Instructions for installation and use 

TD & S substations

Danfoss District Energy 

VI.GP.U2.02 

DKDHR

Pump - Grundfos Alpha2 L, systems with self-acting thermostat

Note! Do not start up the pump untill the system has been filled with 

the flow media and vented. The pump is self-venting.

The pump is set at the factory to the “Highest proportional-pressure 

curve” (PP2). In this control mode, the pump performance and conse-

quently the power consumption are adjusted according to the heat 

demand in the system.

For 1-string systems it is recommended to set the pump to “ Lowest 

proportional-pressure curve PP1”, in accordance with the instructions to 

the right. 

If the heating system consists exclusively of floor heating, set the pump 

to “Lowest constant-pressure curve”

.

 Alternatively, set the pump in ac-

cordance with the instructions to the right or pursuant to the manual 

enclosed.

Pump - Grundfos Alpha 2 L on systems with ECL controller

On systems with ECL controller the pump must be set in 

pos. I or II 

(constant-pressure curve).

For further infomation about pump settings please refer to the en-

closed Grundfos instructions.

ALPHA2 L, 

Installation and operating instructions

 

Pump – Wilo Stratos Yonos OEM, systems with self-acting thermostat

Set the pump to its highest speed when starting operation of the system. 

On a conventional radiator system, turn the red switch to the left (vari-

able curve) and set it to “Max. pos.” initially. 

Then set the pump to the lowest possible position, depending on the 

heating requirement for the building - taking into account aspects such 

as cooling and power consumption. 

For floor heating systems and old radiator set-ups with large pipes and 

radiators, turn the red switch to the right (constant curve) and set it to 

“Max. pos.” initially. Then reduce the pressure until it matches the heating 

requirement for the building – taking into account cooling and power 

consumption.  

Pump – Wilo Yonos OEM, systems with Danfoss ECL

On systems with ECL controller turn the red switch to the right (constant 

curve) and set it to “Max. pos.” initially. Then set the pump to the lowest 

possible position, depending on the heating requirement for the build-

ing - taking into account aspects such as cooling and power consump-

tion. 

Venting: The pump features a built-in venting function, which can be 

used when the system needs to be bled. Turn the red switch to the verti-

cal position. The pump will then run a venting routine that lasts 10 min-

utes. There may be some noise during this phase. Once the 10-minute 

period is finished, reset the pump according to the instructions above.

For additional information, see the manual: 

Wilo Yonos PARA.

Summer operation (all pump types)

Summer operation (systems with self-acting thermostat)

In the summer, you can stop the pump by switching it off at the mains. 

However, remember to start the pump (briefly) at least once a month 

during the summer.

Summer operation (systems with Danfoss ECL 210)

Outside the heating period, the pump will be disconnected automati-

cally from the heating system. During the summer period, the controller 

will start the pump for a minute at least once every three days to prevent 

the pump from blocking.

Start-up after summer operation - venting

Please note that it may be necessary to vent the system again. To vent 

the system, use the vent valve in the substation or on the radiators and, 

if appropriate, the air valve at the highest point of the system.

Grundfos Alpha 2 L

Summary of Contents for Akva Vita II TD

Page 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Vita II TD S Akva Lux II Akva Les II TD S Instructions for installation and use...

Page 2: ...ING STARTED 10 10 Installation instructions general 11 11 Installation instructions specially for S substations 12 12 Installation instructions recirculation connection 13 13 Adjustment and commission...

Page 3: ...Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer DHW Dirt strainer Sensor pocket White painted cover Filter on cold water supply The unit has been p...

Page 4: ...tic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer hot water Dirt strainer Sensor pocket White painte...

Page 5: ...exchanger brazed domestic hot water Domestic hot water controller PM2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor hea...

Page 6: ...Domestic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor heating thermometer domestic hot water...

Page 7: ...s and an excessively high return temperature in the district heating circuit poor cooling of the district heating water Cooling i e the difference between the supply and return temperature of the dist...

Page 8: ...ccur noise in the radiator thermostats or poor regulation capacity it may be necessary to reset the differential pressure controller to a lower operating pressure We suggest that you contact your loca...

Page 9: ...mperature in the district heating network can be up to 120 C and the operating pressure can be up to 16 bar Thismayresultinariskofscaldingfromtouchingthesubstationand fromoutflowofthemedium Exceedingt...

Page 10: ...tructions if necessary 3 NB Tighten all pipe connections as they may have loosened during transport and handling 4 On systems that feature a safety valve establish a drain con nection in compliance wi...

Page 11: ...Before filling the system with water retighten all the pipe connec tions because vibrations and shocks during transport and handling may have caused leaks Once the system has been filled with water ti...

Page 12: ...he right Alwaysmountthesensoronthecoldestsideofthebuilding normally the north side It must not be exposed to morning sunlight and must not be po sitioned above windows doors ventilation ducts balconie...

Page 13: ...ion pump outside the substation is stopped for a protracted period we recommend shutting off the by pass thermostat for the same period NB Please note that substations fitted with Danfoss AVE expansio...

Page 14: ...Danfoss FJVR bypass thermostat Fig 2 so that when water is tapped the water heater immediately starts to produce hot water We re commend setting of the thermostat in pos 3 If you have to wait a long t...

Page 15: ...oss FJVRbypassthermostat Fig 2 sothatwhenwateristapped thewater heaterimmediatelystartstoproducehotwater Werecommendsetting ofthethermostatinpos 3 Ifyouhavetowaitalongtime i e morethan 20 sec for hot...

Page 16: ...time i e more than 20 sec for hot water it may be necessary to position the thermostat higher than pos 3 If you want to avoid waiting time altogether you will need to set up domestic hot water recirc...

Page 17: ...mmediatelystartstoproducehotwater Werecommendsetting the thermostat to pos 3 If you have to wait a long time i e more than 20 sec for the hot water it may be necessary to set the thermostat to a posit...

Page 18: ...ating conditions Indicative supply temperatures 40 C when the outdoor temperature is 10 C 55 C when the outdoor temperature is 0 C 65 C when the outdoor temperature is 10 C It is important to set the...

Page 19: ...power consumption For floor heating systems and old radiator set ups with large pipes and radiators turn the red switch to the right constant curve and set it to Max pos initially Then reduce the pre...

Page 20: ...build up in plate heat ex changers for domestic hot water on account of the large temperature fluctuations and because aerated water is used on the secondary side If it becomes necessary to clean the...

Page 21: ...the pipe connections Check that the safety valve on the cold water supply is functioning correctly Check the functionality by turning the lever on the safety valve Check that all components are intact...

Page 22: ...g Automatic components controller incorrectly adjusted or defective or possibly a power outage The pump is not working The pump is set at a step that is too low not all system types Air pockets in the...

Page 23: ...ivery Check whether the pump is running and whether there is a power supply to the pump Make sure that there is no air in the pump housing No hot water Dirt strainer in the district heating sup ply li...

Page 24: ...y EN 61000 6 2 2005 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromagnetic compatibility Generic standard Emission for residential commercial and light indu...

Page 25: ...gulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks befor...

Page 26: ...26 DKDHR VI GP U2 02 Danfoss District Energy...

Page 27: ...27 27 Danfoss District Energy VI GP U2 02 DKDHR...

Page 28: ...Produced by Danfoss Redan A S 06 2012 VI GP U2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: