The digits indicate the set value as follows:

No.

Parameter settings

Settings range

Default

WT-D/DR WT-P/PR

P01 Working mode

01: Manual

02: Advanced Programmable Timer

NA

02

P02 Temperature control mode

01: Only room temp.;

02: Room and floor temp.;

03: Only floor temp.

01

01

P03 High room temp. limit

5-35° C (only for 01 and 02 in P02)

30° C

30° C

P04 Low room temp. limit

5-35° C (only for 01 and 02 in P02)

5° C

5° C

P05 Floor temp. limitation mode

01: High temp. limitation;

02: Low temp. limitation (only for 02 in P02)

01

01

P06 Floor temp. limitation setpoint

20-45° C (only for 02 in P02)

35° C

35° C

P07 High floor temp. limit

20-45° C (only for 03 in P02)

35° C

35° C

P08 Low floor temp. limit

20-45° C (only for 03 in P02)

20° C

20° C

P09 Frost protection

01: Enable; 02: Disable

01

01

P10 Frost protection setpoint

5-17° C

5° C

5° C

P11 Timer display option

01: 24 h; 02: 12 h

NA

01

P12 Room temp. display option at 

shutdown

01: No display current temp.;

02: Display current temp.

01

01

P03 to P08 appear on relevant temperature control mode.

10 

Error Messages

E1

Room sensor failure

E2

Floor sensor failure

EE

EEPROM failure

Lo

Temperature lower than 0° C

Hi

Temperature higher than 50° C

All relay output will be turned off in all cases.