background image

pin

8

Instructions for installation and use 

TD & S substations

DKDHR 

VI.GP.U2.02 

Danfoss District Energy 

7. 

Enduser instructions, Initial adjustment/setting

Domestic hot water control

Danfoss PM2+P controller (Fig. 1) for domestic hot water. Set the DHW  

temperature by turning the adjuster lever towards red (hotter) or blue 

(colder). Start by turning the lever 

clockwise

 – until the pin is opposite 

the blue dot. Then turn the lever 

counter-clockwise

 until the tempera-

ture of the tap water is approx. 48°C during normal tapping flow (7–8 

litres per min.). The temperature must never exceed 55°C to prevent 

limescale deposits building up in the water heater. 

Danfoss PTC2+P controller (Fig. 2) for domestic hot water. Set the DHW 

temperature by moving the adjuster lever towards “+” (hotter) or “-” 

(colder). 

Start by turning the lever 

clockwise

 – until it stops/until you cannot 

turn it any further. Then turn the lever 

counter-clockwise

 until the 

temperature of the tap water is approx. 48°C during normal tapping 

flow (7–8 litres per min.). The temperature must never exceed 55°C to 

prevent limescale deposits building up in the water heater. 

Bypass or circulation thermostat

Thermostat (Fig. 3) that keeps the branch pipe warm in the summer 

or regulates the circulation temperature if domestic hot water recir-

culation has been established in the hot water system.

The thermostat should initially be set to position 3.  

Heating ciruit, Differential Pressure Controller

The differential pressure controller (Fig. 4) reduces the high, fluctuat-

ing pressure in the district heating network to a constant operating 

pressure over the unit. The differential pressure controller is initially 

set by the plumber in connection with the commissioning of the 

substation. If disruptions to the operation occur: noise in the radiator 

thermostats or poor regulation capacity, it may be necessary to reset 

the differential pressure controller to a lower operating pressure. We 

suggest that you contact your local plumber for assistance.

Regulation of  the supply temperature to the heating circuit

TD substations: 

The temperature cannot be regulated.

S substations:

 The supply temperature to the substation can be set by 

adjusting the thermostat T°C (Fig. 5). The thermostat will be set by the 

plumber in connection with the commissioning, but it may be neces-

sary to adjust it subsequently depending on the outdoor temperature.

Indicative scale setting: (the scale is on top of the lever)

  Pos. 4 ≈  50°C

 

5 ≈  60°C

 

6 ≈  70°C

The setting values may vary depending on the operating conditions. 

It is important to set the supply temperature to the radiators as low as 

possible. Use the radiator thermostats to regulate the room temperature. 

NB! For houses that are heated exclusively with floor heating.

 

The supply temperature should typically be set to approx. 30–35°C, 

which corresponds to pos. 2–2.5 on the thermostat (guiding value). 

The supply temperature must never exceed 40°C. (In addition, ALWAYS 

refer to the instructions from the floor supplier)

Alternatively, S substations can be controlled by an 

electronic control-

ler

, Danfoss ECL (fig. 6). See the enclosed documentation for same. 

Pump

 (only on S substations)

S substations are factory fitted with a pump (fig. 7). The pump setting is 

established in connection with the commissioning. Generally speaking, 

this setting is not to be altered. If it should nevertheless be necessary to 

change the pump setting, see the section concerning pumps in  the in-

stallation and commissioning sections regarding the individual products. 

In the summer, you can switch off the power to the pump at the mains 

if you want to save electricity by not heating your home.

Start-up and venting – see the installation and commissioning sections, 

if necessary.

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 7

or

or

Fig. 6

Summary of Contents for Akva Vita II TD

Page 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Vita II TD S Akva Lux II Akva Les II TD S Instructions for installation and use...

Page 2: ...ING STARTED 10 10 Installation instructions general 11 11 Installation instructions specially for S substations 12 12 Installation instructions recirculation connection 13 13 Adjustment and commission...

Page 3: ...Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer DHW Dirt strainer Sensor pocket White painted cover Filter on cold water supply The unit has been p...

Page 4: ...tic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer hot water Dirt strainer Sensor pocket White painte...

Page 5: ...exchanger brazed domestic hot water Domestic hot water controller PM2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor hea...

Page 6: ...Domestic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor heating thermometer domestic hot water...

Page 7: ...s and an excessively high return temperature in the district heating circuit poor cooling of the district heating water Cooling i e the difference between the supply and return temperature of the dist...

Page 8: ...ccur noise in the radiator thermostats or poor regulation capacity it may be necessary to reset the differential pressure controller to a lower operating pressure We suggest that you contact your loca...

Page 9: ...mperature in the district heating network can be up to 120 C and the operating pressure can be up to 16 bar Thismayresultinariskofscaldingfromtouchingthesubstationand fromoutflowofthemedium Exceedingt...

Page 10: ...tructions if necessary 3 NB Tighten all pipe connections as they may have loosened during transport and handling 4 On systems that feature a safety valve establish a drain con nection in compliance wi...

Page 11: ...Before filling the system with water retighten all the pipe connec tions because vibrations and shocks during transport and handling may have caused leaks Once the system has been filled with water ti...

Page 12: ...he right Alwaysmountthesensoronthecoldestsideofthebuilding normally the north side It must not be exposed to morning sunlight and must not be po sitioned above windows doors ventilation ducts balconie...

Page 13: ...ion pump outside the substation is stopped for a protracted period we recommend shutting off the by pass thermostat for the same period NB Please note that substations fitted with Danfoss AVE expansio...

Page 14: ...Danfoss FJVR bypass thermostat Fig 2 so that when water is tapped the water heater immediately starts to produce hot water We re commend setting of the thermostat in pos 3 If you have to wait a long t...

Page 15: ...oss FJVRbypassthermostat Fig 2 sothatwhenwateristapped thewater heaterimmediatelystartstoproducehotwater Werecommendsetting ofthethermostatinpos 3 Ifyouhavetowaitalongtime i e morethan 20 sec for hot...

Page 16: ...time i e more than 20 sec for hot water it may be necessary to position the thermostat higher than pos 3 If you want to avoid waiting time altogether you will need to set up domestic hot water recirc...

Page 17: ...mmediatelystartstoproducehotwater Werecommendsetting the thermostat to pos 3 If you have to wait a long time i e more than 20 sec for the hot water it may be necessary to set the thermostat to a posit...

Page 18: ...ating conditions Indicative supply temperatures 40 C when the outdoor temperature is 10 C 55 C when the outdoor temperature is 0 C 65 C when the outdoor temperature is 10 C It is important to set the...

Page 19: ...power consumption For floor heating systems and old radiator set ups with large pipes and radiators turn the red switch to the right constant curve and set it to Max pos initially Then reduce the pre...

Page 20: ...build up in plate heat ex changers for domestic hot water on account of the large temperature fluctuations and because aerated water is used on the secondary side If it becomes necessary to clean the...

Page 21: ...the pipe connections Check that the safety valve on the cold water supply is functioning correctly Check the functionality by turning the lever on the safety valve Check that all components are intact...

Page 22: ...g Automatic components controller incorrectly adjusted or defective or possibly a power outage The pump is not working The pump is set at a step that is too low not all system types Air pockets in the...

Page 23: ...ivery Check whether the pump is running and whether there is a power supply to the pump Make sure that there is no air in the pump housing No hot water Dirt strainer in the district heating sup ply li...

Page 24: ...y EN 61000 6 2 2005 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromagnetic compatibility Generic standard Emission for residential commercial and light indu...

Page 25: ...gulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks befor...

Page 26: ...26 DKDHR VI GP U2 02 Danfoss District Energy...

Page 27: ...27 27 Danfoss District Energy VI GP U2 02 DKDHR...

Page 28: ...Produced by Danfoss Redan A S 06 2012 VI GP U2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: