© Danfoss A/S (AC-MCI/MWA), 2012-05
DKRCI.PD.SC0.C3.02 / 520H5687 11
Liquid Level Sensor, AKS 4100/4100U
Technical data
(continued)
Material
Housing
Aluminium
Coaxial (segmented)
Standard: Stainless steel (1.4404 / 316L)
Single cable
Standard: Stainless steel (1.4401 / 316)
Process fitting
Standard: Stainless steel (1.4404 / 316L)
Gaskets
EPDM (-50...+150°C / -58...+300°F)
Cable gland
Plastic (black)
Process connections
Thread:
Single cable Ø2 mm / 0.08¨
AKS 4100: G1 inch pipe thread. Aluminium gasket included
AKS 4100U: ¾ in. NPT
Coaxial
AKS 4100: G1 inch pipe thread. Aluminium gasket included
AKS 4100U: ¾ in. NPT
Electrical connections
Power supply
Terminals output:
14-30 V d.c. Min./Max. Value for an output of 22 mA at the terminal.
Ambient temperature limitations:
-40°C/+80°C(–40°F / +176°F) : 16-30 V d.c.
-20°C/+80°C(–4°F / +176°F) : 14-30 V d.c.
Current output load
RL [Ω] ≤ ((Uext -14 V)/20 mA).
– Default (Error output set to 3.6 mA)
RL [Ω] ≤ ((Uext -14 V)/22 mA).
– (Error output set to 22 mA)
Cable gland
AKS 4100: PG 13, M20×1.5 ; (cable diameter: 6-8 mm (0.24-0.31in.)
AKS 4100U: ½ in. NPT
Cable entry capacity (terminal)
0.5-1.5 mm
2
(~20-15 AWG)
Input and output
Current output:
Output signal
4…20 mA or 3.8…20.5 mA acc. to NAMUR NE 43
Resolution
±3 μA
Temperature drift
Typically 75 ppm/K
Error signal
High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43; Hold (frozen value - not available
with NAMURNE 43 compliant output.
Approvals and certification
CE
This device fufills the statutory requirements of the EMC directives. The manufacturer
certifies successful testing of the product by applying the CE mark.
Other standards and approvals:
EMC
EMC Directives 2004 / 108 / EC and 93 / 68 / EEC in conjunction with
EN 61326-1 (2006) and EN 61326-2-3 (2006). The device conforms to these standards if :
- the device has a coaxial probe or
- the device has a single probe that is installed in a metallic tank.
LVD
Low-Voltage Directives 2006 / 95 / EC and 93 / 68 / EEC in conjunction with
EN 61010-1 (2001)
NAMUR
NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and
Laboratory Control Equipment
NAMUR NE 43 Standardization of the Signal Level for the Failure Information of
Digital Transmitters
Minimum power supply voltage
Use this graph to find the minimum power supply voltage for a given current output load:
Minimum power supply voltage for an output of 22mA at the terminal
Power supply U [VDC]
Current output load
R
L
[
Ω
]