15.0 Trouble shooting 

If operating disturbances occur, the following basic features 

should be checked before carrying out actual troubleshooting:

•  there is pressure on the system. - see manometer on system

•  the system is connected correctly,

•  the system is connected to electricity - pump and automatic

•  the strainer on the district heating supply is clean

•  the district heating supply temperature is at normal level 

•  the differential pressure is higher than or equal to the normal /

      local differential pressure on the district heating network. - If in

      doubt, ask the district heating plant.

15.1 Troubleshooting - Domestic hot water

Problem

Possible cause

Solution

Variations in temperature

Non-return valve on the circulation line 

defective (leads to mixing - and the 

circulation water pipes become cold dur-

ing tapping).

Replace non-return valve.

Low temperature / variations in tem-

perature at the draining points

Non-return valve in thermostatic mixer 

tap in the bathroom defective - leads to 

mixing of cold and hot water-. Note that 

variations in temperature may occur at 

other draining points/water taps in the 

household piping!

REMEMBER, to check all the mixer taps in 

the house!

Replace mixer tap, or non-return valve 

only.

Not enough pressure on the hot water

Strainer in cold water meter or in the 

cold water supply line clogged .

Clean strainer (cold water meter possibly 

in consulation with the water supply 

company).

Long waiting time

Circulation pump out of operation - (not 

part of the dly).

Check whether the pump is running - 

whether the pump is receiving power. 

control that there is no air in the pump 

housing - see pump manual.

No domestic hot water

Defective or wrongly set differential 

pressure controller (not part of the dly).

Strainer on DH supply clogged.

Check the functions of the differential 

pressure controller - clean valve seat and 

capillary tube if required.

Clean strainer.

DHW temperature too low 

See above.

Non-return valve on the circulation line 

defective (leads to mixing - and the 

circulation water pipes become cold du-

ring tapping).

See above.

Replace non-return valve.

DHW temperature too high

Defective DHW controller.

Check the functions of the controller, 

and replace if required.

Declining temperature during tapping

Defective or wrongly set differential 

pressure controller (not part of the dly).

Air in capillary tubes

Check the functions of the differential 

pressure controller - clean valve seat and 

capillary tubes if required.

Air and rinse capillary tubes.

Summary of Contents for Akva Les II

Page 1: ...GW Diagram example measurements and main components 6 9 0 Akva Vita II Diagram example measurements and main components 7 10 0 Mounting 8 10 1 Test and connections 8 10 2 Systems with domestic hot wat...

Page 2: ...qualization of potentials should be effected according to local regulations Warning of hot surfaces Parts of the water heater may become hot and hot surfaces can cause serious burns Please be extremel...

Page 3: ...ose all shut off valves before the water heater is connected to the household piping 03 IMPORTANT Tighten all connections as vibrations during trans port and handling may have caused leaks 04 For syst...

Page 4: ...ion cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instr...

Page 5: ...8 Insulation cover front part 9 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose...

Page 6: ...6 White lacquered cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instruction on page 14 Ac...

Page 7: ...ples 5 Brushed stainless steel cover optional equipment F Filter on cold water inlet C The water heater is prepared for DHW circulation Fittings for DHW connection are supplied loose See instructions...

Page 8: ...valve on the DCWinlet The pump must be installed so that the pump is pumping water towards the water heater If a time controlled pump is used it is to be recommended that the circulation water temper...

Page 9: ...ater towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 in controll...

Page 10: ...ail Fig 14 Fit new capillary tube G on nipple B by means of union nut and cutting ring H Tighten with single end wrench Fig 15 Fit the other end of the capillary tube G on T piece by means of union nu...

Page 11: ...towards the water heater This not part of the circulation set Fig 1 Demount plugs 6 mm Allen key from controller Fig 2 Mount nipple A in controller Fig 3 Mount circulation hose end B1 as shown Fig 4...

Page 12: ...s shown Fig 8 Demount capillary tube from T piece Fig 9 Demount capillary tube from bypass thermostat Fig 10 Mount M8 x 1 screw plug F in T piece Fig 11 Fit new capillary tube G on nipple B by means o...

Page 13: ...and Akva Les II are equipped with a by pass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermostat in pos 3 Ifthew...

Page 14: ...rculation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIGWisequippedwithabypassthermostat Danfoss FJVR 2 which ensures that hot water is produced immedi ately when tapping starts It is r...

Page 15: ...ault As a standard the Akva Vita II is equipped with a bypass thermostat Danfoss FJVR 2 which ensures that hot water is produced immedia tely when tapping starts It is recommended to set the thermosta...

Page 16: ...heatexchangersweakinhibited acid solutions e g 5 formic acetic or phosphoric acid may be used Deacidificationofgasketedplateheatexhanger AkvaLuxIIGW See page 16 Measuresaftermaintenancework After main...

Page 17: ...t and be able to dissolve the fouling calification on the plates Great care must be taken to select a proper cleaning solution that does not damage plates or gaskets Example of cleaning 1 Drain produc...

Page 18: ...l compressed dimension The bolts must not be slackened or tightened indiscriminately They must be loosened tightened alternately on the left and right side and in a crosswise pattern Loosening and tig...

Page 19: ...the household piping REMEMBER to check all the mixer taps in the house Replace mixer tap or non return valve only Not enough pressure on the hot water Strainer in cold water meter or in the cold wate...

Page 20: ...e during tapping Calified heat exchanger Short circuiting of defective heat exchanger Clean heat exchanger with acid solution or replace heat exchanger Replace heat exchanger Poor cooling Calified hea...

Page 21: ...e used in accordance with our instructions EU Directives EMC Directive 2004 108 EEC EN 61000 6 1 2007 Electromagnetic compatibility Generic standard Immunity for residential commercial and light indus...

Page 22: ...technical regulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for...

Page 23: ...23 23 Danfoss District Energy VI GP N2 02 DKDHR Instructions Water Heaters...

Page 24: ...Produced by Danfoss Redan A S 02 2014 VI GP N2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: