background image

© Danfoss | DCS (az) | 2017.11 

IC.PI.P10.K8.53 / 520B8307 

3

Low pressure limiter 

Scale plate directly indicates Low Switching Point. There is no 
pointer for Differential.
Differential value is fixed and printed on the scale plate.
1.   Set Low Switching Point by adjusting range screw (fig. 7)
2.  High Switching Point is equal to Low Switching Point plus 
 Differential:

HIGH = LOW + DIFFERENTIAL

High pressure limiter

Scale plate directly indicates High Switching Point. There is no 
pointer for Differential.
Differential value is fixed and printed on the scale plate.
1.   Set High Switching Point by adjusting range screw (fig. 7)
2.  Low Switching Point is equal to High Switching Point less 
 Differential:

LOW = HIGH - DIFFERENTIAL

Protection for settings

The protective cap on adjustment screws may be used to lock 
and seal the settings (fig. 6)

Manual reset

For resetting use the screwdriver (Fig. 5)
Manual reset is possible to operate only after return of pressure 
to cut-in level.
Before releasing the reset, the cause of the shutdown must be 
found and eliminated.

BCP pressure controller with auto reset as a limiting 
device

Since the pressure controller

 

BCP has no lockout with manual 

resetting, this function must be realized externally as a part of a 
safety logic e.g. by external contactors and/or relays which then 
are to be used according to the requirements of prEN50156-1 
standard for safety relevant hardware.

External closure must not be interlocked, while loss of auxiliary 
energy must lead to a closure.
Resetting must not be automated; it has to be performed 
manually.
Resetting on fault must lead to a repeated closure. When BCP 
limits, for rising or falling application, the external safety logic 
must change to the fail safe position. 

Endurance of any external contactors and relays must be 
according to EN12952-11, which means 250000 switching cycles 
under conditions similar to operating conditions and be capable 
of a mechanical life time of 2 000 000 switching cycles. 
Conditions similar to operating conditions include chemical and 
climatic influences as well as electrical and mechanical stresses. 
In addition, contactors must fulfil EN60947 and relays must fulfil 
EN60255.

BCP with double bellows

BCP6, BCP6H, BCP7, and BCP7H have a double bellows; an outer 
bellows and a regulating (inner) bellows.
When system pressure exceeds the set value, the BCP will 
automatically stop the plant. The double bellows system prevents 
loss of media in the event of bellows rupture. A rupture in the 
inner bellows will cause the switch cut-out pressure to fall about 3 
times less the set value, thus the system will stop. A rupture in the 
outer bellows will cause the switch cut-out pressure to fall to about 
3 bar under the set value, thus providing a fail-safe function.

                                    
 

Safety requirements

Installation

•  Internal rules and legislation current in the country concerned  
  with respect to health and safety at work must be observed
•  For safety reasons, the installation of pressure switches must  
     be carried out only by qualified staff, trained in all technical 
     aspects of their operation,
•  Before installation the pipes must be depressurised and purged  
  (empty of its fluid) in order to avoid any danger to the operator,
•  It is essential to isolate the power supply before wiring 
  connections are made to avoid possible electrical shock or 
  damage to equipment. Never touch live parts with your fingers  
  or with any tool,
•   DIN plug supplied by Danfoss and cable approved for the 
  application must be used. The cable must be connected with  
  adequate stress relief in order to prevent that pulling forces can  
  be carried through the cable to the plug.

Commissioning

Before putting pressure switch into operation, check that:
•  The working conditions are compatible with the details given 
      in the product label and this instruction notice,
•  All electrical connections have been properly made,
•  Installation is tight after assembly.

Operation

•   This notice must be available on site where pressure switches  
  are installed,
•  Internal rules and legislation current in the country concerned  
  with respect to health and safety at work must be observed
•  Personnel carrying out any intervention on the pressure switch  
  must be qualified for the task,
•  The pressure switch should be checked regularly to see if it  
  operates properly,
•  The BCP cover must not be removed under any circumstances
•  Any overload of the pressure switch must be prevented. 
  Overloaded or damaged switch must be exchanged.
•  It is essential to disconnect the plug before dismounting the 
     switch from the system,
•  All operations must be performed using suitable tools
•  It is the responsibility of the user to check that there is no 
  leakage after a faulty operation or on a periodic basis under  
  normal conditions,
•  Only pressure switches designed, constructed and released  
  by Danfoss must be used for the applicaiton concerned. 
  Danfoss can accept no responsibility in case of alterations   
     made on the pressure switches or the use of them against the 
  instructions of Danfoss,
•  Danfoss is not responsible for any damage which may be  
  caused by the use of parts, accessories or switches which are
     not original Danfoss parts.

Summary of Contents for BCP1H

Page 1: ...Danfoss 17 904 30 Installation guide Pressure switch Type BCP Danfoss DCS az 2017 11 IC PI P10 K8 53 520B8307 1 017R9328 017R9328 1 2 3 6 5 Mounting accessories 1 2 3 7 8 4 BCP01 min 20 mm permissible...

Page 2: ...mm if pipe is less than 1m long 15 mm if pipe is more than 1 m long 2 Where pipe supplies the limiter in addition to other limiters 20 mm for all lengths of pipes Functional testing of the limiter Si...

Page 3: ...rupture in the inner bellows will cause the switch cut out pressure to fall about 3 times less the set value thus the system will stop A rupture in the outer bellows will cause the switch cut out pres...

Page 4: ...et forsyner pressostaten s vel som andre pressostater 20 mm for alle r rl ngder Funktionstest af pressostaten Da trykbegr nseren ikke har nogen indbygget mulighed for funktionstest skal der laves en m...

Page 5: ...l BCP en automatisk standse anl gget Dobbeltb lgsystemet forhindrer tab af medie i tilf lde af b lgbrud Ved brud p den indre b lg falder apparatets brydetryk til ca 3 gange under den indstillede v rdi...

Page 6: ...lang ist 15 mm wenn das Rohr ber 1 m lang ist 2 Wenn das Rohr den Druckbegrenzer und andere Druckbegrenzer versorgt 20 mm f r alle Rohrl ngen Funktionspr fung des Druckbegrenzers Da der Druckbegrenzer...

Page 7: ...Wert berschreitet schaltet das Ger t automatisch die Anlage aus Das doppelte Wellrohrsystem verhindert Medienverlust bei einem Bruch des Wellrohrs Bei Bruch des inneren Wellrohrs schaltet der Druckreg...

Page 8: ...us d 1m de long 2 Pour un tuyau alimentant ce limiteur en plus d autres limiteurs 20 mm quelle que soit la longueur du tuyau Test fonctionnel du limiteur Comme il est impossible d effectuer un test fo...

Page 9: ...ement l installation Le syst me double soufflet vite la perte de fluide en cas de rupture d un soufflet En cas de rupture du soufflet int rieur la pression d ouverture du r gulateur chute environ 3 fo...

Page 10: ...be preverse esta circunstancia donde se encuentre la caldera para poder realizar pruebas de funcionamiento La prueba de funcionamiento no tendr a que disminuir la seguridad de la caldera ni la operati...

Page 11: ...rodujera la ruptura del fuelle el sistema de doble fuelle evitar a que se perdieran los medios La ruptura del fuelle interior provocar una disminuci n de la presi n de desconexi n del controlador 3 ve...

Page 12: ...m 2 Se il tubo alimenta questo ed altri pressostati 20 mm per tubi di qualsiasi lunghezza Collaudo funzionale del pressostato di blocco Dal momento che il pressostato di blocco non dispone di metodi...

Page 13: ...offietto esterno e un soffieto di regolazione interno Quando la pressione del sisterna supera il valore impostato il BCP arresta automaticamente l impianto Il sistema con doppio soffietto evita perdit...

Reviews: