4
|
Compressor assembly
A
max. 30°,
max. 2 minutes
a
max. 15°,
continuous
operation
Fig. 4
Fig. 5
A
a
A
a
A
a
A
a
4.1 Setting up
Transport and suspension unit on the eyebolt (Fig . 4) or direct on the discharge line valve
(Fig. 5).
INFO
New compressors are factory-filled with inert gas. Leave this
service charge in the compressor for as long as possible and
prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
WARNING
Move compressors only with hoists that have adequate load-bear
-
ing capacity.
4.2 Maximum permissible inclination
ATTENTION Poor lubrication can damage the compressor. Respect the stated
values.
Fig. 6
Storage at (-40°C) - (+100°C), maximum permissible relative humidity 10% - 95%, no
condensation.
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible only
following consultation with Bock.
Setup on an even surface or frame with sufficient load-bearing capacity. Use all 4 fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.