Please observe!

  If actual refrigerant is different from R 717 (NH

3

),  

  actual refrigerant must be entered the electronic top  

  part.

Refrigerant setting

The setting may be carried out before the level transmitter is 

mounted on the plant.

1.  Push the calibration pushbutton and keep it pressed while 

  24 V a.c. is connected.

  - Now release the switch.

NOTE!

This sequence 

must

 be observed. If the supply  

voltage is connected before the calibration  

 pushbutton is activated, the signal damping will be 

changed.

2.  Release the calibration pushbutton. Observe the present  

  refrigerant setting and measure the 4-20 mA output signal.
  1   flash of Green LED - output signal is ~ 5 mA = R717 

   

(factory setting)

  2   flashes of Green LED - output signal is ~ 6 mA = R22 

  3  flashes of Green LED - output signal is ~ 7 mA = R404A 

  4  flashes of Green LED - output signal is ~ 8 mA = R134a

  5  flashes of Green LED - output signal is ~ 9 mA = R744

3.  Activate the calibration pushbutton to select required  

  refrigerant. Each activating will cause AKS 41 / 41U to step to  

  next refrigerant according to below sequence:
  ~ 5 mA = R717 (factory setting)

  ~ 6 mA = R22  

  ~ 7 mA = R404A 

  ~ 8 mA = R134a

  ~ 9 mA = R744
4.  When the current corresponds to the required refrigerant, wait  

  10 seconds until the green LED is constant ON (not flashing).  

  This indicates that the required refrigerant has been selected.
5.  To leave the setting mode isolate the voltage supply to the  

  level transmitter.
Go through step 1, 2 and 5 if you wish to control the setting.

Calibration

If operating the liquid level to min. and max. level is possible:

Adjusting the min. /max. calibration points:

Min. calibration:

1.  Bring the refrigerant liquid level to desired minimum level.
2.  Press the calibration pushbutton and keep it activated in 

  approx. 5 seconds, until green LED stopps flashing.
3.   Activate, within the next 10 seconds, the calibration    

  pushbutton once (If calibration pushbutton is not activated  

  within 10 seconds,  it will  automatically leave calibration  

  mode and return to normal operation) 

Green LED is ON in a few seconds, and then flashing.

Output is now 4 mA and AKS 41 / 41U is in normal operation

The electronic top part must always be calibrated when mounted 

on the actual sensor part, if the actual sensor part is not a AKS 41-

15 (1500 mm)

If it is not possible to adjust max. liquid level:

Please note!

 

The min. level must be calibrated before the max. level. 

If the min. level corresponds to AKS 41 being completely  

free of the liquid, the standpipe must be drained and 

the procedure described above under min. calibration  

performed.

Actual liquid level must be determined and the corresponding 

mA ouput must be calculated and entered.

Example:

If liquid level cover about 50% of the entire AKS 41 sensor, 

then 12 mA output must be entered: [50% of (20-4)] + 4 = 12 mA.

Min. calibration when minimum refrigerant level must be 

different from 4 mA: 

1.  Bring the refrigerant liquid level to desired minimum level.
2.  Press the calibration pushbutton and keep it activated in  

  approx. 5 seconds, until green LED stopps flashing.
3.  Activate, within the next 10 seconds, the calibration  

  pushbutton once and keep it activated. (If calibration 

   pushbutton is not activated within 10 seconds, it will    

  automatically leave calibration mode and return to normal  

  operation)
4.  Observe the output mA signal increasing fast starting at 4 mA.
5.  Release the calibration pushbutton when the output signal is  

  approx. 0.5 mA from the desired point.
6.  All the next activations will increase the output signal by  

  approx. 0.05 mA
7.  Approx. 10 seconds after the latest activation the LED starts 

   flashing 
8.  Output now corresponds to the value measured at the   

  latest activation.

Max. calibration:

1.  Bring the refrigerant liquid level to desired maximum level.
2.  Press the calibration pushbutton and keep it activated in  

  approx. 5 seconds, until green LED stopps flashing.
3.  Activate, within the next 10 seconds, the calibration push- 

  button two times, with 1 second in between.  (If calibration  

  pushbutton is not activated within 10 seconds, it will  

  automatic leave calibration mode and return to normal  

  operation) 

Green LED is ON in a few seconds, and then flashing. 

Output is now 20 mA and AKS 41 / 41U is in normal operation

50%

Summary of Contents for AKS 41

Page 1: ...ng og m l 4 20 mA udgangssignalet Gr n LED blinker 1 gang udgangssignalet er 5 mA R 717 fabriksindstilling Gr n LED blinker 2 gange udgangssignalet er 6 mA R 22 Gr n LED blinker 3 gange udgangssignale...

Page 2: ...A 7 Ca 10 sekunder efter sidste aktivering begynder LED en at blinke 8 Udgangsv rdien svarer nu til den v rdi der blev m lt ved sidste aktivering Maks kalibrering n r udgangsv rdien ved maks k lemidde...

Page 3: ...eturn to normal operation Green LED is ON in a few seconds and then flashing Output is now 4 mA and AKS 41 41U is in normal operation The electronic top part must always be calibrated when mounted on...

Page 4: ...gssignal ist 7 mA R 404A 4 x Aufleuchten der gr nen LED Ausgangssignal ist 8 mA R 134a 5 x Aufleuchten der gr nen LED Ausgangssignal ist 9 mA R 744 3 Die Kalibrier Drucktaste aktivieren um das gew nsc...

Page 5: ...tel Obergrenze von 20 mA abweichen soll 1 Das K ltemittelniveau auf die gew nschte Untergrenze bringen 2 Die Kalibrier Drucktaste bet tigen und ca 5 Sekunden gedr ckt halten bis die gr ne LED zu blink...

Page 6: ...e La DEL verte s allume pendant quelques secondes puis se met clignoter La sortie est d sormais de 4 mA et l AKS 41 ou 41U est en mode d exploitation normale Calibrage du maximum 1 Amener le niveau du...

Page 7: ...le bouton poussoir de calibrage et le tenir enfonc pendant 5 secondes environ jusqu ce que la DEL verte s arr te de clignoter 3 Dans un d lai de 10 secondes appuyer deux fois sur le bouton de calibrag...

Page 8: ...D comienza a parpadear 8 La salida ahora corresponde al valor medido en la ltima activaci n La calibraci n m xima cuando el nivel de refrigerante se encuentra al m ximo debe ser diferente a 20 mA 1 Aj...

Reviews: