background image

12

Instructions for installation and use 

TD & S substations

DKDHR 

VI.GP.U2.02 

Danfoss District Energy 

11.  Installation instructions – specially for S substations

Controller ECL 210

Supply voltage: 

230 V AC – 50 Hz

Power consumption:  5 VA

Actuator AMV 150 

Supply voltage: 

230 V AC – 50 Hz

Power consumption:  8 VA

Pump (Wilo Yonos Para / Alpha2)

Supply voltage: 

230 V AC – 50/60 Hz

Power consumption:  Max. 40 Watt / max. 25 Watt

Electrical connection (only for S substations)

The electrical connection of the unit must be performed by authorised 

personnel. 

The unit is to be connected to a 230 V AC mains power supply. 

The power supply/connection must be carried out in accordance 

with the applicable regulations and instructions. 

The substation must be connected to an external switch so that it 

can be disconnected in connection with maintenance, cleaning and 

repairs or in the event of an emergency.

S substations are available with Danfoss ECL 210 as extra equipment. 

Installation of outdoor sensor (only for S substations ordered 

with Danfoss ECL)

The outdoor temperature sensor is delivered separately with the 

substation.

It is to be mounted on site as shown in the drawings to the right.

Always mount the sensor on the coldest side of the building (normally 

the north side).

It must not be exposed to morning sunlight, and must not be po-

sitioned above windows, doors, ventilation ducts, balconies under 

overhanging roof sections, or close to any other heat source.

Installation height: approx. 2.5 m above ground level.

Temperature range: -50 to 50° C

Electrical connection

The cables can be connected to the sensor in any order.

Connection cable: 2 x 0.4 - 1.5 mm² 

Connect the cable ends in terminals 29 and 30 in the ECL 210 

controller.

(For ECL 110 - terminals 1 and 2).

Connections for radiator circuit

S substations are fitted with connections for direct connection of a 

radiator circuit before the mixing loop. 

The connections are typically used to connect one or more radiators 

that are not to be regulated by the mixing loop.

The connections are positioned as shown in the photo to the right. 

The connections are sealed with blind plates, which you must remove 

if you wish to use the connections. 

Connections with a red arrow are for radiator supply, while connec-

tions with a blue arrow are for radiator return.

Connections for radiator circuit – (cut-out in insulation cover)

On fully insulated system types, it is necessary to cut a section out 

of the insulation cover (for the connection pipes to the connection 

pieces) as shown in the photo to the right.

Summary of Contents for Akva Les II S

Page 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Vita II TD S Akva Lux II Akva Les II TD S Instructions for installation and use...

Page 2: ...ING STARTED 10 10 Installation instructions general 11 11 Installation instructions specially for S substations 12 12 Installation instructions recirculation connection 13 13 Adjustment and commission...

Page 3: ...Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer DHW Dirt strainer Sensor pocket White painted cover Filter on cold water supply The unit has been p...

Page 4: ...tic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer hot water Dirt strainer Sensor pocket White painte...

Page 5: ...exchanger brazed domestic hot water Domestic hot water controller PM2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor hea...

Page 6: ...Domestic hot water controller PTC2 P Bypass thermostat Danfoss FJVR Differential pressure controller AVPL Safety valve Fitting piece for meter Thermometer floor heating thermometer domestic hot water...

Page 7: ...s and an excessively high return temperature in the district heating circuit poor cooling of the district heating water Cooling i e the difference between the supply and return temperature of the dist...

Page 8: ...ccur noise in the radiator thermostats or poor regulation capacity it may be necessary to reset the differential pressure controller to a lower operating pressure We suggest that you contact your loca...

Page 9: ...mperature in the district heating network can be up to 120 C and the operating pressure can be up to 16 bar Thismayresultinariskofscaldingfromtouchingthesubstationand fromoutflowofthemedium Exceedingt...

Page 10: ...tructions if necessary 3 NB Tighten all pipe connections as they may have loosened during transport and handling 4 On systems that feature a safety valve establish a drain con nection in compliance wi...

Page 11: ...Before filling the system with water retighten all the pipe connec tions because vibrations and shocks during transport and handling may have caused leaks Once the system has been filled with water ti...

Page 12: ...he right Alwaysmountthesensoronthecoldestsideofthebuilding normally the north side It must not be exposed to morning sunlight and must not be po sitioned above windows doors ventilation ducts balconie...

Page 13: ...ion pump outside the substation is stopped for a protracted period we recommend shutting off the by pass thermostat for the same period NB Please note that substations fitted with Danfoss AVE expansio...

Page 14: ...Danfoss FJVR bypass thermostat Fig 2 so that when water is tapped the water heater immediately starts to produce hot water We re commend setting of the thermostat in pos 3 If you have to wait a long t...

Page 15: ...oss FJVRbypassthermostat Fig 2 sothatwhenwateristapped thewater heaterimmediatelystartstoproducehotwater Werecommendsetting ofthethermostatinpos 3 Ifyouhavetowaitalongtime i e morethan 20 sec for hot...

Page 16: ...time i e more than 20 sec for hot water it may be necessary to position the thermostat higher than pos 3 If you want to avoid waiting time altogether you will need to set up domestic hot water recirc...

Page 17: ...mmediatelystartstoproducehotwater Werecommendsetting the thermostat to pos 3 If you have to wait a long time i e more than 20 sec for the hot water it may be necessary to set the thermostat to a posit...

Page 18: ...ating conditions Indicative supply temperatures 40 C when the outdoor temperature is 10 C 55 C when the outdoor temperature is 0 C 65 C when the outdoor temperature is 10 C It is important to set the...

Page 19: ...power consumption For floor heating systems and old radiator set ups with large pipes and radiators turn the red switch to the right constant curve and set it to Max pos initially Then reduce the pre...

Page 20: ...build up in plate heat ex changers for domestic hot water on account of the large temperature fluctuations and because aerated water is used on the secondary side If it becomes necessary to clean the...

Page 21: ...the pipe connections Check that the safety valve on the cold water supply is functioning correctly Check the functionality by turning the lever on the safety valve Check that all components are intact...

Page 22: ...g Automatic components controller incorrectly adjusted or defective or possibly a power outage The pump is not working The pump is set at a step that is too low not all system types Air pockets in the...

Page 23: ...ivery Check whether the pump is running and whether there is a power supply to the pump Make sure that there is no air in the pump housing No hot water Dirt strainer in the district heating sup ply li...

Page 24: ...y EN 61000 6 2 2005 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromagnetic compatibility Generic standard Emission for residential commercial and light indu...

Page 25: ...gulations and the applicable legislation in every respect Installation and commissioning must only be performed by trained authorised personnel The substation is checked in the factory for leaks befor...

Page 26: ...26 DKDHR VI GP U2 02 Danfoss District Energy...

Page 27: ...27 27 Danfoss District Energy VI GP U2 02 DKDHR...

Page 28: ...Produced by Danfoss Redan A S 06 2012 VI GP U2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: