Danfoss District Energy 

145X2085  /  AQ428255318526en-010101 DKDHR

Instructions 

 

 

Akva Lux II TDv

Reach

All products of the Akva Lux II TDv series comply with the provisions of 

the REACH regulation.

We are therefore obliged to inform our customers about the presence 

of substances according to the SVHC candidate list, if they are present. 

We hereby inform you: This product contains brass parts containing lead 

(CAS 7439-92-1) in a concentration above 1% (w/w)

.

Potential equalization / grounding

Equipotential bonding is understood as all measures for eliminating elec-

tri-cal potential differences (contact voltages), which can occur between 

eg two pipelines. Equipotential bonding is an important measure for pro-

tec-tion against electric shock. Equipotential bonding reduces corrosion 

in the heat exchanger, instantaneous water heaters, district heating sta-

tions and plumbing installations. Equipotential bonding should be in ac-

cordance with the provisions 60364-4-41: 2007 and IEC 60364-5-54: 2011. 

Binding point is marked with a grounding symbol on the bottom right 

corner of the mounting plate and there is a hole in the mounting plate 

and a label with grounding symbol.

Disposal

The station consists of materials that must not be disposed of with 

household waste. Disconnect the entire energy supply and disassem-

ble the product for disassembly and dispose of it in accordance with 

local regulations.

Disposal

Dispose of the packaging in accordance with the local regulations for 

disposal of used packaging materials.

The substation is made of materials that cannot be disposed of together 

with household waste.  

Close all energy sources and disconnect all connection pipes. Disconnect 

and dismantle the product for disposal in accordance with the applicable 

local regulations for the disposal of the individual components.

3.

 PRODUCT INTRODUCTION

Application

Akva Lux II TDv is a fully insulated substation substation for direct heating and instan-

taneous domestic hot water for large singlefamily, houses. The Akva Lux II TDv is also 

suitable for small apartment houses with 2-4 apartments.

Construction

The Akva Lux II TDv is prefabricated with a brazed, highly efficent Danfoss plate heat 

exchanger type XB06H-1 26 or XB06H-1 40 for domestic hot water production, an energy-

saving domestic hot water controller Danfoss PTC2+P as well as a Danfoss FJVR thermostat 

for control of the bypass/circulation temperature, non-return valve on the cold water 

connection, differential pressure controller and strainer.

The Akva Lux II TDv is also equipped with a zone valve RA-C and thereby prepared for 

fitting of a thermal actuator TWA-Q, which enables connection to an electronic 

programmable room thermostat. 

The substation is prepared for domestic hot water recirculation, if required.

A circulation set and a safety set is available as optional equipment.

Design

The design emphasizes the user-friendly placement of all components.   

The Akva Lux II TDv supplied with an elegant insulation cover and can be supplied with 

a white-lacquered cover in modern design.

Akva Lux II TDv units are prepared for merger with Danfoss distribution systems, mounted 

underneath the unit, for use on DHW and heating systems with concealed pipe installations.

Heat exchanger for DHW heating

The substation is based on a brazed, highly efficient plate heat exchanger, which is 

controlled by a thermostatic and pressure controlled PTC2+P DHW controller.

The Danfoss PTC2+P DHW controller with integrated differential pressure controller 

and energy saving function ensures that the heat exchanger is cold during standby.

Bypass (thermostatic circulation)

The water heater is supplied with a thermostatically controlled bypass, which ensures 

that hot water is produced immediately, when tapping starts. The bypass temperature 

is set with due consideration of the best possible DHW comfort and economy. DHW 

re-circulation can be easily added to the substation when it is required.

Domestic hot water recirculation

The substation is prepared for connection to systems with DHW recirculation. DHW 

installations with recirculation ensures DHW at the tap site without waiting time and 

without water waste. Switching to DHW recirculation is possible from a constructional 

point of view, requiring only mounting of a separate circulation set (see options). The 

circulation temperature is set independently of the set DHW temperature. This ensures 

the best possible DHW comfort, very low standby losses and thus a very good district 

heating economy.

Service and maintenance

The substation is very service-friendly and easy to install. It is mounted on the wall and as 

all pipes are placed in pipe bracket distance, it is possible to establish a nice piping either 

in the top or in the bottom of the substation.

Summary of Contents for Akva Lux II TDv

Page 1: ...Dv Fully insulated district heating substation for district heating and in stantaneous DHW Fullyinsulateddistrictheatingsubstationforlow temperaturedistrictheatingandinstantaneousdomestichotwater Akva...

Page 2: ...ple 8 7 0 General 9 8 0 Recirculation 10 9 0 Safety set 13 10 0 Adjustment and commissioning 14 11 0 Domestic hot water 16 12 0 Maintenance 17 13 0 Troubleshooting 19 14 0 EU Declaration of conformity...

Page 3: ...red in a dry heated i e frost free room Relative humidity max 80 and storage temperature 5 70 C Theunitsmustnotbestackedhigherthanthelimitatthefactory max 8layers Unitssuppliedincardboardpackagingmust...

Page 4: ...rictheatingsta tionsandplumbinginstallations Equipotentialbondingshouldbeinac cordancewiththeprovisions60364 4 41 2007andIEC60364 5 54 2011 Binding point is marked with a grounding symbol on the botto...

Page 5: ...eaththeunit foruseonDHWandheatingsystemswithconcealedpipeinstallations Heat exchanger for DHW heating The substation is based on a brazed highly efficient plate heat exchanger which is controlled by a...

Page 6: ...ax 8mm screws expansion bolts or similar 2 Close all shut off valves before the water heater is connected to the household piping 3 Tighten all pipe connections as they may have loosened during trans...

Page 7: ...afety set for mounting underneath substation 145H3001 Actuator TWA Q for zone valve Supplement for stainless steel HEX XB 06H 1 26StS 26 pl Supplement for stainless steel HEX XB 06H 1 40StS 40 pl 5 MA...

Page 8: ...Akva Lux II TDv DH Return DHW DCW DH Supply 2 Plate heat exchanger DHW 4 Differential pressure controller AVPL 5 Strainer 38 DHW controller PTC2 P 40 Danfoss FJVR for bypass circ 52 Zone valve RA C D...

Page 9: ...a Lux II TDv substations can be removed without using tools Take hold of the air duct in the top and bottom of the front insulation section and pull carefully forward until the front insulation sectio...

Page 10: ...ted on the circulation pipe of the substation Seepages10to12forinformationaboutpreparation ofsubstationforandconnectiontotheDHWrecirculationsystem Remember always to mount circulation pump and non ret...

Page 11: ...controller Fig 3 Mount circulation hose end B1 in controller Fig 4 Unscrew the 3 screws on locking rail Fig 5 Demount locking rail Fig 6 Demount support rail as shown Fig 7 GB Place bracket C on suppo...

Page 12: ...port rail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of un...

Page 13: ...ems with recirculation For mounting underneath unit Please note that the safety kit shown can be used on different unit types and that there may therefore be components pipe pieces that should not be...

Page 14: ...just ment is made according to the instructions in this manual Commissioning Commission the substation in accordance with the instruction manual Heating circuit Differential Pressure Controller The di...

Page 15: ...s controlled by the room thermostat and radiator thermostats Please note that the room thermostat keeps the temperature at a constant level in the whole apartment according to the set room parameters...

Page 16: ...Thetemperature must never exceed 55 C to prevent limescale deposits building up in the water heater Bypass thermostat default As a standard the substation is equipped with a bypass thermostat Danfoss...

Page 17: ...cause aerated water is used on the secondary side If it becomes necessary to clean the exchanger with acid this canbedoneasshownonthedrawingtotheright Brazedplateheat exchangers can withstand rinsing...

Page 18: ...e component in question Clean all dirt filters strainers in the substation Replace any filters that are not intact Check that any electrical cables are in ser viceable condition and that it is possibl...

Page 19: ...ctions Poor cooling Insufficient heating surface radiators too small compared to the total heating requirement of the building Poor utilisation of the existing heating sursurface Increase total heatin...

Page 20: ...in the pump housing No hot water Dirt strainer in the district heating sup ply line clogged Defective DHW controller Defective sensor PTC2 Clean the dirt strainer Check controller settings You may con...

Page 21: ...eat exchanger Short circuited heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Discoloured water for a longer period Short circuited heat exchang...

Page 22: ...22 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv 14 EU DECLARATION OF CONFORMITY...

Page 23: ...ions and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks before del...

Page 24: ...o 0 5 Good corrosion resistance o Corrosion could happen when more parameters are evaluated with o o Risk of corrosion Use is not recommended Hardness ration limits defined per experience and interna...

Page 25: ...25 25 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Page 26: ...26 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Page 27: ...27 27 Danfoss District Energy 145X2085 AQ428255318526en 010101 DKDHR Instructions Akva Lux II TDv...

Page 28: ...28 DKDHR 145X2085 AQ428255318526en 010101 Danfoss District Energy Instructions Akva Lux II TDv...

Reviews: