User Guide 

|

 Optyma™ control AK-RC 111 single phase

10 | BC309238530328en-000101

© Danfoss | DCS (vt) | 2020.03

CE1

Duration of compressor ON time in the case of 

faulty ambient probe

(emergency mode). 

If CE1=0 the emergency mode in the presence of 

error E0 remains disabled, the compressor remains 

off and defrosting is prevented in order to conserve 

the remaining cold.

0 – 240 min

0 = disabled

0 min

CE2

Duration of compressor OFF time in the case of 

faulty ambient probe 

(emergency mode).

5 – 240 min

5 min

doC

Compressor safety time for door switch:

when the door is opened the evaporator fans shut 

down and the compressor will continue working for 

time 

doC

, after which it will shut down.

0 – 5 min

0 min

tdo

Compressor restart time after door opening. 

when 

the door is opened and after tdo time, it’s setted back 

the normal functioning giving door open alarm (Ed)

If the door switch is closed and the light stays on for 

a longer time than tdo light cell alarm is signaled 

(E9). With tdo=0 the parameter is disabled.

0 – 240 min

0 = disabled

0 min

Fst

FAN shutdown TEMPERATURE

The fans will stop if the temperature value read by 

the evaporator sensor is higher than this value.

-45 – 99 °C

99 °C

Fd

Fst differential

1 – 10 °C

2 °C

LSE

Minimum value attributable to setpoint.

-45 – (HSE-1) °C

-45 °C

HSE

Maximum value attributable to setpoint.

(LSE+1) – 99 °C

99 °C

AU1

Auxiliary/alarm relay 1 control

-6 (NC) = relay de-energised 

during stand-by

-5 (NC) = Contact for casing 

element control (AUX 

relay closed with 

compressor output 

inactive).

-4 (NC) = pump down function 

(NC, see CHAP 5.16)

-3 (NC) = automatic auxiliary 

relay managed by StA 

temp. setting with 2°C 

differential (NC)

-2 (NC) = manual auxiliary relay 

controlled via AUX key 

(NC)

-1 (NC) = alarm relay (NC)

 0 = relay deactivated

 1 (NO) = alarm relay (NO)

 2 (NO) =manual auxiliary relay 

controlled via AUX key 

(NO)

 3 (NO) = automatic auxiliary 

relay managed by StA 

temp. setting with 2°C 

differential (NO)

 4 (NO) = pump down function 

(NO, see CHAP 5.16)

 5 (NO) = free voltage contact for 

condensing unit (AUX 

relay and compressor 

relay in parallel)

 6 (NO) = relay excited during 

stand-by

-1

AU2

Auxiliary/alarm relay 2 control

(like AU1 )

5

StA

Temperature setting for auxiliary relay

-45 – 99 °C

0 °C

nSC

Correction factor for the SET button during night 

operation 

(energy saving)

(with In1 or In2 = 8 or -8) 

During night operation the control set is: 

Set Control = Set + nSC 

In night mode decimal point flashes.

-20 – 20 °C

0 °C

Summary of Contents for AK-RC 111

Page 1: ...User Guide Optyma control AK RC 111 single phase...

Page 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Page 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Page 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Page 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Page 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Page 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Page 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Page 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Page 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Page 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Page 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Page 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Page 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Page 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Page 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...

Reviews: