Danfoss District Energy 

VI.GP.N2.02 

DKDHR

Instructions   Water 

Heaters

5.0  Easy start-up

5.1 Connections, Dimensioned sketches and  Start-up

Type A 

Follow the below start-up instructions for easy start-up.

Water heater types:

A.  Akva Lux / Les II - fully insulated water heater with PTC2+P

B.  Akva Lux II GW - water heater with gasketed heat exchanger and 

PTC2+P

C.  Akva Vita II with PM2+P

Connections:

1.  Domestic cold water (DCW) inlet

2.  Domestic hot water (DHW) outlet

3.  District heating (DH) supply

4.  DIstrict heating (DH) return

Connect the water heater to the household piping according to the labels 

placed on the water heater as well as the instructions in this manual.

If the household piping includes hot water recirculation the substation 

must be connected to the recirculation piping. 

Switching to recirculation is possible from a constructional point of view, 

requiring only an additional circulation set. 

The components for DHW 

circulation are not part of the delivery and must be ordered separately 

and mounted on site. See page 9-13 for further information about 

recirculation.

It is to be recommended to prepare the substation for recirculation before 

mounting it on the wall.

Start-up

01.  Fix the water heater on a solid wall with two strong bolts, screws, 

expansion plugs or the like. 

02.  Close all shut-off valves, before the water heater is connected to 

the household piping. 

03.  IMPORTANT! Tighten 

all

 connections, as vibrations during trans-

port and handling may have caused leaks. 

04.  For systems with safety valve, a discharge outlet must be estab-

lished in compliance with local regulations. 

05.  If the household plumbing system includes hot water recirculation 

the water heater must be connected to the hot water recirculation 

system. 

Remember always to mount circulation pump and non-

return valve on the circulation pipe and to mount safety valve 

on the DCW inlet. 

The pump must be installed so that the pump is 

pumping water towards the water heater. The pump must be con-

nected to power supply, 

but do not switch on the pump

.

06.  Carefully open the ball valve on DH supply. Subsequently open the 

remaining ball valves. 

07.  Check the water heater and the household piping carefully for any 

leaks. 

08.  Perform pressure testing of the household installation in compli-

ance with local regulations. 

09.  Switch on circulation pump (if any). 

10.  Finally adjust the water heater according to the enclosed installa-

tion instructions. 

IMPORTANT! Heating and cooling of the system may cause leaks. 

Therefore tightening of all connections may be necessary after 

commencement of operation.

Type B 

Type C

1

3

4

1

2

3

4

306

80

60

60

190

40

200

145,5

403

463

300

80 60

60

240

40

300

430

463

25

45-35

55-65

200

25

25

80 60

60

40

160

255

391

420

200

55

2

!

!

4

3

2

1

Summary of Contents for Akva Les II

Page 1: ...GW Diagram example measurements and main components 6 9 0 Akva Vita II Diagram example measurements and main components 7 10 0 Mounting 8 10 1 Test and connections 8 10 2 Systems with domestic hot wat...

Page 2: ...qualization of potentials should be effected according to local regulations Warning of hot surfaces Parts of the water heater may become hot and hot surfaces can cause serious burns Please be extremel...

Page 3: ...ose all shut off valves before the water heater is connected to the household piping 03 IMPORTANT Tighten all connections as vibrations during trans port and handling may have caused leaks 04 For syst...

Page 4: ...ion cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instr...

Page 5: ...8 Insulation cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose...

Page 6: ...6 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instruction on page 14 Ac...

Page 7: ...ples 5 Brushed stainless steel cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instructions...

Page 8: ...valve on the DCWinlet The pump must be installed so that the pump is pumping water towards the water heater If a time controlled pump is used it is to be recommended that the circulation water temper...

Page 9: ...ater towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 in controll...

Page 10: ...ail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of union nu...

Page 11: ...towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 as shown Fig 4...

Page 12: ...s shown Fig 8 Demount capillary tube from T piece Fig 9 Demount capillary tube from bypass thermostat Fig 10 Mount M8 x 1 screw plug F in T piece Fig 11 Fit new capillary tube G on nipple B by means o...

Page 13: ...and Akva Les II are equipped with a by pass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermostat in pos 3 Ifthew...

Page 14: ...rculation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIGWisequippedwithabypassthermostat Danfoss FJVR 2 which ensures that hot water is produced immedi ately when tapping starts It is r...

Page 15: ...ault As a standard the Akva Vita II is equipped with a bypass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermosta...

Page 16: ...heatexchangersweakinhibited acid solutions e g 5 formic acetic or phosphoric acid may be used Deacidificationofgasketedplateheatexhanger AkvaLuxIIGW See page 16 Measuresaftermaintenancework After main...

Page 17: ...t and be able to dissolve the fouling calification on the plates Great care must be taken to select a proper cleaning solution that does not damage plates or gaskets Example of cleaning 1 Drain produc...

Page 18: ...l compressed dimension The bolts must not be slackened or tightened indiscriminately They must be loosened tightened alternately on the left and right side and in a crosswise pattern Loosening and tig...

Page 19: ...the household piping REMEMBER to check all the mixer taps in the house Replace mixer tap or non return valve only Not enough pressure on the hot water Strainer in cold water meter or in the cold wate...

Page 20: ...e during tapping Calified heat exchanger Short circuiting of defective heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Poor cooling Calified hea...

Page 21: ...e used in accordance with our instructions EU Directives EMC Directive 2004 108 EEC EN 61000 6 1 2007 Electromagnetic compatibility Generic standard Immunity for residential commercial and light indus...

Page 22: ...technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for...

Page 23: ...23 23 Danfoss District Energy VI GP N2 02 DKDHR Instructions Water Heaters...

Page 24: ...Produced by Danfoss Redan A S 02 2014 VI GP N2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: