User Guide 

|

 Optyma™ control AK-RC 111 single phase

© Danfoss | DCS (vt) | 2020.03

BC309238530328en-000101 | 9

4.9  Level 2 programming

 

(installer level)

4.10  List of Level 2 variables

 

(installer level)

To access the second programming level press the UP (

) and DOWN (

) keys and the LIGHT key 

simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1.  Select the variable to be modified by pressing the UP (

) and DOWN (

) keys.

  When the parameter has been selected it is possible to:
2.  View the setting by pressing the SET key.
3.  Modify the setting by holding the SET key down and pressing the (

) or (

) key.

4.  When configuration settings have been completed you can exit the menu by pressing the (

) and 

(

) keys simultaneously and keeping them pressed until the room temperature reappears.

5.  Changes are saved automatically when you exit the configuration menu.
6. Press the STAND-BY key to enable electronic control.

Variables Meaning

Value

Default

F3

Fan status with compressor off

0 = Fans run continuously 

1 = Fans only run when

compressor is working 

2 = Fans disabled

1

F4

Fan pause during defrost

0 = Fans run during defrost

1 = Fans do not run during 

defrost

1

F6

Evaporator fans activation for air recirculation.

The fans activate for a time defined by F7 if they have 

not started working for the F6 time. If activation time 

coincides with the defrosting time, end of defrosting 

is awaited.

0 – 240 min

0 = (function not activated)

0 min

F7

Evaporator fans duration for air recirculation.

Fans working time for F6

0 – 240 sec

10 sec

dE  

Sensor presence

If the evaporator sensor is disabled defrosts are 

carried out cyclically with period d0: defrosting ends 

when an external device trips and closes the remote 

defrost contact or when time 

d3

 expires.

0 = evaporator sensor present

1 = no evaporator sensor 

0

d1 

Defrost type

, cycle inversion (hot gas) or with heater 

elements

0 = heating element

1 = hot gas

2 = heater with

 temperature control

0

dPo

Defrost at Power On

0 = disabled

1 = defrost at power-on

(if possible)

0

dSE

Smart defrost

0 = disabled

1 = enabled

0

dSt

Smart defrost Setpoint (if dSE=1)

The counting of the time between the defrost is 

incremented only if the compressor is ON and the 

evaporator temperature is less than dSt.

-30 – 30 °C

1 °C

dFd

Display viewing during Defrost

0 = current temperature

1 = temperature at the

 start of the defrost

2 = “DEF”

1

Ad

Modbus Network address

0 – 247

0

Bdr

Modbus baudrate

0 = 300 baud

1 = 600 baud 

2 = 1200 baud

3 = 2400 baud

4 = 4800 baud

5 = 9600 baud

6 = 14400 baud

7 = 19200 baud

8 = 38400 baud

8

Prt

Modbus parity check

0 = none

1 = even

2 = odd

1

Ald

Minimum and maximum temperature

signalling and alarm display delay

0 – 240 min

120 min

C1

Minimum time between shutdown and 

subsequent 

switching on of the compressor.

0 – 15 min

0 min

CAL

Cold room sensor value correction

-10 – 10 °C

0 °C

Summary of Contents for AK-RC 111

Page 1: ...User Guide Optyma control AK RC 111 single phase...

Page 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Page 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Page 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Page 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Page 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Page 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Page 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Page 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Page 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Page 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Page 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Page 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Page 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Page 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Page 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...

Reviews: