© Danfoss A/S (AC-MCI/MWA), 2012-05
DKRCI.PD.SC0.C3.02 / 520H5687 13
Liquid Level Sensor, AKS 4100/4100U
• Connect the device to the power supply
(see the product instruction for detail on
electrical installation/connection).
• Press
3 times.
• Press
• Press
or to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to confirm.
• Press
(YES) to confirm
• Press
to change GAS EPS.R.
(Select the correct value from the tables
on page 16)
Press to change cursor-
position.
Press to decrease the value or to
increase the value.
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
•
Press to confirm.
• Press
to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press
to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press
to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
•
Press to confirm.
• Press
or to select between
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
You have the possibility of checking your
settings by pressing twice.
Press to return to default screen.
Quick Setup (all values below are only examples)
• Connect the device to the power supply
• Press
3 times.
• Press
• Press
or to select between SINGLE
or COAXIAL. Choose COAXIAL and
press to confirm.
• Press
(NO) to confirm
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
PROBE TYPE
SINGLE CABLE
• Press
to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press
to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press
to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
•
Press to confirm.
• Press
or to select between
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
AKS 4100
GAS EPS R ?
001.000
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK START
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
When CO
2
is used:
For all other refrigerants:
AKS 4100
LIQUID CO2 ?
YES NO
AKS 4100
LIQUID CO2 ?
YES NO
AKS 4100
SCALE 4 mA
04946 mm
AKS 4100
SCALE 20 mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm
AKS 4100
1.0.0
QUICK START
AKS 4100
PROBE LENGTH
05000 mm
COAXIAL version
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
QUICK SETUP ?
YES NO
AKS 4100
COAXIAL
2200 mm
(0 %) 4 mA
1900 mm
(100 %) 20 mA
70 mm