: You change manually between summer and
winter time by setting the clock backward
or forward.
174 Motor protection
Circuit
Setting range
Factory setting
I
OFF / 10 ... 59 min.
OFF
Prevents the controller from unstable temperature control (and
resulting actuator oscillations). This can occur when there is
no DHW tapping, i.e. when the load is only due to the DHW
circulation, or when the heating demand in the heating circuit
is very low. The motor protection increases the lifetime of all
involved components.
OFF: Motor protection is not activated.
10 ... 59:
Motor protection is activated after the set
activation delay.
A high value should be used for DHW
installations with many consumers.